Hoval TopTronic E Measuring Module
Hoval module for up to 16 M-Bus meters with energy, power, flow, volume and temperatures over Modbus TCP.
The Hoval TopTronic E Measuring Module is a controller module that reads up to 16 meters over M-Bus in Hoval TopTronic E systems, for example in boiler plants and greenhouses. This Modbus TCP template reads energy, power, flow, volume and temperatures of every meter through the Hoval Modbus gateway into ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 221, read only
- Brand
- Hoval
- Key readings
- Energy · Power · Flow rate · Volume · Flow and return temperature · Temperature difference · Current, voltage and cos phi · Meter serial number
- Compatible models
- TopTronic E measuring module (MWA)
- Last updated
Registers (221)
221 read, 0 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| M-Bus Meter 1 Energy | MWh | Read | |||
| M-Bus Meter 1 Power | kW | Read | |||
| M-Bus Meter 1 Flow Rate | l/h | Read | |||
| M-Bus Meter 1 Volume | m³ | Read | |||
| M-Bus Meter 1 Flow Temperature | °C | Read | |||
| M-Bus Meter 1 Return Temperature | °C | Read | |||
| M-Bus Meter 1 Temperature Difference | K | Read | |||
| M-Bus Meter 1 Current | A | Read | |||
| M-Bus Meter 1 Voltage | V | Read | |||
| M-Bus Meter 1 Cos Phi | Read | ||||
| M-Bus Meter 1 Serial Number | Read | ||||
| M-Bus Meter 2 Energy | MWh | Read | |||
| M-Bus Meter 2 Power | kW | Read | |||
| M-Bus Meter 2 Flow Rate | l/h | Read | |||
| M-Bus Meter 2 Volume | m³ | Read | |||
| M-Bus Meter 2 Flow Temperature | °C | Read | |||
| M-Bus Meter 2 Return Temperature | °C | Read | |||
| M-Bus Meter 2 Temperature Difference | K | Read | |||
| M-Bus Meter 2 Current | A | Read | |||
| M-Bus Meter 2 Voltage | V | Read | |||
| M-Bus Meter 2 Cos Phi | Read | ||||
| M-Bus Meter 2 Serial Number | Read | ||||
| M-Bus Meter 3 Energy | MWh | Read | |||
| M-Bus Meter 3 Power | kW | Read | |||
| M-Bus Meter 3 Flow Rate | l/h | Read | |||
| M-Bus Meter 3 Volume | m³ | Read | |||
| M-Bus Meter 3 Flow Temperature | °C | Read | |||
| M-Bus Meter 3 Return Temperature | °C | Read | |||
| M-Bus Meter 3 Temperature Difference | K | Read | |||
| M-Bus Meter 3 Current | A | Read | |||
| M-Bus Meter 3 Voltage | V | Read | |||
| M-Bus Meter 3 Cos Phi | Read | ||||
| M-Bus Meter 3 Serial Number | Read | ||||
| M-Bus Meter 4 Energy | MWh | Read | |||
| M-Bus Meter 4 Power | kW | Read | |||
| M-Bus Meter 4 Flow Rate | l/h | Read | |||
| M-Bus Meter 4 Volume | m³ | Read | |||
| M-Bus Meter 4 Flow Temperature | °C | Read | |||
| M-Bus Meter 4 Return Temperature | °C | Read | |||
| M-Bus Meter 4 Temperature Difference | K | Read | |||
| M-Bus Meter 4 Current | A | Read | |||
| M-Bus Meter 4 Voltage | V | Read | |||
| M-Bus Meter 4 Cos Phi | Read | ||||
| M-Bus Meter 4 Serial Number | Read | ||||
| M-Bus Meter 5 Energy | MWh | Read | |||
| M-Bus Meter 5 Power | kW | Read | |||
| M-Bus Meter 5 Flow Rate | l/h | Read | |||
| M-Bus Meter 5 Volume | m³ | Read | |||
| M-Bus Meter 5 Flow Temperature | °C | Read | |||
| M-Bus Meter 5 Return Temperature | °C | Read | |||
| M-Bus Meter 5 Temperature Difference | K | Read | |||
| M-Bus Meter 5 Current | A | Read | |||
| M-Bus Meter 5 Voltage | V | Read | |||
