Invertek Optidrive P2

High performance frequency drive for pumps, fans, compressors and machines, with speed, torque and status.

The Invertek Optidrive P2 is a high performance variable frequency drive for induction, permanent magnet and synchronous reluctance motors on pumps, fans, compressors and machines. This Modbus RTU template reads frequency, current, torque, power, temperature and trip status, and lets you start, stop and reset the drive and write speed, torque and parameters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 115200 baud
Registers
108, read and write
Key readings
Output frequency · Output current · Output torque · Output power · DC bus voltage · Heatsink temperature · Drive status and trip code
Available commands
Run and stop · Fault reset · Speed reference · Torque reference · Ramp time · Drive parameters
Compatible models
Optidrive P2 IP20 (ODP-2-...) · Optidrive P2 IP55 · Optidrive P2 IP66
Last updated

Registers (108)

108 read, 97 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Output FrequencyHzRead
Output CurrentARead
Output Torque%Read
Output PowerkWRead
DC Bus VoltageVRead
Drive Temperature°CRead
Drive Status and Error CodeRead
Digital Input StatusRead
Analog Input 1 Level%Read
Analog Input 2 Level%Read
Pre Ramp Speed ReferenceRead
Command Control WordRead and write
Command Speed ReferenceHzRead and write
Command Torque Reference%Read and write
Command Ramp TimessRead and write
P1-01 Maximum Frequency / Speed LimitRead and write
P1-02 Minimum Frequency / Speed LimitRead and write
P1-03 Acceleration Ramp TimeRead and write
P1-04 Deceleration Ramp TimeRead and write
P1-05 Stop ModeRead and write
P1-06 Energy OptimiserRead and write
P1-07 Motor Rated Voltage / kERead and write
P1-08 Motor Rated CurrentRead and write
P1-09 Motor Rated FrequencyRead and write
P1-10 Motor Rated SpeedRead and write
P1-11 Boost VoltageRead and write
P1-12 Primary Command SourceRead and write
P1-13 Digital Input FunctionRead and write
P1-14 Extended Menu AccessRead and write
P2-01 Preset Speed 1Read and write
P2-02 Preset Speed 2Read and write
P2-03 Preset Speed 3Read and write
P2-04 Preset Speed 4Read and write
P2-05 Preset Speed 5Read and write
P2-06 Preset Speed 6Read and write
P2-07 Preset Speed 7Read and write
P2-08 Preset Speed 8Read and write
P2-09 Skip Frequency Centre PointRead and write
P2-10 Skip Frequency Band WidthRead and write
P2-11 Analog Output 1 FunctionRead and write
P2-12 Analog Output 1 FormatRead and write
P2-13 Analog Output 2 FunctionRead and write
P2-14 Analog Output 2 FormatRead and write
P2-15 Relay 1 FunctionRead and write
P2-16 Relay 1 / AO1 Upper LimitRead and write
P2-17 Relay 1 / AO1 Lower LimitRead and write
P2-18 Relay 2 FunctionRead and write
P2-19 Relay 2 / AO2 Upper LimitRead and write
P2-20 Relay 2 / AO2 Lower LimitRead and write
P2-21 Display Scaling FactorRead and write
P2-22 Display Scaling SourceRead and write
P2-23 Zero Speed Holding TimeRead and write
P2-24 Effective Switching FrequencyRead and write
P2-25 Fast Decel Ramp TimeRead and write
P2-26 Spin Start EnableRead and write
P2-27 Standby Mode TimerRead and write
P2-28 Slave Speed Scaling ControlRead and write
P2-29 Slave Speed Scaling FactorRead and write
P2-30 Analog Input 1 FormatRead and write
P2-31 Analog Input 1 ScalingRead and write
P2-32 Analog Input 1 OffsetRead and write
P2-33 Analog Input 2 FormatRead and write
P2-34 Analog Input 2 ScalingRead and write
P2-35 Analog Input 2 OffsetRead and write
P2-36 Start Mode / Automatic RestartRead and write
P2-37 Keypad Start ModeRead and write
P2-38 Mains Loss Stop / Ride ThroughRead and write
P2-39 Parameter LockRead and write
P2-40 Extended Menu Access CodeRead and write
P3-01 PID Proportional GainRead and write
P3-02 PID Integral Time ConstantRead and write
P3-03 PID Differential Time ConstantRead and write
P3-04 PID Operating ModeRead and write
P3-05 PID Reference SelectRead and write
P3-06 PID Digital Reference ValueRead and write
P3-07 PID Output Upper LimitRead and write
P3-08 PID Output Lower LimitRead and write
P3-09 PID Output Limit SelectRead and write
P3-10 PID Feedback SelectRead and write
P3-11 PID Error To Enable RampRead and write
P3-12 PID Feedback Display ScalingRead and write
P3-13 PID Error Wake LevelRead and write
P3-18 PID Reset ControlRead and write
P4-01 Motor Control ModeRead and write
P4-02 Motor Auto-tune EnableRead and write
P4-03 Vector Speed Controller P GainRead and write
P4-04 Vector Speed Controller Integral TimeRead and write
P4-05 Motor Power FactorRead and write
P4-06 Torque Control Reference / Limit SourceRead and write
P4-07 Maximum Torque / Current LimitRead and write
P4-08 Minimum Torque LimitRead and write
P4-09 Regenerative Torque LimitRead and write
P4-10 V/F Adjustment FrequencyRead and write
P4-11 V/F Adjustment VoltageRead and write
P4-12 Thermal Overload RetentionRead and write
P4-13 Output Phase SequenceRead and write
P4-14 Thermal Overload ReactionRead and write
P4-15 Master Mode ConfigurationRead and write
P5-02 CAN Baud RateRead and write
P5-05 Communications Loss TimeoutRead and write
P5-06 Communications Loss ActionRead and write
P5-07 Fieldbus Ramp ControlRead and write
P5-08 Fieldbus PDO-4 Data SelectRead and write
P5-12 Fieldbus PDO-3 Data SelectRead and write
P5-13 Fieldbus PDI-4 Function SelectRead and write
P5-14 Fieldbus PDI-3 Function SelectRead and write
P5-15 Modbus Response DelayRead and write
P5-16 Drive Modbus AddressRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Put frequency, current and power of every P2 drive in a plant on one dashboard.
  • Send an e-mail when the drive status shows a trip, or when heatsink temperature passes a limit you choose.
  • Keep a history of output torque and current to see when a pump or conveyor starts to need more effort.
  • Change the speed reference or the PID setpoint from ModbusCloud without a visit to the site.
  • Compare DC bus voltage and power over weeks to spot supply problems or a changing load.

