Metz Connect Metz Connect MR-AO4 Modbus RTU Modbus RTU template

Metz Connect MR-AO4 Modbus RTU

Controls 4 analog outputs for decentralized switching tasks via Modbus RTU

Modbus RTU template for the Metz Connect MR-AO4 analog output module. It provides control of 4 analog outputs typically used to drive vent valves, mixing valves, and similar actuators in HVAC and building automation systems.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
4, read and write
Available commands
Analog output 1 · Analog output 2 · Analog output 3 · Analog output 4
Compatible models
MR-AO4 · MR-F-AO4
Last updated

Registers (4)

0 read, 4 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Analog output 1Write
Analog output 2Write
Analog output 3Write
Analog output 4Write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Control mixing valve positions remotely from the ModbusCloud dashboard to adjust heating or cooling setpoints.
  • Write analog output values to vent valve actuators on a scheduled basis for seasonal HVAC adjustments.
  • Monitor and adjust control signals across multiple MR-AO4 modules installed at different customer sites from one platform.
  • Create automation rules that ramp analog outputs up or down based on external sensor data or time schedules.
  • Commission analog output levels remotely during initial system setup to verify actuator wiring and response.

Installation

  1. Mount the Metz Connect MR-AO4 on a DIN TH35 rail inside the distribution cabinet and wire the analog outputs to the target actuators.

  2. Connect the RS-485 A and B terminals of the MR-AO4 to the RS-485 port on your ModbusCloud Gateway.

  3. Set a unique Modbus address and the baud rate to 9600 using the two rotary switches on the front panel of the module.

  4. Use the Metz Connect MBus configuration tool to select the correct output type (voltage or current) for each channel.

  5. Import the Metz Connect MR-AO4 template in the ModbusCloud portal and assign it to the gateway with the matching Modbus address.

  6. Verify communication by writing a test value to one of the four analog outputs and confirming the actuator responds.

Things to watch for

The gateway cannot communicate with the MR-AO4. What should I check?

Verify that the RS-485 A and B wires are not swapped and that the baud rate on the module matches 9600 as expected by the template. Also confirm the Modbus address set on the rotary switches matches the address configured in ModbusCloud.

How do I change the output type from voltage to current?

Use the Metz Connect MBus configuration tool connected via RS-485 to set the output mode for each channel. This cannot be done through Modbus registers alone.

What value range should I write to the output registers?

Each output register is a uint16 at addresses 0 through 3. The exact scaling depends on the configured output type. Consult the MR-AO4 datasheet for the mapping between register value and physical output level.

Can I use multiple MR-AO4 modules on the same RS-485 bus?

Yes. Assign each module a unique Modbus address using the front panel rotary switches. Add a separate template instance in ModbusCloud for each module with the corresponding address.

Want to see how it works?

Electrician working in an open distribution board