Hoval Hoval TopTronic E Heat Generator Modbus TCP template

Hoval TopTronic E Heat Generator

Controller of Hoval boilers and heat pumps with temperatures, output, energy, status and setpoints over Modbus TCP.

The Hoval TopTronic E Heat Generator is the basic controller module that runs Hoval boilers and heat pumps with their heating circuits and hot water in buildings, commercial boiler plants and greenhouses. This Modbus TCP template reads temperatures, modulation, power, energy counters, status and error codes through the Hoval Modbus gateway and writes operating modes and setpoints from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
352, read and write
Brand
Hoval
Key readings
Flow and return temperature · Modulation · Heating and electrical power · Water pressure · Operating hours and switching cycles · Heat quantity and electrical energy · Outdoor temperature · Status and error code
Available commands
Heat generator operation choice · Manual mode set temperature · Manual mode output setpoint · Heating circuit room setpoints · Hot water setpoint · Smart Grid and power limitation
Compatible models
TopTronic E basic module heat generator (WEZ) · Hoval gas and pellet boilers with TopTronic E · Hoval heat pumps with TopTronic E (WFA-200 or ECR461 controller)
Last updated

Registers (352)

352 read, 113 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Heat Generator Flow Temperature°CRead
Heat Generator Return Temperature°CRead
Heat Generator Flow Setpoint°CRead
Heat Generator Modulation%Read
Heat Generator Electrical PowerkWRead
Heat Generator Heating PowerkWRead
Heat Generator Current Output HeatingkWRead
Heat Generator Current Output CoolingkWRead
Heat Generator Water PressurebarRead
Heat Generator Volume Flowl/minRead
Heat Generator Main Pump Speed%Read
Heat Generator IonisationRead
Heat Generator Total Energy EfficiencyRead
FA Setpoint Heating Circuit Operation°CRead
FA Setpoint Tank Operation°CRead
FA Output Limitation%Read
FA Setpoint Cooling Mode°CRead
FA Heat Generator Temperature°CRead
FA Exhaust Gas Temperature°CRead
FA Switching Temperature Active/Passive°CRead
FA Heating Setpoint°CRead
FA Storage Tank Setpoint°CRead
FA Heat Generator Setpoint°CRead
FA Heating External Maximum Limit°CRead
FA Tank External Maximum Limit°CRead
FA Return Temperature°CRead
FA Heat Generator Output%Read
FA Absolute Output%Read
FA Water PressurebarRead
FA Cooling Setpoint°CRead
FA COPRead
FA Probe Flow/Intake Temperature°CRead
FA Probe Return/Evaporator Temperature°CRead
Outdoor Temperature AF1°CRead
Outdoor Temperature AF2°CRead
System Flow Temperature Heating°CRead
System Flow Temperature Hot Water°CRead
System Flow Temperature Cooling°CRead
System Temperature Setpoint Heating°CRead
System Temperature Setpoint Hot Water°CRead
System Temperature Setpoint Cooling°CRead
System Output Setpoint Heating%Read
System Output Setpoint Hot Water%Read
System Output Setpoint Cooling%Read
Heating Circuit 1 Room Temperature°CRead and write
Heating Circuit 1 Flow Temperature°CRead
Heating Circuit 1 Return Temperature°CRead
Heating Circuit 1 Room Setpoint°CRead
Heating Circuit 1 Flow Setpoint°CRead
Heating Circuit 2 Room Temperature°CRead and write
Heating Circuit 2 Flow Temperature°CRead
Heating Circuit 2 Return Temperature°CRead
Heating Circuit 2 Room Setpoint°CRead
Heating Circuit 2 Flow Setpoint°CRead
Heating Circuit 3 Room Temperature°CRead and write
Heating Circuit 3 Flow Temperature°CRead
Heating Circuit 3 Return Temperature°CRead
Heating Circuit 3 Room Setpoint°CRead
Heating Circuit 3 Flow Setpoint°CRead
Hot Water Temperature SF°CRead
Hot Water Temperature SF2°CRead
Circulation Temperature°CRead
Hot Water Setpoint°CRead
Global RadiationW/m²Read
Plant Flow Temperature FAV°CRead
Plant Flow Setpoint FAV°CRead
Info Sensor 1°CRead
Info Sensor 2°CRead
Info Sensor 3°CRead
Info Sensor 4°CRead
Info Sensor 5°CRead
Info 1 0-10VRead
Info 2 0-10VRead
Info 3 0-10VRead
Cascade 1 Output Setpoint%Read
Cascade 1 Current Demand%Read
Cascade 2 Output Setpoint%Read
