Hoval Hoval Heating & Cooling Modbus TCP template

Hoval Heating & Cooling

Control Hoval TopTronic E heating and cooling systems via Modbus TCP or RTU.

This ModbusCloud template controls and monitors Hoval TopTronic E heating and cooling systems via the Hoval Connect Modbus Gateway (part 6049501) over Modbus TCP or RTU. It reads flow and return temperatures for up to two heating circuits, outdoor temperature, domestic hot water temperatures, electrical and thermal power, current and annual COP, and total energy per mode. Writes are supported for setpoints, operating modes, and DHW control.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
49, read and write
Brand
Hoval
Key readings
Flow and return temperatures HC1/HC2 · Outdoor temperature · DHW storage temperatures (top/bottom) · Electrical and thermal power (kW) · Current COP and annual performance factor · Total energy (heating, cooling, DHW)
Available commands
Heating/cooling flow setpoints HC1/HC2 · DHW setpoint temperature · Operating mode HC1/HC2 · DHW operating mode
Compatible models
TTE · Belaria · UltraSource · UltraGas · UltraOil · BioLyt · UltraSol · Thermalia · TopGas · MultiJet · Max-3
Last updated

Registers (49)

41 read, 10 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Aktuelle Vorlauftemperatur HC2 [VF2]°CRead
Status Betriebsart HC2Read
Aktuelle Warmwasserspeichertemperatur Oben [SF1]°CRead
Status Warmwasserspeicher BetriebsartRead
Status Warmwasserspeicher Solltemperatur°CRead
Status Erzeuger BetriebsartRead
Status Betriebsart HC1Read
Aktuelle Vorlauftemperatur HC1 [VF1]°CRead
Status Erzeuger Solltemperatur°CRead
Aktuelle Erzeugervorlauftemperatur [CVF]°CRead
Status Erzeuger BetriebsmeldungRead
Aktuelle Regelstrategie HC1Read and write
Aktuelle Regelstrategie HC2Read and write
Aktuelle Außentemperatur [AF1]°CRead
Aktuelle Warmwasserspeichertemperatur Unten [SF2]°CRead
Aktuelle Puffertemperatur Oben [PF1]°CRead
Aktuelle Pufferisstemperatur Unten [PF2]°CRead
Status Pufferspeicher BetriebsartRead
Status Pufferspeicher Solltemperatur°CRead
Status Elektrische GesamtleistungMWhRead
Status Thermische Gesamtleistung HeizbetriebMWhRead
Status Thermische Gesamtleistung WarmwasserbetriebMWhRead
Status Thermische Gesamtleistung KühlbetriebMWhRead
Aktuelle elektrische LeistungkWRead
Aktuelle thermische LeistungkWRead
Status Vorlaufsolltemperatur HC1°CRead
Status Vorlaufsolltemperatur HC2°CRead
Status Fehlercode vom AutomatenRead
Status Mischkreispumpe HC1Read
Status Mischkreispumpe HC2Read
Status Mischer HC1%Read
Status Mischer HC2%Read
Aktueller COPRead
Aktuelle HZ Puffer WPF Temperatur°CRead
Aktuelle Rücklauftemperatur°CRead
Aktueller Volumenstroml/minRead
Status Detailstatus WärmepumpeRead
Status JahresarbeitszahlRead
Status SchaltzyklencountRead
Status BetriebsstundenhRead
Aktuelle Modulation%Read
Sollvorlauftemperatur Heizen HC1°CWrite
Warmwasser Solltemperatur°CWrite
Warmwasser BetriebsartWrite
Sollvorlauftemperatur Heizen HC2°CWrite
Sollvorlauftemperatur Kühlen HC1°CWrite
Sollvorlauftemperatur Kühlen HC2°CWrite
Betriebsart HC1Write
Betriebsart HC2Write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show the full heating system at a glance with outdoor temperature, flow and return on every circuit, and current electrical vs thermal power.
  • Automatically reduce flow temperature during warm afternoons or when a room thermostat signals satisfied demand.
  • Log annual performance factor and total energy per mode for subsidy applications or your own reports.
  • Trigger an alert when the COP drops below an expected threshold, a sign of a refrigerant or air-flow problem.
  • Remotely activate or deactivate cooling mode on HC1 or HC2 based on room temperature or outside forecast.

Installation

  1. Install the Hoval Connect Modbus Gateway (6049501) on the TopTronic E system and connect it to the LAN for Modbus TCP, or to the RS485 bus for Modbus RTU.

  2. Configure the gateway address and baudrate (RTU) or IP (TCP) per the Hoval installation guide.

  3. In ModbusCloud, add a matching Modbus TCP or RTU device and import the Hoval Heating and Cooling template.

  4. Verify readings in the first minute. If total energy values look wrong, your firmware may still use the old 16-bit layout and you should switch to the older Energy Management template.

Things to watch for

Total energy registers return impossibly large numbers. Firmware version issue?

Yes. Hoval 3.0.0 changed the total energy registers from two 16-bit high and low to single 32-bit values. If your firmware is older than 3.0.0 you will see overflow. Either update the TopTronic E firmware or switch to the older Energy Management Template.

Modbus RTU or Modbus TCP: which one should I choose?

Both work equally well. Choose TCP when the Hoval cabinet is near a network switch, and RTU when you want to run a single twisted pair to the ModbusCloud gateway. The register map is identical.

I can read everything but writing setpoints has no effect. Why?

Some Hoval installations lock external setpoint writes at commissioning. Ask the commissioning engineer to unlock the external control permission on the TopTronic E menu. Without that, Modbus writes are accepted silently but not applied.

Want to see how it works?