Hoval Hoval Energy Management Modbus TCP template

Hoval Energy Management

Manages Hoval heat pump energy via Smart Grid offsets and PV integration

This template connects Hoval heat pumps running TopTronic E to ModbusCloud via Modbus TCP or Modbus RTU. It reads temperatures, energy totals, COP, and operating states while providing Smart Grid trigger and setpoint offsets for DHW, heating buffer, and room temperature across up to three heating circuits.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
54, read and write
Brand
Hoval
Key readings
Outdoor and flow temperatures (HC1-HC3) · DHW and buffer tank temperatures · Electrical and thermal power/energy totals · COP and annual efficiency factor · Operating hours and switching cycles · Heat pump modulation and status
Available commands
Smart Grid trigger · Smart Grid offset DHW setpoint · Smart Grid offset heating buffer setpoint · Smart Grid offset room setpoint HC1-HC3
Compatible models
TTE · Belaria · UltraSource · Thermalia
Last updated

Registers (54)

47 read, 7 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Aktuelle Vorlauftemperatur HC2 [VF2]°CRead
Status Betriebsart HC2Read
Aktuelle Warmwasserspeichertemperatur Oben [SF1]°CRead
Status Warmwasserspeicher BetriebsartRead
Status Warmwasserspeicher Solltemperatur°CRead
Status Betriebsart HC1Read
Aktuelle Vorlauftemperatur HC1 [VF1]°CRead
Status Erzeuger Solltemperatur°CRead
Aktuelle Erzeugervorlauftemperatur [CVF]°CRead
Status Erzeuger BetriebsmeldungRead
Aktuelle Regelstrategie HC1Read
Aktuelle Regelstrategie HC2Read
Aktuelle Außentemperatur [AF1]°CRead
Aktuelle Warmwasserspeichertemperatur Unten [SF2]°CRead
Aktuelle Puffertemperatur Oben [PF1]°CRead
Aktuelle Pufferisstemperatur Unten [PF2]°CRead
Status Pufferspeicher BetriebsartRead
Status Pufferspeicher Solltemperatur°CRead
Status Elektrische GesamtenergieMWhRead
Status Thermische Gesamtenergie HeizbetriebMWhRead
Status Thermische Gesamtenergie WarmwasserbetriebMWhRead
Status Thermische Gesamenergie KühlbetriebMWhRead
Aktuelle elektrische LeistungkWRead
Aktuelle thermische LeistungkWRead
Status Vorlaufsolltemperatur HC1°CRead
Status Vorlaufsolltemperatur HC2°CRead
Status Fehlercode vom AutomatenRead
Status Mischkreispumpe HC1Read
Status Mischkreispumpe HC2Read
Status Mischer HC1%Read
Status Mischer HC2%Read
Status WärmeerzeugerRead
Aktuelle Modulation WP%Read
Status BetriebsstundenhRead
Status SchaltzyklencountRead
Aktuelle HZ Puffer WPF Fühler Temperatur [WPF]°CRead
Status Betriebsart HC3Read
Aktuelle Vorlauftemperatur HC3 [VF3]°CRead
Status Mischkreispumpe HC3Read
Status Vorlaufsolltemperatur HC3°CRead
Status Mischer HC3%Read
Aktuelle Regelstrategie HC3Read
Aktuelle Rücklauftemperatur°CRead
Status JahresarbeitszahlRead
Aktueller Volumenstroml/minRead
Aktueller COPRead
Status Detailstatus WärmepumpeRead
Smart Grid AuslösenWrite
Smart Grid Offset Warmwasser Soll°CWrite
Smart Grid Offset Heizungspuffer Soll°CWrite
Smart Grid Offset Raum Soll HC1°CWrite
Smart Grid Offset Raum Soll HC2°CWrite
Smart Grid Offset Raum Soll HC3°CWrite
Smart Grid über SystembusWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor outdoor temperature, flow temperatures, and COP of Hoval heat pumps on a live cloud dashboard.
  • Trigger Smart Grid mode to shift heat pump operation into periods of PV surplus production.
  • Create alerts when DHW or buffer tank temperatures drop below expected thresholds for more than 15 minutes.
  • Track thermal and electrical energy totals over time to calculate seasonal performance factors.
  • Adjust room temperature setpoint offsets for up to three heating circuits based on energy tariff schedules.
  • Log operating hours and switching cycles to plan preventive maintenance intervals for heat pump compressors.

Installation

  1. Connect the Hoval Modbus TCP Gateway to your local network, or wire the Hoval Modbus RTU Gateway to the RS485 port on your ModbusCloud Gateway.

  2. Enable the Modbus interface on the Hoval TopTronic E controller and configure the correct Modbus slave address.

  3. For Modbus RTU, set the baud rate, parity, and stop bits on both the Hoval gateway and the ModbusCloud gateway to matching values.

  4. Import the Hoval Energy Management template in the ModbusCloud platform and assign it to your gateway.

  5. Verify that live readings such as outdoor temperature and heat pump status appear correctly on the ModbusCloud dashboard.

  6. Test the Smart Grid trigger and confirm that the heat pump acknowledges the switch-on recommendation.

Things to watch for

What happens if the ModbusCloud connection is lost?

The Hoval heat pump continues to operate on its own internal logic. The Energy Management template only sends switch-on recommendations and setpoint offsets, so a communication failure does not affect normal heating or hot water operation.

Why does my Smart Grid offset seem to have no effect?

The Hoval TopTronic E ignores setpoint offsets when the outdoor temperature is above the configured heating limit. Check the heating limit setting on the controller and verify that the heat pump is actually in heating mode.

What data format do the energy registers use?

Thermal and electrical energy totals are transmitted as uint32 or int32 values in MWh. Make sure your register configuration uses 32-bit reads and the correct byte order to avoid misinterpreted values.

Can I use this template with both Modbus TCP and Modbus RTU?

Yes. Use the Hoval Modbus TCP Gateway for a direct network connection, or the Hoval Modbus RTU Gateway connected to the RS485 port of your ModbusCloud gateway. Select the matching protocol when configuring the template.