Cascade 2 Current Demand%Read
Cascade 3 Output Setpoint%Read
Cascade 3 Current Demand%Read
Cascade 4 Output Setpoint%Read
Cascade 4 Current Demand%Read
Cascade 5 Output Setpoint%Read
Cascade 5 Current Demand%Read
Cascade 6 Output Setpoint%Read
Cascade 6 Current Demand%Read
Cascade 7 Output Setpoint%Read
Cascade 7 Current Demand%Read
Cascade 8 Output Setpoint%Read
Cascade 8 Current Demand%Read
Additional Heat Flow Temperature°CRead
Additional Heat Return Temperature°CRead
Additional Heat Flow Setpoint°CRead
Additional Heat Current Output HeatingkWRead
Additional Heat Volume Flowl/minRead
Additional Heat Main Pump Speed%Read
Additional Heat Output Setpoint%Read
WFA Buffer Sensor WPF°CRead
WFA CP Speed%Read
WFA CP Speed (Duplicate)Read
WFA Heat Source Pump Speed%Read
WFA Heat Source Pump Speed (Duplicate)%Read
WFA GWPRead
WFA Ground Water Temperature°CRead
WFA Ground Water Temperature (Duplicate)°CRead
WFA Volume Flow Averagedl/minRead
WFA GWP Speed%Read
WFA HP Flow Temperature°CRead
WFA HP Return Temperature°CRead
WFA Primary Flow Temperature°CRead
WFA Primary Return Temperature°CRead
WFA Intake Air Temperature 1°CRead
WFA Suction Gas Temperature 1°CRead
WFA Hot Gas Temperature 1°CRead
WFA Overheating 1KRead
WFA Low Pressure 1barRead
WFA High Pressure 1barRead
WFA Actual Speed%Read
ECR Primary Flow Temperature 1°CRead
ECR Primary Return Temperature 1°CRead
ECR Ground Water Temperature°CRead
ECR Current COPRead
Heat Generator Pump%Read
Heat Generator StatusRead
Heat Generator FA StatusRead
Heat Generator Operating MessageRead
FA Emission MeasurementRead
FA Burner FlameRead
FA Error CodeRead
FA Heat Generator StatusRead
FA Operating StatusRead
FA Status InformationRead
Cooling Valve Active UKARead
Cooling Valve General UHKARead
Heating Circuit 1 PumpRead
Heating Circuit 1 Mixer%Read
Heating Circuit 1 StatusRead
Heating Circuit 2 PumpRead
Heating Circuit 2 Mixer%Read
Heating Circuit 2 StatusRead
Heating Circuit 3 PumpRead
Heating Circuit 3 Mixer%Read
Heating Circuit 3 StatusRead
Hot Water Circulation PumpRead
Hot Water Charging PumpRead
Hot Water StatusRead
Collective Fault OutputRead
AVP PumpRead
YAV Mixer%Read
Smart Grid StatusRead
Smart Grid Status (Duplicate)Read
Setpoint Increase/Decrease StatusRead
Cascade 1 Lead Heat GeneratorRead
Additional Heat Pump%Read
Additional Heat Burner StageRead
Additional Heat StatusRead
WFA High Pressure 1 FaultRead
Heat Generator Operation ChoiceRead and write
Heat Generator Manual Mode Set Temperature°CRead and write
Heat Generator Manual Mode Output Setpoint%Read and write
Heat Generator Temperature IncreaseKRead and write
Heat Generator Emissions Test ActiveRead and write
Heat Generator Emissions Test Output Limit%Read and write
Heating Circuit 1 Operation ChoiceRead and write
Heating Circuit 1 Normal Room Temperature Heating°CRead and write
Heating Circuit 1 Eco Room Temperature Heating°CRead and write
Heating Circuit 1 Normal Room Temperature Cooling°CRead and write
Heating Circuit 1 Eco Room Temperature Cooling°CRead and write
Heating Circuit 1 Manual Mode Set Temperature°CRead and write
Heating Circuit 1 Manual Mode Set Temperature (Duplicate)°CRead and write
Heating Circuit 1 Constant Flow Setpoint Heating°CRead and write
Heating Circuit 1 Constant Flow Setpoint Cooling°CRead and write
Heating Circuit 1 Smart Grid Room Offset HeatingKRead and write
Heating Circuit 1 Smart Grid Room Offset CoolingKRead and write
Heating Circuit 2 Operation ChoiceRead and write
Heating Circuit 2 Normal Room Temperature Heating°CRead and write
Heating Circuit 2 Eco Room Temperature Heating°CRead and write
Heating Circuit 2 Normal Room Temperature Cooling°CRead and write
Heating Circuit 2 Eco Room Temperature Cooling°CRead and write
Heating Circuit 2 Manual Mode Set Temperature°CRead and write
Heating Circuit 2 Manual Mode Set Temperature (Duplicate)°CRead and write
Heating Circuit 2 Constant Flow Setpoint Heating°CRead and write
Heating Circuit 2 Constant Flow Setpoint Cooling°CRead and write
Heating Circuit 2 Smart Grid Room Offset HeatingKRead and write