Installation

  1. Connect pin 7 (RS485-), pin 8 (RS485+) and pin 3 (0 V) of the RJ45 port in the drive wiring enclosure to the RS485 port of the ModbusCloud Gateway. Terminate both ends with 120 ohm.

  2. Set address P5-01, baud rate P5-03 and data format P5-04 on the drive (default 1, 115200 baud, no parity, 1 stop bit). For control over Modbus set P1-12 to 4.

  3. In ModbusCloud, add a Modbus device with the same address and serial settings and import this template.

  4. Check that output frequency, DC bus voltage and drive status come in with plausible values.

Things to watch for

The drive does not answer. What should I check?

Compare P5-01, P5-03 and P5-04 with the settings in ModbusCloud. Use pins 7 and 8 of the RJ45 port, not 4 and 5 which carry Optibus for keypads and PC, and connect the 0 V on pin 3. A fieldbus option module in the option slot switches Modbus RTU off.

The motor does not start when I write the control word.

Modbus control works only with P1-12 set to 4 and no fieldbus module installed. The drive also needs its enable input and both Safe Torque Off inputs. Set bit 0 to run; a reset with bit 2 must be cleared again once the fault is gone.

Why does a parameter read 500 when the display shows 50.0?

Parameters with one decimal place are sent multiplied by ten. The template applies this factor for those parameters. A few parameters with two or three decimals are shown raw; compare them with the drive display before you write.

The drive trips on loss of communication.

P5-05 sets the watchdog time, default 1.0 s, and P5-06 what the drive does when no valid message arrives. Poll at least one register faster than that, set a longer time, or set P5-05 to 0 to switch the watchdog off.

What should I keep in mind when writing parameters?

A written parameter takes effect in the drive at once and changes how the motor runs. Read the current value first, write one parameter at a time and check the display. Some parameters cannot be changed while the drive runs, and P4-02 starts an autotune immediately.

Want to see how it works?