Hoval TopTronic E Heat Generator
Controller of Hoval boilers and heat pumps with temperatures, output, energy, status and setpoints over Modbus TCP.
The Hoval TopTronic E Heat Generator is the basic controller module that runs Hoval boilers and heat pumps with their heating circuits and hot water in buildings, commercial boiler plants and greenhouses. This Modbus TCP template reads temperatures, modulation, power, energy counters, status and error codes through the Hoval Modbus gateway and writes operating modes and setpoints from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 352, read and write
- Brand
- Hoval
- Key readings
- Flow and return temperature · Modulation · Heating and electrical power · Water pressure · Operating hours and switching cycles · Heat quantity and electrical energy · Outdoor temperature · Status and error code
- Available commands
- Heat generator operation choice · Manual mode set temperature · Manual mode output setpoint · Heating circuit room setpoints · Hot water setpoint · Smart Grid and power limitation
- Compatible models
- TopTronic E basic module heat generator (WEZ) · Hoval gas and pellet boilers with TopTronic E · Hoval heat pumps with TopTronic E (WFA-200 or ECR461 controller)
- Last updated
Registers (352)
352 read, 113 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Heat Generator Flow Temperature | °C | Read | |||
| Heat Generator Return Temperature | °C | Read | |||
| Heat Generator Flow Setpoint | °C | Read | |||
| Heat Generator Modulation | % | Read | |||
| Heat Generator Electrical Power | kW | Read | |||
| Heat Generator Heating Power | kW | Read | |||
| Heat Generator Current Output Heating | kW | Read | |||
| Heat Generator Current Output Cooling | kW | Read | |||
| Heat Generator Water Pressure | bar | Read | |||
| Heat Generator Volume Flow | l/min | Read | |||
| Heat Generator Main Pump Speed | % | Read | |||
| Heat Generator Ionisation | Read | ||||
| Heat Generator Total Energy Efficiency | Read | ||||
| FA Setpoint Heating Circuit Operation | °C | Read | |||
| FA Setpoint Tank Operation | °C | Read | |||
| FA Output Limitation | % | Read | |||
| FA Setpoint Cooling Mode | °C | Read | |||
| FA Heat Generator Temperature | °C | Read | |||
| FA Exhaust Gas Temperature | °C | Read | |||
| FA Switching Temperature Active/Passive | °C | Read | |||
| FA Heating Setpoint | °C | Read | |||
| FA Storage Tank Setpoint | °C | Read | |||
| FA Heat Generator Setpoint | °C | Read | |||
| FA Heating External Maximum Limit | °C | Read | |||
| FA Tank External Maximum Limit | °C | Read | |||
| FA Return Temperature | °C | Read | |||
| FA Heat Generator Output | % | Read | |||
| FA Absolute Output | % | Read | |||
| FA Water Pressure | bar | Read | |||
| FA Cooling Setpoint | °C | Read | |||
| FA COP | Read | ||||
| FA Probe Flow/Intake Temperature | °C | Read | |||
| FA Probe Return/Evaporator Temperature | °C | Read | |||
| Outdoor Temperature AF1 | °C | Read | |||
| Outdoor Temperature AF2 | °C | Read | |||
| System Flow Temperature Heating | °C | Read | |||
| System Flow Temperature Hot Water | °C | Read | |||
| System Flow Temperature Cooling | °C | Read | |||
| System Temperature Setpoint Heating | °C | Read | |||
| System Temperature Setpoint Hot Water | °C | Read | |||
| System Temperature Setpoint Cooling | °C | Read | |||
| System Output Setpoint Heating | % | Read | |||
| System Output Setpoint Hot Water | % | Read | |||
| System Output Setpoint Cooling | % | Read | |||
| Heating Circuit 1 Room Temperature | °C | Read and write | |||
| Heating Circuit 1 Flow Temperature | °C | Read | |||
| Heating Circuit 1 Return Temperature | °C | Read | |||
| Heating Circuit 1 Room Setpoint | °C | Read | |||
| Heating Circuit 1 Flow Setpoint | °C | Read | |||