| M-Bus Meter 5 Cos Phi | Read | ||||
| M-Bus Meter 5 Serial Number | Read | ||||
| M-Bus Meter 6 Energy | MWh | Read | |||
| M-Bus Meter 6 Power | kW | Read | |||
| M-Bus Meter 6 Flow Rate | l/h | Read | |||
| M-Bus Meter 6 Volume | m³ | Read | |||
| M-Bus Meter 6 Flow Temperature | °C | Read | |||
| M-Bus Meter 6 Return Temperature | °C | Read | |||
| M-Bus Meter 6 Temperature Difference | K | Read | |||
| M-Bus Meter 6 Current | A | Read | |||
| M-Bus Meter 6 Voltage | V | Read | |||
| M-Bus Meter 6 Cos Phi | Read | ||||
| M-Bus Meter 6 Serial Number | Read | ||||
| M-Bus Meter 7 Energy | MWh | Read | |||
| M-Bus Meter 7 Power | kW | Read | |||
| M-Bus Meter 7 Flow Rate | l/h | Read | |||
| M-Bus Meter 7 Volume | m³ | Read | |||
| M-Bus Meter 7 Flow Temperature | °C | Read | |||
| M-Bus Meter 7 Return Temperature | °C | Read | |||
| M-Bus Meter 7 Temperature Difference | K | Read | |||
| M-Bus Meter 7 Current | A | Read | |||
| M-Bus Meter 7 Voltage | V | Read | |||
| M-Bus Meter 7 Cos Phi | Read | ||||
| M-Bus Meter 7 Serial Number | Read | ||||
| M-Bus Meter 8 Energy | MWh | Read | |||
| M-Bus Meter 8 Power | kW | Read | |||
| M-Bus Meter 8 Flow Rate | l/h | Read | |||
| M-Bus Meter 8 Volume | m³ | Read | |||
| M-Bus Meter 8 Flow Temperature | °C | Read | |||
| M-Bus Meter 8 Return Temperature | °C | Read | |||
| M-Bus Meter 8 Temperature Difference | K | Read | |||
| M-Bus Meter 8 Current | A | Read | |||
| M-Bus Meter 8 Voltage | V | Read | |||
| M-Bus Meter 8 Cos Phi | Read | ||||
| M-Bus Meter 8 Serial Number | Read | ||||
| M-Bus Meter 9 Energy | MWh | Read | |||
| M-Bus Meter 9 Power | kW | Read | |||
| M-Bus Meter 9 Flow Rate | l/h | Read | |||
| M-Bus Meter 9 Volume | m³ | Read | |||
| M-Bus Meter 9 Flow Temperature | °C | Read | |||
| M-Bus Meter 9 Return Temperature | °C | Read | |||
| M-Bus Meter 9 Temperature Difference | K | Read | |||
| M-Bus Meter 9 Current | A | Read | |||
| M-Bus Meter 9 Voltage | V | Read | |||
| M-Bus Meter 9 Cos Phi | Read | ||||
| M-Bus Meter 9 Serial Number | Read | ||||
| M-Bus Meter 10 Energy | MWh | Read | |||
| M-Bus Meter 10 Power | kW | Read | |||
| M-Bus Meter 10 Flow Rate | l/h | Read | |||
| M-Bus Meter 10 Volume | m³ | Read | |||
| M-Bus Meter 10 Flow Temperature | °C | Read | |||
| M-Bus Meter 10 Return Temperature | °C | Read | |||
| M-Bus Meter 10 Temperature Difference | K | Read | |||
| M-Bus Meter 10 Current | A | Read | |||
| M-Bus Meter 10 Voltage | V | Read | |||
| M-Bus Meter 10 Cos Phi | Read | ||||
| M-Bus Meter 10 Serial Number | Read | ||||
| M-Bus Meter 11 Energy | MWh | Read | |||
| M-Bus Meter 11 Power | kW | Read | |||
| M-Bus Meter 11 Flow Rate | l/h | Read | |||
| M-Bus Meter 11 Volume | m³ | Read | |||
| M-Bus Meter 11 Flow Temperature | °C | Read | |||
| M-Bus Meter 11 Return Temperature | °C | Read | |||
| M-Bus Meter 11 Temperature Difference | K | Read | |||
| M-Bus Meter 11 Current | A | Read | |||
| M-Bus Meter 11 Voltage | V | Read | |||
| M-Bus Meter 11 Cos Phi | Read | ||||
| M-Bus Meter 11 Serial Number | Read | ||||
| M-Bus Meter 12 Energy | MWh | Read | |||
| M-Bus Meter 12 Power | kW | Read | |||
| M-Bus Meter 12 Flow Rate | l/h | Read | |||
| M-Bus Meter 12 Volume | m³ | Read | |||