Heating Circuit 2 Smart Grid Room Offset CoolingKRead and write
Heating Circuit 3 Operation ChoiceRead and write
Heating Circuit 3 Normal Room Temperature Heating°CRead and write
Heating Circuit 3 Eco Room Temperature Heating°CRead and write
Heating Circuit 3 Normal Room Temperature Cooling°CRead and write
Heating Circuit 3 Eco Room Temperature Cooling°CRead and write
Heating Circuit 3 Manual Mode Set Temperature°CRead and write
Heating Circuit 3 Manual Mode Set Temperature (Duplicate)°CRead and write
Heating Circuit 3 Constant Flow Setpoint Heating°CRead and write
Heating Circuit 3 Constant Flow Setpoint Cooling°CRead and write
Heating Circuit 3 Smart Grid Room Offset HeatingKRead and write
Heating Circuit 3 Smart Grid Room Offset CoolingKRead and write
Hot Water Operation ChoiceRead and write
Normal Hot Water Temperature°CRead and write
Eco Hot Water Temperature°CRead and write
Smart Grid Hot Water OffsetKRead and write
Available Electrical PowerkWRead and write
Available Electrical Power DampenedkWRead and write
Smart Grid via System BusRead and write
Smart Grid Function TriggerRead and write
Additional Heat Operation ChoiceRead and write
Additional Heat Manual Mode Set Temperature°CRead and write
Additional Heat Manual Mode Output Setpoint%Read and write
Additional Heat Temperature IncreaseKRead and write
WFA Power LimitationkWRead and write
WFA Power Limitation FunctionRead and write
Heat Generator Max Output Heating%Read and write
Heat Generator Max Output Hot Water%Read and write
Heat Generator Max Output Cooling%Read and write
Heat Generator Release Outdoor Temperature°CRead and write
Heating Circuit 1 Heating Curve Base Flow Temperature°CRead and write
Heating Circuit 1 Heating Curve Design Outdoor Temperature°CRead and write
Heating Circuit 1 Heating Curve Design Flow Temperature°CRead and write
Heating Circuit 1 Control StrategyRead and write
Heating Circuit 1 Cooling Curve Base Flow Temperature°CRead and write
Heating Circuit 1 Summer Compensation Start Point°CRead and write
Heating Circuit 1 Cooling Curve Design Outdoor Temperature°CRead and write
Heating Circuit 1 Cooling Curve Design Flow Temperature°CRead and write
Heating Circuit 1 Heat Generator Flow Setpoint Offset°CRead and write
Heating Circuit 1 Minimum Flow Temperature°CRead and write
Heating Circuit 1 Maximum Flow Temperature°CRead and write
Heating Circuit 1 Minimum Flow Temperature Cooling°CRead and write
Heating Circuit 2 Heating Curve Base Flow Temperature°CRead and write
Heating Circuit 2 Heating Curve Design Outdoor Temperature°CRead and write
Heating Circuit 2 Heating Curve Design Flow Temperature°CRead and write
Heating Circuit 2 Control StrategyRead and write
Heating Circuit 2 Cooling Curve Base Flow Temperature°CRead and write
Heating Circuit 2 Summer Compensation Start Point°CRead and write
Heating Circuit 2 Cooling Curve Design Outdoor Temperature°CRead and write
Heating Circuit 2 Cooling Curve Design Flow Temperature°CRead and write
Heating Circuit 2 Heat Generator Flow Setpoint Offset°CRead and write
Heating Circuit 2 Minimum Flow Temperature°CRead and write
Heating Circuit 2 Maximum Flow Temperature°CRead and write
Heating Circuit 2 Minimum Flow Temperature Cooling°CRead and write
Heating Circuit 3 Heating Curve Base Flow Temperature°CRead and write
Heating Circuit 3 Heating Curve Design Outdoor Temperature°CRead and write
Heating Circuit 3 Heating Curve Design Flow Temperature°CRead and write
Heating Circuit 3 Control StrategyRead and write
Heating Circuit 3 Cooling Curve Base Flow Temperature°CRead and write
Heating Circuit 3 Summer Compensation Start Point°CRead and write
Heating Circuit 3 Cooling Curve Design Outdoor Temperature°CRead and write
Heating Circuit 3 Cooling Curve Design Flow Temperature°CRead and write
Heating Circuit 3 Heat Generator Flow Setpoint Offset°CRead and write
Heating Circuit 3 Minimum Flow Temperature°CRead and write
Heating Circuit 3 Maximum Flow Temperature°CRead and write
Heating Circuit 3 Minimum Flow Temperature Cooling°CRead and write