| Heating Circuit 2 Room Temperature | °C | Read and write | |||
| Heating Circuit 2 Flow Temperature | °C | Read | |||
| Heating Circuit 2 Return Temperature | °C | Read | |||
| Heating Circuit 2 Room Setpoint | °C | Read | |||
| Heating Circuit 2 Flow Setpoint | °C | Read | |||
| Heating Circuit 3 Room Temperature | °C | Read and write | |||
| Heating Circuit 3 Flow Temperature | °C | Read | |||
| Heating Circuit 3 Return Temperature | °C | Read | |||
| Heating Circuit 3 Room Setpoint | °C | Read | |||
| Heating Circuit 3 Flow Setpoint | °C | Read | |||
| Hot Water Temperature SF | °C | Read | |||
| Hot Water Temperature SF2 | °C | Read | |||
| Circulation Temperature | °C | Read | |||
| Hot Water Setpoint | °C | Read | |||
| Global Radiation | W/m² | Read | |||
| Plant Flow Temperature FAV | °C | Read | |||
| Plant Flow Setpoint FAV | °C | Read | |||
| Info Sensor 1 | °C | Read | |||
| Info Sensor 2 | °C | Read | |||
| Info Sensor 3 | °C | Read | |||
| Info Sensor 4 | °C | Read | |||
| Info Sensor 5 | °C | Read | |||
| Info 1 0-10V | Read | ||||
| Info 2 0-10V | Read | ||||
| Info 3 0-10V | Read | ||||
| Cascade 1 Output Setpoint | % | Read | |||
| Cascade 1 Current Demand | % | Read | |||
| Cascade 2 Output Setpoint | % | Read | |||
| Cascade 2 Current Demand | % | Read | |||
| Cascade 3 Output Setpoint | % | Read | |||
| Cascade 3 Current Demand | % | Read | |||
| Cascade 4 Output Setpoint | % | Read | |||
| Cascade 4 Current Demand | % | Read | |||
| Cascade 5 Output Setpoint | % | Read | |||
| Cascade 5 Current Demand | % | Read | |||
| Cascade 6 Output Setpoint | % | Read | |||
| Cascade 6 Current Demand | % | Read | |||
| Cascade 7 Output Setpoint | % | Read | |||
| Cascade 7 Current Demand | % | Read | |||
| Cascade 8 Output Setpoint | % | Read | |||
| Cascade 8 Current Demand | % | Read | |||
| Additional Heat Flow Temperature | °C | Read | |||
| Additional Heat Return Temperature | °C | Read | |||
| Additional Heat Flow Setpoint | °C | Read | |||
| Additional Heat Current Output Heating | kW | Read | |||
| Additional Heat Volume Flow | l/min | Read | |||
| Additional Heat Main Pump Speed | % | Read | |||
| Additional Heat Output Setpoint | % | Read | |||
| WFA Buffer Sensor WPF | °C | Read | |||
| WFA CP Speed | % | Read | |||
| WFA CP Speed (Duplicate) | Read | ||||
| WFA Heat Source Pump Speed | % | Read | |||
| WFA Heat Source Pump Speed (Duplicate) | % | Read | |||
| WFA GWP | Read | ||||
| WFA Ground Water Temperature | °C | Read | |||
| WFA Ground Water Temperature (Duplicate) | °C | Read | |||
| WFA Volume Flow Averaged | l/min | Read | |||
| WFA GWP Speed | % | Read | |||
| WFA HP Flow Temperature | °C | Read | |||
| WFA HP Return Temperature | °C | Read | |||
| WFA Primary Flow Temperature | °C | Read | |||
| WFA Primary Return Temperature | °C | Read | |||
| WFA Intake Air Temperature 1 | °C | Read | |||
| WFA Suction Gas Temperature 1 | °C | Read | |||
| WFA Hot Gas Temperature 1 | °C | Read | |||
| WFA Overheating 1 | K | Read | |||
| WFA Low Pressure 1 | bar | Read | |||
| WFA High Pressure 1 | bar | Read | |||
| WFA Actual Speed | % | Read | |||
| ECR Primary Flow Temperature 1 | °C | Read | |||
| ECR Primary Return Temperature 1 | °C | Read | |||
| ECR Ground Water Temperature | °C | Read | |||
| ECR Current COP | Read | ||||
| Heat Generator Pump | % | Read | |||
| Heat Generator Status | Read | ||||
| Heat Generator FA Status | Read | ||||
| Heat Generator Operating Message | Read | ||||
| FA Emission Measurement | Read | ||||
| FA Burner Flame | Read | ||||
| FA Error Code | Read | ||||
| FA Heat Generator Status | Read | ||||
| FA Operating Status | Read | ||||
| FA Status Information | Read | ||||
| Cooling Valve Active UKA | Read | ||||
| Cooling Valve General UHKA | Read | ||||
