WEG SSW07

Soft starter for three-phase motors with current, status and fault readout and remote start.

The WEG SSW07 is a compact soft starter with built-in bypass that starts and stops three-phase motors on pumps, fans and compressors. This Modbus RTU template reads motor and phase currents, power, thermal status, heatsink temperature and faults, and lets you start, stop, reset and adjust ramps and protections from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
120, read and write
Brand
WEG
Key readings
Motor current · Phase currents · Apparent output power · Motor thermal status · Heatsink temperature · Soft starter status · Active fault
Available commands
Start and stop · Fault reset · Ramp times · Current limit · Protection settings
Compatible models
SSW-07 (software V1.5x) · SSW-08
Last updated

Registers (120)

120 read, 78 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Status WordRead5001FC03uint16
Motor CurrentARead3FC03uint16
Phase R CurrentARead30FC03uint16
Phase S CurrentARead31FC03uint16
Phase T CurrentARead32FC03uint16
Motor Current Pct of Starter%Read
Motor Current Pct of Motor%Read
Apparent Output PowerkVARead
Output Voltage%Read
Supply FrequencyHzRead
Motor Thermal Status%Read
Heatsink Temperature°CRead
Soft Starter StatusRead
Active FaultRead
Digital InputsRead
Relay OutputsRead
Last FaultRead
Second FaultRead
Third FaultRead
Fourth FaultRead
Software VersionRead
Command WordRead and write
Relay Output CommandRead and write
Status Bit RunningRead
Status Bit General EnabledRead
Status Bit Jog ActiveRead
Status Bit AcceleratingRead
Status Bit In Current LimitRead
Status Bit Full VoltageRead
Status Bit DeceleratingRead
Status Bit Remote ModeRead
Status Bit DC BrakingRead
Status Bit ReversingRead
Status Bit Direction CCWRead
Status Bit Bypass ClosedRead
Status Bit Supply PresentRead
Status Bit Fault ActiveRead
Command Bit RunRead and write
Command Bit General EnableRead and write
Command Bit JogRead and write
Command Bit Direction CCWRead and write
Command Bit RemoteRead and write
Command Bit Fault ResetRead and write
Initial Voltage%Read and write
Acceleration Ramp TimesRead and write
Deceleration Voltage Step%Read and write
Deceleration Ramp TimesRead and write
End Deceleration Voltage%Read and write
Current Limit%Read and write
Current Ramp Initial Current%Read and write
Current Ramp Time%Read and write
Parameter AccessRead and write
Type of ControlRead and write
Fan ControlRead and write
Load Factory DefaultsRead and write
Display Parameter at Power UpRead and write
Auto Reset TimesRead and write
Auto ResetRead and write
Parameter SourceRead and write
Local Remote SourceRead and write
Local Command SourceRead and write
Remote Command SourceRead and write
DI1 FunctionRead and write
DI2 FunctionRead and write
DI3 FunctionRead and write
RL1 FunctionRead and write
RL2 FunctionRead and write
Nominal Current SettingRead and write
Modbus AddressRead and write
Serial Protocol and Baud RateRead and write
Serial Error ActionRead and write
Serial Watchdog TimesRead and write
CAN AddressRead and write
CAN Baud RateRead and write
Bus Off ResetRead and write
DeviceNet IO InstancesRead and write
DeviceNet Read Word 2Read and write
DeviceNet Read Word 3Read and write
DeviceNet Read Word 4Read and write
DeviceNet Read Word 5Read and write
DeviceNet Read Word 6Read and write
DeviceNet Read Word 7Read and write
DeviceNet Write Word 2Read and write
DeviceNet Write Word 3Read and write
DeviceNet Write Word 4Read and write
DeviceNet Write Word 5Read and write
DeviceNet Write Word 6Read and write
DeviceNet Write Word 7Read and write
Fieldbus Error ActionRead and write
CAN Controller StatusRead
DeviceNet Network StatusRead
DeviceNet Master StatusRead
CAN Telegrams ReceivedRead
CAN Telegrams TransmittedRead
CAN Bus Off CounterRead
CAN Lost MessagesRead
Motor Nominal VoltageVRead and write
Motor Current Setting%Read and write
Service FactorRead and write
DC Braking TimesRead and write
DC Braking Voltage%Read and write
JogRead and write
Jog Level%Read and write
Kick StartRead and write
Kick Start TimesRead and write
Kick Start Level%Read and write
Undercurrent Level%Read and write
Undercurrent TimesRead and write
Overcurrent Level%Read and write
Overcurrent TimesRead and write
Current Imbalance Level%Read and write
Current Imbalance TimesRead and write
Undercurrent Before BypassRead and write
Blocked Rotor ProtectionRead and write
Phase Sequence CheckRead and write
E77 EnableRead and write
SSW Short Circuit DetectionRead and write
Interval Between StartssRead and write
Motor Thermal ClassRead and write
Thermal Memory Auto ResetsRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show motor current, thermal status and heatsink temperature of pump and fan starters on one ModbusCloud dashboard.
  • Get an email alert when Active Fault is not 0, with the fault name from the fault list.
  • Compare the three phase currents over time to spot imbalance before the starter trips.
  • Start, stop or reset a pump starter from the portal when the commands are set to Serial.
  • Adjust ramp times or the current limit on site from ModbusCloud without opening the panel.

Installation

  1. Fit the Modbus RTU RS485 kit in the SSW07 and connect A and B to the RS485 port of the ModbusCloud Gateway. Set the termination switches on at both ends of the bus.

  2. Set the address in P308 and the baud rate and parity in P312. The default is address 1, 9600 baud, no parity with 2 stop bits.

  3. In ModbusCloud, add a Modbus RTU device with the same settings and import the WEG SSW07 template.

  4. Check that Motor Current and Soft Starter Status match the keypad. For control over Modbus, set P220, P229 or P230 to Serial.

Things to watch for

The soft starter does not answer. What should I check?

Check that the RS485 kit is fitted; without it there is no Modbus. Compare P308 and P312 with the device in ModbusCloud; with no parity the starter uses 2 stop bits. Swap A and B, and switch on the termination only at the two bus ends. Changes to P308 and P312 need the motor stopped.

I write a start command but the motor does not start.

The starter only follows Command Word or the command bits when P220, P229 or P230 select Serial for the active local or remote mode. A start during the P630 wait time after a stop is ignored without an error. Read Status Word to see whether the starter is in remote mode and enabled.

Why can I not change the ramp time or current limit?

With P219 = 0 the ramp, current limit, control type and several protections come from the trimpots and DIP switches and are read only. Set P219 to 1 (keypad) with the motor stopped to set them over Modbus. P200 and P215 cannot be reached over serial at all.

What should I watch out for when writing to the starter?

Commands act on a running motor, so make sure nobody is working on the driven machine. Read a parameter before you change it, and change one at a time. Writing 5 to Load Factory Defaults resets almost every setting. Values with decimals are sent as integers, so 9.5 is written as 95.