Available Power SourceRead and write
Dampened Power SourceRead and write
Dampened Power Time FilterminRead and write
Smart Grid Minimum PowerkWRead and write
SG Forced Acceptance ThresholdkWRead and write
SG Forced Acceptance HysteresiskWRead and write
SG Preferential Operation ThresholdkWRead and write
SG Preferential Operation HysteresiskWRead and write
Available Power OffsetkWRead and write
Available Power Dampened OffsetkWRead and write
SG Minimum Power HysteresiskWRead and write
Cascade 1 Sequence Change TimeRead and write
Heat Generator Operating Hours (Duplicate)hRead
Heat Generator Operating HourshRead
Heat Generator Switching CyclesRead
Heat Generator Operating Hours Above 50%hRead
Heat Generator Switching Cycles Above 50%Read
Heat Generator Heat Quantity HeatingMWhRead
Heat Generator Cooling QuantityMWhRead
Heat Generator Electrical EnergyMWhRead
FA Heat Quantity HeatingMWhRead
FA Heat Quantity CoolingMWhRead
FA Heat Quantity Hot WaterMWhRead
Additional Heat Operating HourshRead
Additional Heat Switching CyclesRead
Additional Heat Heat Quantity HeatingMWhRead
WFA Heating Running TimehRead
WFA Cooling Running TimehRead
WFA Hot Water Running TimehRead
ECR Additional Heating Operating HourshRead
ECR Additional Heating StartsRead
ECR Heating Operating HourshRead
ECR Hot Water Operating HourshRead
ECR Active Cooling Operating HourshRead
FA Burner ID IndexRead
FA Function ExtensionsRead
MK1 OutputRead and write
YK1+ OutputRead and write
YK1- OutputRead and write
DKP OutputRead and write
SLP OutputRead and write
VA1 OutputRead
VA2 OutputRead
VA1-FE1 OutputRead
VA2-FE1 OutputRead
VA3-FE1 OutputRead
VA1-FE2 OutputRead
VA2-FE2 OutputRead
VA3-FE2 OutputRead
VA 0-10V/PWM Output%Read
VA 0-10V/PWM FE1 Output%Read
Relay Test ActiveRead
WFA Application NumberRead
ECR Output Y1 0-10V/PWM%Read
ECR Output Y2 0-10V/PWM%Read
ECR Relay Output R9Read
ECR Relay Output R152Read
Active Error 1 Appearance TimeRead
Active Error 1 Appearance DateRead
Active Error 1 Disappear TimeRead
Active Error 1 Disappear DateRead
Active Error 1 SourceRead
Active Error 1 Function GroupRead
Active Error 1 Function NumberRead
Active Error 1 Error TypeRead
Active Error 1 Error CodeRead
Active Error 2 Appearance TimeRead
Active Error 2 Appearance DateRead
Active Error 2 Disappear TimeRead
Active Error 2 Disappear DateRead
Active Error 2 SourceRead
Active Error 2 Function GroupRead
Active Error 2 Function NumberRead
Active Error 2 Error TypeRead
Active Error 2 Error CodeRead
Active Error 3 Appearance TimeRead
Active Error 3 Appearance DateRead
Active Error 3 Disappear TimeRead
Active Error 3 Disappear DateRead
Active Error 3 SourceRead
Active Error 3 Function GroupRead
Active Error 3 Function NumberRead
Active Error 3 Error TypeRead
Active Error 3 Error CodeRead
Active Error 4 Appearance TimeRead
Active Error 4 Appearance DateRead
Active Error 4 Disappear TimeRead
Active Error 4 Disappear DateRead
Active Error 4 SourceRead
Active Error 4 Function GroupRead
Active Error 4 Function NumberRead
Active Error 4 Error TypeRead
Active Error 4 Error CodeRead
Active Error 5 Appearance TimeRead
Active Error 5 Appearance DateRead
Active Error 5 Disappear TimeRead
Active Error 5 Disappear DateRead
Active Error 5 SourceRead
Active Error 5 Function GroupRead
Active Error 5 Function NumberRead
Active Error 5 Error TypeRead
Active Error 5 Error CodeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Put flow, return and outdoor temperature, modulation and output of the boiler or heat pump on one dashboard for the boiler house.
  • Get an email, in-app or webhook alert when the heat generator status goes to fault or the error code changes.
  • Track operating hours, switching cycles and heat quantity over 365 days to plan maintenance and spot short cycling.
  • Change the operating mode and room or hot water setpoints remotely once writing is enabled for the gateway.
  • Write the available electrical power or the Smart Grid state from an automation on an energy price or a time schedule.