| Heating Circuit 1 Pump | Read | ||||
| Heating Circuit 1 Mixer | % | Read | |||
| Heating Circuit 1 Status | Read | ||||
| Heating Circuit 2 Pump | Read | ||||
| Heating Circuit 2 Mixer | % | Read | |||
| Heating Circuit 2 Status | Read | ||||
| Heating Circuit 3 Pump | Read | ||||
| Heating Circuit 3 Mixer | % | Read | |||
| Heating Circuit 3 Status | Read | ||||
| Hot Water Circulation Pump | Read | ||||
| Hot Water Charging Pump | Read | ||||
| Hot Water Status | Read | ||||
| Collective Fault Output | Read | ||||
| AVP Pump | Read | ||||
| YAV Mixer | % | Read | |||
| Smart Grid Status | Read | ||||
| Smart Grid Status (Duplicate) | Read | ||||
| Setpoint Increase/Decrease Status | Read | ||||
| Cascade 1 Lead Heat Generator | Read | ||||
| Additional Heat Pump | % | Read | |||
| Additional Heat Burner Stage | Read | ||||
| Additional Heat Status | Read | ||||
| WFA High Pressure 1 Fault | Read | ||||
| Heat Generator Operation Choice | Read and write | ||||
| Heat Generator Manual Mode Set Temperature | °C | Read and write | |||
| Heat Generator Manual Mode Output Setpoint | % | Read and write | |||
| Heat Generator Temperature Increase | K | Read and write | |||
| Heat Generator Emissions Test Active | Read and write | ||||
| Heat Generator Emissions Test Output Limit | % | Read and write | |||
| Heating Circuit 1 Operation Choice | Read and write | ||||
| Heating Circuit 1 Normal Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 1 Eco Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 1 Normal Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 1 Eco Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 1 Manual Mode Set Temperature | °C | Read and write | |||
| Heating Circuit 1 Manual Mode Set Temperature (Duplicate) | °C | Read and write | |||
| Heating Circuit 1 Constant Flow Setpoint Heating | °C | Read and write | |||
| Heating Circuit 1 Constant Flow Setpoint Cooling | °C | Read and write | |||
| Heating Circuit 1 Smart Grid Room Offset Heating | K | Read and write | |||
| Heating Circuit 1 Smart Grid Room Offset Cooling | K | Read and write | |||
| Heating Circuit 2 Operation Choice | Read and write | ||||
| Heating Circuit 2 Normal Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 2 Eco Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 2 Normal Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 2 Eco Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 2 Manual Mode Set Temperature | °C | Read and write | |||
| Heating Circuit 2 Manual Mode Set Temperature (Duplicate) | °C | Read and write | |||
| Heating Circuit 2 Constant Flow Setpoint Heating | °C | Read and write | |||
| Heating Circuit 2 Constant Flow Setpoint Cooling | °C | Read and write | |||
| Heating Circuit 2 Smart Grid Room Offset Heating | K | Read and write | |||
| Heating Circuit 2 Smart Grid Room Offset Cooling | K | Read and write | |||
| Heating Circuit 3 Operation Choice | Read and write | ||||
| Heating Circuit 3 Normal Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 3 Eco Room Temperature Heating | °C | Read and write | |||
| Heating Circuit 3 Normal Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 3 Eco Room Temperature Cooling | °C | Read and write | |||
| Heating Circuit 3 Manual Mode Set Temperature | °C | Read and write | |||
| Heating Circuit 3 Manual Mode Set Temperature (Duplicate) | °C | Read and write | |||
| Heating Circuit 3 Constant Flow Setpoint Heating | °C | Read and write | |||
| Heating Circuit 3 Constant Flow Setpoint Cooling | °C | Read and write | |||
| Heating Circuit 3 Smart Grid Room Offset Heating | K | Read and write | |||
| Heating Circuit 3 Smart Grid Room Offset Cooling | K | Read and write | |||
| Hot Water Operation Choice | Read and write | ||||
| Normal Hot Water Temperature | °C | Read and write | |||