| M-Bus Meter 12 Flow Temperature | °C | Read | |||
| M-Bus Meter 12 Return Temperature | °C | Read | |||
| M-Bus Meter 12 Temperature Difference | K | Read | |||
| M-Bus Meter 12 Current | A | Read | |||
| M-Bus Meter 12 Voltage | V | Read | |||
| M-Bus Meter 12 Cos Phi | Read | ||||
| M-Bus Meter 12 Serial Number | Read | ||||
| M-Bus Meter 13 Energy | MWh | Read | |||
| M-Bus Meter 13 Power | kW | Read | |||
| M-Bus Meter 13 Flow Rate | l/h | Read | |||
| M-Bus Meter 13 Volume | m³ | Read | |||
| M-Bus Meter 13 Flow Temperature | °C | Read | |||
| M-Bus Meter 13 Return Temperature | °C | Read | |||
| M-Bus Meter 13 Temperature Difference | K | Read | |||
| M-Bus Meter 13 Current | A | Read | |||
| M-Bus Meter 13 Voltage | V | Read | |||
| M-Bus Meter 13 Cos Phi | Read | ||||
| M-Bus Meter 13 Serial Number | Read | ||||
| M-Bus Meter 14 Energy | MWh | Read | |||
| M-Bus Meter 14 Power | kW | Read | |||
| M-Bus Meter 14 Flow Rate | l/h | Read | |||
| M-Bus Meter 14 Volume | m³ | Read | |||
| M-Bus Meter 14 Flow Temperature | °C | Read | |||
| M-Bus Meter 14 Return Temperature | °C | Read | |||
| M-Bus Meter 14 Temperature Difference | K | Read | |||
| M-Bus Meter 14 Current | A | Read | |||
| M-Bus Meter 14 Voltage | V | Read | |||
| M-Bus Meter 14 Cos Phi | Read | ||||
| M-Bus Meter 14 Serial Number | Read | ||||
| M-Bus Meter 15 Energy | MWh | Read | |||
| M-Bus Meter 15 Power | kW | Read | |||
| M-Bus Meter 15 Flow Rate | l/h | Read | |||
| M-Bus Meter 15 Volume | m³ | Read | |||
| M-Bus Meter 15 Flow Temperature | °C | Read | |||
| M-Bus Meter 15 Return Temperature | °C | Read | |||
| M-Bus Meter 15 Temperature Difference | K | Read | |||
| M-Bus Meter 15 Current | A | Read | |||
| M-Bus Meter 15 Voltage | V | Read | |||
| M-Bus Meter 15 Cos Phi | Read | ||||
| M-Bus Meter 15 Serial Number | Read | ||||
| M-Bus Meter 16 Energy | MWh | Read | |||
| M-Bus Meter 16 Power | kW | Read | |||
| M-Bus Meter 16 Flow Rate | l/h | Read | |||
| M-Bus Meter 16 Volume | m³ | Read | |||
| M-Bus Meter 16 Flow Temperature | °C | Read | |||
| M-Bus Meter 16 Return Temperature | °C | Read | |||
| M-Bus Meter 16 Temperature Difference | K | Read | |||
| M-Bus Meter 16 Current | A | Read | |||
| M-Bus Meter 16 Voltage | V | Read | |||
| M-Bus Meter 16 Cos Phi | Read | ||||
| M-Bus Meter 16 Serial Number | Read | ||||
| Active Error 1 Appearance Time | Read | ||||
| Active Error 1 Appearance Date | Read | ||||
| Active Error 1 Disappear Time | Read | ||||
| Active Error 1 Disappear Date | Read | ||||
| Active Error 1 Source | Read | ||||
| Active Error 1 Function Group | Read | ||||
| Active Error 1 Function Number | Read | ||||
| Active Error 1 Error Type | Read | ||||
| Active Error 1 Error Code | Read | ||||
| Active Error 2 Appearance Time | Read | ||||
| Active Error 2 Appearance Date | Read | ||||
| Active Error 2 Disappear Time | Read | ||||
| Active Error 2 Disappear Date | Read | ||||
| Active Error 2 Source | Read | ||||
| Active Error 2 Function Group | Read | ||||
| Active Error 2 Function Number | Read | ||||
| Active Error 2 Error Type | Read | ||||
| Active Error 2 Error Code | Read | ||||
| Active Error 3 Appearance Time | Read | ||||
| Active Error 3 Appearance Date | Read | ||||
