WEG SSW07
Soft starter for three-phase motors with current, status and fault readout and remote start.
The WEG SSW07 is a compact soft starter with built-in bypass that starts and stops three-phase motors on pumps, fans and compressors. This Modbus RTU template reads motor and phase currents, power, thermal status, heatsink temperature and faults, and lets you start, stop, reset and adjust ramps and protections from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 120, read and write
- Brand
- WEG
- Key readings
- Motor current · Phase currents · Apparent output power · Motor thermal status · Heatsink temperature · Soft starter status · Active fault
- Available commands
- Start and stop · Fault reset · Ramp times · Current limit · Protection settings
- Compatible models
- SSW-07 (software V1.5x) · SSW-08
- Last updated
Registers (120)
120 read, 78 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Status Word | Read | 5001 | FC03 | uint16 | |
| Motor Current | A | Read | 3 | FC03 | uint16 |
| Phase R Current | A | Read | 30 | FC03 | uint16 |
| Phase S Current | A | Read | 31 | FC03 | uint16 |
| Phase T Current | A | Read | 32 | FC03 | uint16 |
| Motor Current Pct of Starter | % | Read | |||
| Motor Current Pct of Motor | % | Read | |||
| Apparent Output Power | kVA | Read | |||
| Output Voltage | % | Read | |||
| Supply Frequency | Hz | Read | |||
| Motor Thermal Status | % | Read | |||
| Heatsink Temperature | °C | Read | |||
| Soft Starter Status | Read | ||||
| Active Fault | Read | ||||
| Digital Inputs | Read | ||||
| Relay Outputs | Read | ||||
| Last Fault | Read | ||||
| Second Fault | Read | ||||
| Third Fault | Read | ||||
| Fourth Fault | Read | ||||
| Software Version | Read | ||||
| Command Word | Read and write | ||||
| Relay Output Command | Read and write | ||||
| Status Bit Running | Read | ||||
| Status Bit General Enabled | Read | ||||
| Status Bit Jog Active | Read | ||||
| Status Bit Accelerating | Read | ||||
| Status Bit In Current Limit | Read | ||||
| Status Bit Full Voltage | Read | ||||
| Status Bit Decelerating | Read | ||||
| Status Bit Remote Mode | Read | ||||
| Status Bit DC Braking | Read | ||||
| Status Bit Reversing | Read | ||||
| Status Bit Direction CCW | Read | ||||
| Status Bit Bypass Closed | Read | ||||
| Status Bit Supply Present | Read | ||||
| Status Bit Fault Active | Read | ||||
| Command Bit Run | Read and write | ||||
| Command Bit General Enable | Read and write | ||||
| Command Bit Jog | Read and write | ||||
| Command Bit Direction CCW | Read and write | ||||
| Command Bit Remote | Read and write | ||||
| Command Bit Fault Reset | Read and write | ||||
| Initial Voltage | % | Read and write | |||
| Acceleration Ramp Time | s | Read and write | |||
| Deceleration Voltage Step | % | Read and write | |||
| Deceleration Ramp Time | s | Read and write | |||
| End Deceleration Voltage | % | Read and write | |||
| Current Limit | % | Read and write | |||
| Current Ramp Initial Current | % | Read and write | |||
| Current Ramp Time | % | Read and write | |||
| Parameter Access | Read and write | ||||
| Type of Control | Read and write | ||||
| Fan Control | Read and write | ||||
| Load Factory Defaults | Read and write | ||||
| Display Parameter at Power Up | Read and write | ||||
| Auto Reset Time | s | Read and write | |||
| Auto Reset | Read and write | ||||
| Parameter Source | Read and write | ||||
| Local Remote Source | Read and write | ||||
| Local Command Source | Read and write | ||||
| Remote Command Source | Read and write | ||||
| DI1 Function | Read and write | ||||
| DI2 Function | Read and write | ||||
| DI3 Function | Read and write | ||||
| RL1 Function | Read and write | ||||
| RL2 Function | Read and write | ||||
| Nominal Current Setting | Read and write | ||||
| Modbus Address | Read and write | ||||
| Serial Protocol and Baud Rate | Read and write | ||||
| Serial Error Action | Read and write | ||||
| Serial Watchdog Time | s | Read and write | |||
| CAN Address | Read and write | ||||
| CAN Baud Rate | Read and write | ||||
| Bus Off Reset | Read and write | ||||
| DeviceNet IO Instances | Read and write | ||||
| DeviceNet Read Word 2 | Read and write | ||||
| DeviceNet Read Word 3 | Read and write | ||||
| DeviceNet Read Word 4 | Read and write | ||||