| Eco Hot Water Temperature | °C | Read and write | |||
| Smart Grid Hot Water Offset | K | Read and write | |||
| Available Electrical Power | kW | Read and write | |||
| Available Electrical Power Dampened | kW | Read and write | |||
| Smart Grid via System Bus | Read and write | ||||
| Smart Grid Function Trigger | Read and write | ||||
| Additional Heat Operation Choice | Read and write | ||||
| Additional Heat Manual Mode Set Temperature | °C | Read and write | |||
| Additional Heat Manual Mode Output Setpoint | % | Read and write | |||
| Additional Heat Temperature Increase | K | Read and write | |||
| WFA Power Limitation | kW | Read and write | |||
| WFA Power Limitation Function | Read and write | ||||
| Heat Generator Max Output Heating | % | Read and write | |||
| Heat Generator Max Output Hot Water | % | Read and write | |||
| Heat Generator Max Output Cooling | % | Read and write | |||
| Heat Generator Release Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 1 Heating Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Heating Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 1 Heating Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Control Strategy | Read and write | ||||
| Heating Circuit 1 Cooling Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Summer Compensation Start Point | °C | Read and write | |||
| Heating Circuit 1 Cooling Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 1 Cooling Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Heat Generator Flow Setpoint Offset | °C | Read and write | |||
| Heating Circuit 1 Minimum Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Maximum Flow Temperature | °C | Read and write | |||
| Heating Circuit 1 Minimum Flow Temperature Cooling | °C | Read and write | |||
| Heating Circuit 2 Heating Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Heating Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 2 Heating Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Control Strategy | Read and write | ||||
| Heating Circuit 2 Cooling Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Summer Compensation Start Point | °C | Read and write | |||
| Heating Circuit 2 Cooling Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 2 Cooling Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Heat Generator Flow Setpoint Offset | °C | Read and write | |||
| Heating Circuit 2 Minimum Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Maximum Flow Temperature | °C | Read and write | |||
| Heating Circuit 2 Minimum Flow Temperature Cooling | °C | Read and write | |||
| Heating Circuit 3 Heating Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Heating Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 3 Heating Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Control Strategy | Read and write | ||||
| Heating Circuit 3 Cooling Curve Base Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Summer Compensation Start Point | °C | Read and write | |||
| Heating Circuit 3 Cooling Curve Design Outdoor Temperature | °C | Read and write | |||
| Heating Circuit 3 Cooling Curve Design Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Heat Generator Flow Setpoint Offset | °C | Read and write | |||
| Heating Circuit 3 Minimum Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Maximum Flow Temperature | °C | Read and write | |||
| Heating Circuit 3 Minimum Flow Temperature Cooling | °C | Read and write | |||
| Available Power Source | Read and write | ||||
| Dampened Power Source | Read and write | ||||
| Dampened Power Time Filter | min | Read and write | |||
| Smart Grid Minimum Power | kW | Read and write | |||
| SG Forced Acceptance Threshold | kW | Read and write | |||
| SG Forced Acceptance Hysteresis | kW | Read and write | |||