| Active Error 3 Disappear Time | Read | ||||
| Active Error 3 Disappear Date | Read | ||||
| Active Error 3 Source | Read | ||||
| Active Error 3 Function Group | Read | ||||
| Active Error 3 Function Number | Read | ||||
| Active Error 3 Error Type | Read | ||||
| Active Error 3 Error Code | Read | ||||
| Active Error 4 Appearance Time | Read | ||||
| Active Error 4 Appearance Date | Read | ||||
| Active Error 4 Disappear Time | Read | ||||
| Active Error 4 Disappear Date | Read | ||||
| Active Error 4 Source | Read | ||||
| Active Error 4 Function Group | Read | ||||
| Active Error 4 Function Number | Read | ||||
| Active Error 4 Error Type | Read | ||||
| Active Error 4 Error Code | Read | ||||
| Active Error 5 Appearance Time | Read | ||||
| Active Error 5 Appearance Date | Read | ||||
| Active Error 5 Disappear Time | Read | ||||
| Active Error 5 Disappear Date | Read | ||||
| Active Error 5 Source | Read | ||||
| Active Error 5 Function Group | Read | ||||
| Active Error 5 Function Number | Read | ||||
| Active Error 5 Error Type | Read | ||||
| Active Error 5 Error Code | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Collect the meter readings of a boiler house or of greenhouse sections in one dashboard and compare energy per meter.
- Track energy and volume over 365 days and download them as CSV for an energy report or an invoice check.
- Get an alert when the power or the temperature difference of a meter crosses a threshold.
- Share a PDF report with the energy readings of each meter with the building owner.
Installation
Connect the Hoval Modbus gateway of the TopTronic E system to the same network as the ModbusCloud Gateway and give it a fixed IP address.
Check the address of the measuring module on its DIP switch or on the TopTronic E operating module. This template is for module address 1.
In ModbusCloud, add a Modbus device with Modbus TCP, the IP address of the Hoval gateway, port 502 and unit ID 1, then import this template.
Check that M-Bus Meter 1 Energy and M-Bus Meter 1 Serial Number match the display and type plate of the first meter.
Things to watch for
The Hoval gateway does not answer. What should I check?
Check that the ModbusCloud Gateway reaches the IP address of the Hoval Modbus gateway, and use port 502 and unit ID 1. The Hoval gateway has to be registered in the HovalConnect app. Meter positions without a meter can time out.
Which meter is M-Bus Meter 1?
M-Bus Meter 1 to 16 are the meter positions of the measuring module. Compare the Serial Number register of each position with the serial number on the type plate of the meter to see which meter sits where.
How do I read a second measuring module?
Every module has its own address on the TopTronic E bus. In the Hoval Modbus data point list the module with address n is MWA UnitId 384 plus n, with its own register addresses. This template is for UnitId 385. Make your own template in ModbusCloud with the addresses Hoval lists for your UnitId.
In which units do the meter values arrive?
Energy comes in MWh with three decimals, a resolution of 1 kWh. Power comes in kW and volume in m³, each with one decimal, and the flow rate in l/h. Compare one reading with the meter display before you use the values for billing.