Invertek Optidrive E3

Variable frequency drive for pumps, fans and conveyors, with speed control, motor data and trip status.

The Invertek Optidrive E3 is a compact variable frequency drive that controls the speed of motors on pumps, fans, compressors and conveyors. This Modbus RTU template reads frequency, current, power, temperatures, status and trip codes, and lets you start, stop and reset the drive and write the speed setpoint and parameters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 115200 baud
Registers
116, read and write
Key readings
Output frequency · Motor current · Motor power · DC bus voltage · Heatsink temperature · Drive status · Trip code · Energy meter
Available commands
Run and stop · Fault reset · Speed setpoint · Ramp time · Drive parameters
Compatible models
Optidrive E3 IP20 (ODE-3-...) · Optidrive E3 IP66 indoor · Optidrive E3 IP66 outdoor · Optidrive Compact 2 Basic (OPC-2-...E)
Last updated

Registers (116)

116 read, 65 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Output FrequencyHzRead
Motor CurrentARead
Motor TorqueRead
Motor PowerkWRead
DC Bus VoltageVRead
Drive Power Stage Temperature°CRead
Output VoltageVRead
Drive Status and Error CodeRead
Trip CodeRead
Status Word 2Read
Motor Output SpeedHzRead
Motor Output CurrentARead
Motor Output PowerkWRead
IO Status WordRead
Motor Output TorqueRead
DC Bus Voltage (Extended)VRead
Heatsink Temperature°CRead
Analog Input 1 (Extended)%Read
Analog Input 2 (Extended)%Read
Analog Output%Read
PI Output%Read
Internal Temperature°CRead
Motor Output VoltageVRead
IP66 Pot Input Value%Read
Digital Input StatusRead
Relay Output StatusRead
Analog Input 1%Read
Analog Input 2%Read
Pre-Ramp Speed ReferenceHzRead
Internal Drive Temperature°CRead
Speed Reference (Internal Format)Read
Digital Pot / Keypad ReferenceRead
Scope Channel 1 DataRead
Scope Channel 2 DataRead
Control WordRead and write
Frequency SetpointHzRead and write
PI Setpoint / Analog Output ControlRead and write
Ramp TimesRead and write
High Resolution Frequency SetpointRead and write
Parameter Access IndexRead and write
Parameter Access ValueRead and write
Energy Meter kWhkWhRead
Energy Meter MWhMWhRead
Running Time HourshRead
Running Time Minutes and SecondssRead
Run Time Since Last Enable HourshRead
Run Time Since Last Enable SecondssRead
Parameter ChecksumRead
Rating IDRead
Power RatingkWRead
Voltage RatingRead
IO Processor Software VersionRead
Motor Control Processor Software VersionRead
Drive TypeRead
Drive Serial Number 4Read
Drive Serial Number 3Read
Drive Serial Number 2Read
Drive Serial Number 1Read
P-04 Deceleration Ramp TimeRead and write
P-05 Stopping Mode / Mains Loss ResponseRead and write
P-06 Energy OptimiserRead and write
P-07 Motor Rated VoltageRead and write
P-08 Motor Rated CurrentRead and write
P-09 Motor Rated FrequencyRead and write
P-10 Motor Rated SpeedRead and write
P-11 Low Frequency Torque BoostRead and write
P-12 Primary Command SourceRead and write
P-13 Operating Mode SelectRead and write
P-14 Extended Menu Access CodeRead and write
P-15 Digital Input Function SelectRead and write
P-16 Analog Input 1 Signal FormatRead and write
P-17 Maximum Effective Switching FrequencyRead and write
P-18 Output Relay Function SelectRead and write
P-19 Relay Threshold LevelRead and write
P-20 Preset Speed 1Read and write
P-21 Preset Speed 2Read and write
P-22 Preset Speed 3Read and write
P-23 Preset Speed 4Read and write
P-24 2nd Ramp Time (Fast Stop)Read and write
P-25 Analog Output Function SelectRead and write
P-26 Skip Frequency Hysteresis BandRead and write
P-27 Skip Frequency Centre PointRead and write
P-28 V/F Adjustment VoltageRead and write
P-29 V/F Adjustment FrequencyRead and write
P-30 Start Mode, Restart and Fire ModeRead and write
P-31 Keypad Start Mode SelectRead and write
P-32 DC Injection ConfigurationRead and write
P-33 Spin StartRead and write
P-34 Brake Chopper EnableRead and write
P-35 Analog Input 1 ScalingRead and write
P-36 Serial Communications ConfigurationRead and write
P-37 Access Code DefinitionRead and write
P-38 Parameter Access LockRead and write
P-39 Analog Input 1 OffsetRead and write
P-40 Display ScalingRead and write
P-41 PI Proportional GainRead and write
P-42 PI Integral TimeRead and write
P-43 PI Operating ModeRead and write
P-44 PI Setpoint SourceRead and write
P-45 PI Digital SetpointRead and write
P-46 PI Feedback SourceRead and write
P-47 Analog Input 2 Signal FormatRead and write
P-48 Standby Mode TimerRead and write
P-49 PI Wake Up Error LevelRead and write
P-50 Output Relay HysteresisRead and write
P-51 Motor Control ModeRead and write
P-52 Motor Parameter AutotuneRead and write
P-53 Vector Mode GainRead and write
P-54 Maximum Current LimitRead and write
P-55 Motor Stator ResistanceRead and write
P-56 Motor Stator d-axis InductanceRead and write
P-57 Motor Stator q-axis InductanceRead and write
P-58 DC Injection SpeedRead and write
P-59 DC Injection CurrentRead and write
P-60 Motor Overload ManagementRead and write
P-63 Modbus Mode SelectionRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show frequency, motor current and power of every pump or fan drive on one dashboard.
  • Send an e-mail when the trip code changes from No fault, for example on over current or DC bus over voltage.
  • Keep a history of motor current and heatsink temperature to spot a pump or bearing that starts to wear.
  • Change the speed setpoint of a fan or pump from ModbusCloud without a visit on site.
  • Read the kWh meter and run hours per drive to report energy use and plan maintenance.