| SG Preferential Operation Threshold | kW | Read and write | |||
| SG Preferential Operation Hysteresis | kW | Read and write | |||
| Available Power Offset | kW | Read and write | |||
| Available Power Dampened Offset | kW | Read and write | |||
| SG Minimum Power Hysteresis | kW | Read and write | |||
| Cascade 1 Sequence Change Time | Read and write | ||||
| Heat Generator Operating Hours (Duplicate) | h | Read | |||
| Heat Generator Operating Hours | h | Read | |||
| Heat Generator Switching Cycles | Read | ||||
| Heat Generator Operating Hours Above 50% | h | Read | |||
| Heat Generator Switching Cycles Above 50% | Read | ||||
| Heat Generator Heat Quantity Heating | MWh | Read | |||
| Heat Generator Cooling Quantity | MWh | Read | |||
| Heat Generator Electrical Energy | MWh | Read | |||
| FA Heat Quantity Heating | MWh | Read | |||
| FA Heat Quantity Cooling | MWh | Read | |||
| FA Heat Quantity Hot Water | MWh | Read | |||
| Additional Heat Operating Hours | h | Read | |||
| Additional Heat Switching Cycles | Read | ||||
| Additional Heat Heat Quantity Heating | MWh | Read | |||
| WFA Heating Running Time | h | Read | |||
| WFA Cooling Running Time | h | Read | |||
| WFA Hot Water Running Time | h | Read | |||
| ECR Additional Heating Operating Hours | h | Read | |||
| ECR Additional Heating Starts | Read | ||||
| ECR Heating Operating Hours | h | Read | |||
| ECR Hot Water Operating Hours | h | Read | |||
| ECR Active Cooling Operating Hours | h | Read | |||
| FA Burner ID Index | Read | ||||
| FA Function Extensions | Read | ||||
| MK1 Output | Read and write | ||||
| YK1+ Output | Read and write | ||||
| YK1- Output | Read and write | ||||
| DKP Output | Read and write | ||||
| SLP Output | Read and write | ||||
| VA1 Output | Read | ||||
| VA2 Output | Read | ||||
| VA1-FE1 Output | Read | ||||
| VA2-FE1 Output | Read | ||||
| VA3-FE1 Output | Read | ||||
| VA1-FE2 Output | Read | ||||
| VA2-FE2 Output | Read | ||||
| VA3-FE2 Output | Read | ||||
| VA 0-10V/PWM Output | % | Read | |||
| VA 0-10V/PWM FE1 Output | % | Read | |||
| Relay Test Active | Read | ||||
| WFA Application Number | Read | ||||
| ECR Output Y1 0-10V/PWM | % | Read | |||
| ECR Output Y2 0-10V/PWM | % | Read | |||
| ECR Relay Output R9 | Read | ||||
| ECR Relay Output R152 | Read | ||||
| Active Error 1 Appearance Time | Read | ||||
| Active Error 1 Appearance Date | Read | ||||
| Active Error 1 Disappear Time | Read | ||||
| Active Error 1 Disappear Date | Read | ||||
| Active Error 1 Source | Read | ||||
| Active Error 1 Function Group | Read | ||||
| Active Error 1 Function Number | Read | ||||
| Active Error 1 Error Type | Read | ||||
| Active Error 1 Error Code | Read | ||||
| Active Error 2 Appearance Time | Read | ||||
| Active Error 2 Appearance Date | Read | ||||
| Active Error 2 Disappear Time | Read | ||||
| Active Error 2 Disappear Date | Read | ||||
| Active Error 2 Source | Read | ||||
| Active Error 2 Function Group | Read | ||||
| Active Error 2 Function Number | Read | ||||
| Active Error 2 Error Type | Read | ||||
| Active Error 2 Error Code | Read | ||||
| Active Error 3 Appearance Time | Read | ||||
| Active Error 3 Appearance Date | Read | ||||
| Active Error 3 Disappear Time | Read | ||||
| Active Error 3 Disappear Date | Read | ||||
| Active Error 3 Source | Read | ||||
| Active Error 3 Function Group | Read | ||||
| Active Error 3 Function Number | Read | ||||
| Active Error 3 Error Type | Read | ||||
| Active Error 3 Error Code | Read | ||||
| Active Error 4 Appearance Time | Read | ||||
| Active Error 4 Appearance Date | Read | ||||
| Active Error 4 Disappear Time | Read | ||||
| Active Error 4 Disappear Date | Read | ||||
| Active Error 4 Source | Read | ||||
| Active Error 4 Function Group | Read | ||||
