Kostal Kostal Inverter Modbus RTU template

Kostal Inverter

Reads values from Kostal inverters via RS485 Modbus connection.

This template reads operational values from Kostal solar inverters via an RS485 Modbus RTU connection at 19200 baud. It enables remote monitoring of inverter data through the ModbusCloud platform, giving installers insight into PV system performance without being on site.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
0, read only
Brand
Kostal
Last updated

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time PV production from Kostal inverters on a centralized cloud dashboard.
  • Log daily and cumulative energy yield for reporting and performance analysis.
  • Create alerts when inverter output drops unexpectedly, indicating a potential fault or shading issue.
  • Compare production data across multiple Kostal inverter installations from a single platform.
  • Verify correct system operation after commissioning without returning to the installation site.

Installation

  1. Connect the ModbusCloud Gateway to the RS485 terminals on the Kostal inverter using a twisted pair cable with correct A and B polarity.

  2. Set the baud rate on the Kostal inverter to 19200 and note the configured Modbus slave address.

  3. Import the Kostal Inverter template in the ModbusCloud platform and assign the correct slave address to match the inverter configuration.

  4. Ensure the RS485 bus is properly terminated if the gateway is at the end of the bus, using a 120 ohm termination resistor.

  5. Power on the gateway and verify in the ModbusCloud dashboard that data is being received from the Kostal inverter.

Things to watch for

The gateway is not receiving any data from the Kostal inverter. What should I check?

Verify that the RS485 wiring polarity (A and B) is correct and that the baud rate on both the gateway and inverter is set to 19200. Also confirm the Modbus slave address in the template matches the address configured on the inverter.

Do I need to enable Modbus on the Kostal inverter first?

Some Kostal inverter models require Modbus communication to be explicitly enabled in the inverter settings menu or via the inverter's web interface. Consult your specific Kostal inverter manual for the exact steps.

Can I connect multiple Kostal inverters on the same RS485 bus?

Yes, as long as each inverter has a unique Modbus slave address. Add a separate device entry in ModbusCloud for each inverter, each referencing the Kostal Inverter template with the correct address.

Which Kostal inverter models are compatible with this template?

The template is designed for Kostal inverters that support Modbus RTU over RS485. Most Kostal Piko and Plenticore models support this protocol. Check the datasheet of your specific model to confirm Modbus RTU availability.