Installation

  1. Connect pin 7 (RS485-), pin 8 (RS485+) and pin 3 (0 V) of the RJ45 port on the drive to the RS485 port of the ModbusCloud Gateway. Terminate both ends of the bus.

  2. Set the drive address and baud rate in P-36 (default address 1, 115200 baud). For control over Modbus also set P-12 to 3 or 4.

  3. In ModbusCloud, add a Modbus device with the same address and serial settings (8 data bits, no parity, 1 stop bit) and import this template.

  4. Check that output frequency, DC bus voltage and drive status show plausible values.

Things to watch for

The drive does not answer. What should I check?

Compare address and baud rate in P-36 with the settings in ModbusCloud; the factory speed is 115200 baud, 8 data bits, no parity, 1 stop bit. Check that you use pins 7 and 8 of the RJ45 port, not 4 and 5, which are for the keypad and PC. Plug the cable into the drive only, never into an Ethernet port.

I write the control word but the motor does not start.

The drive only takes run commands over Modbus when P-12 is 3 or 4, and digital input 1 must be closed as hardware enable. With P-31 set to a terminal start option the keypad and fieldbus start commands are ignored. Bit 0 is run, bit 2 resets a fault.

The drive trips with a Modbus comms loss fault.

P-36 index 3 sets a watchdog: when no valid message arrives within that time the drive trips or coasts to stop. Poll at least one register faster than the timeout, or set the watchdog to 0 when the drive does not need it. P-63 decides whether messages for other addresses also count.

Several drives on one bus answer at the same time.

Every drive leaves the factory with address 1. Give each drive its own address in P-36 index 1 before you connect them to the same RS485 line, and add each one in ModbusCloud as a separate device.

What should I keep in mind when writing parameters?

Parameter values go straight into the drive and change how the motor runs. Some parameters use an internal scaling, so read the current value first and compare it with the drive display before you write. Some cannot be changed while the drive is running, and P-52 starts an autotune at once.

More RTU templates