Installation

  1. Connect the Hoval Modbus gateway of the TopTronic E system to the same network as the ModbusCloud Gateway and give it a fixed IP address.

  2. Check on the TopTronic E operating module that the heat generator has module address 1. Another address uses other register addresses.

  3. In ModbusCloud, add a Modbus device with Modbus TCP, the IP address of the Hoval gateway, port 502 and unit ID 1, then import this template.

  4. Check that Outdoor Temperature AF1 and Heat Generator Flow Temperature show plausible values. Functions that are not installed may not answer.

  5. Keep the reading interval at the default 5 minutes. Hoval advises longer intervals as the number of requests to its gateway grows.

Things to watch for

The Hoval gateway does not answer. What should I check?

Check that the ModbusCloud Gateway reaches the IP address of the Hoval Modbus gateway, and use port 502 and unit ID 1. The Hoval gateway has to be registered in the HovalConnect app, which also keeps its software up to date. Data points of functions or modules that are not installed can time out, for example the SF2 hot water sensor when it is not fitted.

How do I read a second heat generator or a cascade?

Every heat generator has its own module address from 1 to 16 on the TopTronic E bus, shown on the operating module. Hoval gives each data point of each module address its own register address, with no fixed offset. This template is for address 1. For heat generator 2, make your own template in ModbusCloud with the addresses Hoval lists for WEZ UnitId 2 in its Modbus data point list.

Why does a setpoint I write have no effect?

Writing is off per gateway until you request it in the portal. Room setpoints only apply when Operation Choice of the heating circuit is 4 (constant), and hot water works the same way. Constant flow setpoints, manual heat generator modes and Smart Grid need basic settings by Hoval service first. A written value stays active until a new one is written.

How often should ModbusCloud read the Hoval gateway?

The default of every 5 minutes is a good choice. Hoval warns that its Modbus gateway can lock up when it gets too many requests. This template has many registers. If you only need a few values, make your own template with just those registers.

Why do some registers not answer on my boiler?

The template holds the values of every heat generator type, including the heat pump controllers WFA-200 and ECR461 and the cascade manager. On a boiler without those functions these data points can time out or show no useful value. Leave them off your dashboards or out of your own template.