KNV Nibe (KNV) Heating & Cooling (S-Series) Modbus TCP template

Nibe (KNV) Heating & Cooling (S-Series)

Controls Nibe (KNV) S-Series heat pumps directly via Modbus TCP without a gateway.

Template for Nibe (KNV) S-Series heat pumps via Modbus TCP. Reads temperatures, compressor data, thermal and electrical energy, and operating hours. Controls heating/cooling modes, supply flow setpoints, hot water demand, and curve offsets.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
41, read and write
Brand
KNV
Key readings
Outdoor temperature · Supply and return flow temperatures · Hot water top/bottom temperatures · Compressor state and operating hours · Total thermal power (heating/hot water) · Actual electrical power
Available commands
Heatpump operating mode · Target heating/cooling supply flow temperature · Hot water demand · Offset curve HC1
Compatible models
S1155 · S1155PC · S1156 · S1156PC · S1255 · S1255PC · S1256 · S1256PC · S2125 · SMO S40
Last updated

Registers (41)

39 read, 8 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Actual Outdoor temperature [BT1]°CRead
Actual Hot Water Bottom temperature [BT6]°CRead
Actual Supply Flowtemperature HC1 [BT2]°CRead
State Room temperature HC1 [BT50]°CRead
State Offset Curve HC1Read and write
State Heat Curve HC1Read and write
Total Thermal Power HeatingkWhRead
Total Operating time direct heaterhRead
Actual Return temperature HC1 [BT3]°CRead
Actual Brine Out Flowtemperature [BT11]°CRead
Actual Brine In Flowtemperature [BT10]°CRead
State CompressorRead
Actual Hot Water Top temperature [BT7]°CRead
Total Thermal Power Hot WaterkWhRead
Actual Heatpump Flowtemperature [BT12]°CRead
Actual Liquid Line temperature [BT15]°CRead
Average Outdoor temperature 24h [BT1]°CRead
Actual Heatpump Flow Sensor [BF1]l/mRead
State Brine Pump Speed [GP2]%Read
State Compressor StartscountRead
State Circulation pump HC1 [GP10]%Read
State Calculated Supply Flowtemperature°CRead
Actual Electrical Power CompressorWRead
State Compressor Operation hourshRead
State Hot Water DemandRead and write
State Hot Water operation modeRead
State Cooling operation modeRead
State Heatpump Operating prioritisationRead
Actual Flowtemperature Buffer to HC [BT25]°CRead
Actual Current BE3ARead
Actual Current BE2ARead
Actual Current BE1ARead
State Heatpump Operating modeRead and write
Actual Electrical PowerWRead
State Hot Water Circulation pump [GP11]Read
State Target Heating Supply Flowtemperature HC1°CRead and write
State Target Cooling Supply Flowtemperature HC1°CRead and write
State Alarm numberRead
State Active alarmRead
Release Heating at manual modeWrite
Release Cooling at manual modeWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Monitor outdoor, supply, and return flow temperatures on a live cloud dashboard to verify heat pump performance remotely.
  • Create an alert when the compressor exceeds a defined number of operating hours to schedule preventive maintenance.
  • Track total thermal power and actual electrical power over time to calculate and report seasonal coefficient of performance.
  • Switch heating and cooling modes remotely based on building occupancy or external scheduling logic.
  • Adjust the HC1 offset curve remotely to optimize comfort without an on-site visit.
  • Trigger hot water demand activation in coordination with PV surplus to maximize self-consumption.

Installation

  1. Enable Modbus TCP on the Nibe S-Series heat pump via the HMI under menu 7.5.9 Modbus TCP/IP and note the assigned IP address.

  2. Connect the ModbusCloud Gateway to the same local network as the heat pump using an Ethernet cable.

  3. In the ModbusCloud portal, import the Nibe (KNV) S-Series template and assign the heat pump IP address and default Modbus TCP port 502.

  4. Optionally export the full register list from the heat pump HMI to a USB stick to verify register availability for your specific model.

  5. Verify communication by checking that live temperature values and compressor status appear on the ModbusCloud dashboard.

  6. Configure any desired control setpoints such as operating mode or supply flow target temperature and confirm correct write access.

Things to watch for

Why do I see zero or incorrect values for total thermal power or compressor starts?

These registers (e.g. addresses 1575, 1577, 1083) are 32-bit values spanning two consecutive Modbus registers. Ensure the template is configured to read them as 32-bit integers rather than single 16-bit registers.

Can I use this template for Nibe F-Series or Greenline models?

No. The register maps differ significantly between the F-Series, S-Series, and Greenline product families. Use the dedicated F-Series or Greenline template for those models.

How do I find the correct Modbus TCP port and IP address on the heat pump?

Navigate to menu 7.5.9 Modbus TCP/IP on the heat pump HMI display. The IP address and port (typically 502) are shown there. Make sure the gateway and heat pump are on the same subnet.

Do I need an external Modbus gateway module to connect the S-Series?

No. The Nibe S-Series and SMO S40 controller have a built-in Modbus TCP interface. You connect the ModbusCloud gateway directly over Ethernet without any additional hardware.