| Active Error 4 Function Number | Read | ||||
| Active Error 4 Error Type | Read | ||||
| Active Error 4 Error Code | Read | ||||
| Active Error 5 Appearance Time | Read | ||||
| Active Error 5 Appearance Date | Read | ||||
| Active Error 5 Disappear Time | Read | ||||
| Active Error 5 Disappear Date | Read | ||||
| Active Error 5 Source | Read | ||||
| Active Error 5 Function Group | Read | ||||
| Active Error 5 Function Number | Read | ||||
| Active Error 5 Error Type | Read | ||||
| Active Error 5 Error Code | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Put flow, return and outdoor temperature, modulation and output of the boiler or heat pump on one dashboard for the boiler house.
- Get an email, in-app or webhook alert when the heat generator status goes to fault or the error code changes.
- Track operating hours, switching cycles and heat quantity over 365 days to plan maintenance and spot short cycling.
- Change the operating mode and room or hot water setpoints remotely once writing is enabled for the gateway.
- Write the available electrical power or the Smart Grid state from an automation on an energy price or a time schedule.
Installation
Connect the Hoval Modbus gateway of the TopTronic E system to the same network as the ModbusCloud Gateway and give it a fixed IP address.
Check on the TopTronic E operating module that the heat generator has module address 1. Another address uses other register addresses.
In ModbusCloud, add a Modbus device with Modbus TCP, the IP address of the Hoval gateway, port 502 and unit ID 1, then import this template.
Check that Outdoor Temperature AF1 and Heat Generator Flow Temperature show plausible values. Functions that are not installed may not answer.
Keep the reading interval at the default 5 minutes. Hoval advises longer intervals as the number of requests to its gateway grows.
Things to watch for
The Hoval gateway does not answer. What should I check?
Check that the ModbusCloud Gateway reaches the IP address of the Hoval Modbus gateway, and use port 502 and unit ID 1. The Hoval gateway has to be registered in the HovalConnect app, which also keeps its software up to date. Data points of functions or modules that are not installed can time out, for example the SF2 hot water sensor when it is not fitted.
How do I read a second heat generator or a cascade?
Every heat generator has its own module address from 1 to 16 on the TopTronic E bus, shown on the operating module. Hoval gives each data point of each module address its own register address, with no fixed offset. This template is for address 1. For heat generator 2, make your own template in ModbusCloud with the addresses Hoval lists for WEZ UnitId 2 in its Modbus data point list.
Why does a setpoint I write have no effect?
Writing is off per gateway until you request it in the portal. Room setpoints only apply when Operation Choice of the heating circuit is 4 (constant), and hot water works the same way. Constant flow setpoints, manual heat generator modes and Smart Grid need basic settings by Hoval service first. A written value stays active until a new one is written.
How often should ModbusCloud read the Hoval gateway?
The default of every 5 minutes is a good choice. Hoval warns that its Modbus gateway can lock up when it gets too many requests. This template has many registers. If you only need a few values, make your own template with just those registers.
Why do some registers not answer on my boiler?
The template holds the values of every heat generator type, including the heat pump controllers WFA-200 and ECR461 and the cascade manager. On a boiler without those functions these data points can time out or show no useful value. Leave them off your dashboards or out of your own template.