| DeviceNet Read Word 5 | Read and write | ||||
| DeviceNet Read Word 6 | Read and write | ||||
| DeviceNet Read Word 7 | Read and write | ||||
| DeviceNet Write Word 2 | Read and write | ||||
| DeviceNet Write Word 3 | Read and write | ||||
| DeviceNet Write Word 4 | Read and write | ||||
| DeviceNet Write Word 5 | Read and write | ||||
| DeviceNet Write Word 6 | Read and write | ||||
| DeviceNet Write Word 7 | Read and write | ||||
| Fieldbus Error Action | Read and write | ||||
| CAN Controller Status | Read | ||||
| DeviceNet Network Status | Read | ||||
| DeviceNet Master Status | Read | ||||
| CAN Telegrams Received | Read | ||||
| CAN Telegrams Transmitted | Read | ||||
| CAN Bus Off Counter | Read | ||||
| CAN Lost Messages | Read | ||||
| Motor Nominal Voltage | V | Read and write | |||
| Motor Current Setting | % | Read and write | |||
| Service Factor | Read and write | ||||
| DC Braking Time | s | Read and write | |||
| DC Braking Voltage | % | Read and write | |||
| Jog | Read and write | ||||
| Jog Level | % | Read and write | |||
| Kick Start | Read and write | ||||
| Kick Start Time | s | Read and write | |||
| Kick Start Level | % | Read and write | |||
| Undercurrent Level | % | Read and write | |||
| Undercurrent Time | s | Read and write | |||
| Overcurrent Level | % | Read and write | |||
| Overcurrent Time | s | Read and write | |||
| Current Imbalance Level | % | Read and write | |||
| Current Imbalance Time | s | Read and write | |||
| Undercurrent Before Bypass | Read and write | ||||
| Blocked Rotor Protection | Read and write | ||||
| Phase Sequence Check | Read and write | ||||
| E77 Enable | Read and write | ||||
| SSW Short Circuit Detection | Read and write | ||||
| Interval Between Starts | s | Read and write | |||
| Motor Thermal Class | Read and write | ||||
| Thermal Memory Auto Reset | s | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show motor current, thermal status and heatsink temperature of pump and fan starters on one ModbusCloud dashboard.
- Get an email alert when Active Fault is not 0, with the fault name from the fault list.
- Compare the three phase currents over time to spot imbalance before the starter trips.
- Start, stop or reset a pump starter from the portal when the commands are set to Serial.
- Adjust ramp times or the current limit on site from ModbusCloud without opening the panel.
Installation
Fit the Modbus RTU RS485 kit in the SSW07 and connect A and B to the RS485 port of the ModbusCloud Gateway. Set the termination switches on at both ends of the bus.
Set the address in P308 and the baud rate and parity in P312. The default is address 1, 9600 baud, no parity with 2 stop bits.
In ModbusCloud, add a Modbus RTU device with the same settings and import the WEG SSW07 template.
Check that Motor Current and Soft Starter Status match the keypad. For control over Modbus, set P220, P229 or P230 to Serial.
Things to watch for
The soft starter does not answer. What should I check?
Check that the RS485 kit is fitted; without it there is no Modbus. Compare P308 and P312 with the device in ModbusCloud; with no parity the starter uses 2 stop bits. Swap A and B, and switch on the termination only at the two bus ends. Changes to P308 and P312 need the motor stopped.
I write a start command but the motor does not start.
The starter only follows Command Word or the command bits when P220, P229 or P230 select Serial for the active local or remote mode. A start during the P630 wait time after a stop is ignored without an error. Read Status Word to see whether the starter is in remote mode and enabled.
Why can I not change the ramp time or current limit?
With P219 = 0 the ramp, current limit, control type and several protections come from the trimpots and DIP switches and are read only. Set P219 to 1 (keypad) with the motor stopped to set them over Modbus. P200 and P215 cannot be reached over serial at all.
What should I watch out for when writing to the starter?
Commands act on a running motor, so make sure nobody is working on the driven machine. Read a parameter before you change it, and change one at a time. Writing 5 to Load Factory Defaults resets almost every setting. Values with decimals are sent as integers, so 9.5 is written as 95.
More WEG templates
Want to see how it works?