HygroMatik HygroMatik FlexLine Modbus RTU template

HygroMatik FlexLine

Steam humidifier for air handling units and steam baths, with remote setpoints and fault codes.

The HygroMatik FlexLine is a steam humidifier that produces steam with electrode or heater cylinders for air handling units, process rooms and steam baths. This Modbus RTU template reads steam output, humidity, temperature, states and fault messages, and lets you set humidity and temperature setpoints, ECO mode and steam on or off from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
49, read and write
Key readings
Steam output · Relative humidity · Temperature · Demand · Cylinder current · Water level · Unit state · Fault message
Available commands
Humidity setpoint · Temperature setpoint · ECO mode · Steam on or off · Maximum steam output · Demand via Modbus
Compatible models
FlexLine electrode steam humidifier (FLE) · FlexLine heater steam humidifier (FLH) · FlexLine FLE · FlexLine FLH · FlexLine Spa
Last updated

Registers (49)

49 read, 21 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Steam Output Unitkg/hRead
Steam Output Cylinder 1kg/hRead
Steam Output Cylinder 2kg/hRead
Humidity Actual Value%Read
Humidity Actual Max%Read
Humidity Setpoint Active%Read
Humidity Set Max%Read
Temperature Actual Value°CRead
Temperature Setpoint Active°CRead
Temperature Actual Value 1°CRead
Temperature Actual Value 2°CRead
Demand%Read
Demand PI%Read
Demand SPA%Read
Control Signal Internal%Read
Current Cylinder 1ARead
Current Cylinder 2ARead
Water Level Cylinder 1mmRead
Water Level Cylinder 2mmRead
Safety InterlockRead
Status UnitRead
Fault Message UnitRead
Status Cylinder 1Read
Fault Message Cylinder 1Read
Service Message Cylinder 1Read
Status Cylinder 2Read
Fault Message Cylinder 2Read
Service Message Cylinder 2Read
Demand Via Modbus%Read and write
Modbus CountersRead and write
Safety Interlock VirtualRead and write
ECO ModeRead and write
Humidity Setpoint%Read and write
Dehumidification Setpoint Delta%Read and write
Humidity ECO Delta%Read and write
Humidity PI Gain%Read and write
Humidity PI Integral%Read and write
Temperature Setpoint°CRead and write
Temperature Steam Off Delta°CRead and write
Temperature ECO Delta°CRead and write
Temperature Max Delta°CRead and write
Temperature PI Gain%Read and write
Temperature PI Integral%Read and write
Steam Output Max%Read and write
Light 1Read and write
Light 2Read and write
Light 3Read and write
Light 4Read and write
Modbus TimeoutsRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show actual humidity, setpoint and steam output of each humidifier on a dashboard per air handling unit.
  • Send an email when Fault Message Unit is not 0, with the fault shown as text.
  • Alert on a service message such as electrode or pump warning before the cylinder needs replacing.
  • Keep a 365-day history of humidity and steam output to show that a process room stayed in range.
  • Raise or lower the humidity setpoint remotely when the use of a room changes.

Installation

  1. With the board switched off, plug the RS485 interface option onto the FlexLine main board and fix it with the locking post.

  2. Wire the 3-pole plug to the RS485 bus of the ModbusCloud Gateway. Set jumper X3 on the units at both ends of the line, and X2 and X4 on one unit only.

  3. Check address, baud rate, parity and stop bits in the unit control. Factory settings are address 1, 19200 baud, no parity, 1 stop bit.

  4. In ModbusCloud, add a Modbus device with the same settings and import the HygroMatik FlexLine template.

  5. Check that Status Unit shows a plain state such as Humidification or No demand and that Humidity Actual Value matches the display.

Things to watch for

The humidifier does not answer. What should I check?

Check that the RS485 interface option is fitted on the main board and fully seated. Then compare address, baud rate and parity with the Modbus device in ModbusCloud; the factory setting is 19200 baud without parity. Swap A and B if needed, and check that termination jumper X3 is set only at the two ends of the line.

Steam production stops when I control demand over Modbus.

With Control_settings on Modbus, the demand must be rewritten cyclically together with Modbus Counter set to 0. If the counter passes the Modbus Timeout (factory 20 s), steam stops on purpose. ModbusCloud is not meant for this fast refresh; keep the demand on the analog input or internal controller, or let the building management system write it.

The cylinder current looks ten times too high.

The cylinder current registers have no clear scale factor: cylinder 1 is listed with factor 1 and cylinder 2 with factor 10 for the same range. The template uses scale 1 for both. Compare the value with the display and change the scale in ModbusCloud if needed.

What happens when I write to the humidifier?

Setpoints, ECO offsets and PI settings take effect immediately and change the humidity in the room. Writing 0 to Safety Interlock Virtual switches steam production off until you write 1. Agree on values with whoever maintains the air handling unit before you change them.

Want to see how it works?