Wolf Airflow Wolf CWL-2-325 Modbus RTU template

Airflow Wolf CWL-2-325

Controls and monitors a Wolf CWL-2-325 ventilation unit via Modbus RTU

This template provides full monitoring and control of the Wolf CWL-2-325 ventilation unit via Modbus RTU. It reads supply and exhaust air temperatures, pressures, flow rates, bypass status, and filter status. It also allows control of throughput settings, bypass mode, imbalance offsets, and device resets.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
19, read and write
Brand
Wolf
Key readings
Supply & exhaust air temperature · Supply & exhaust air pressure · Supply & exhaust air flow rate · Bypass status · Filter status
Available commands
Desired throughput setting · Bypass mode · Imbalance offset supply/exhaust · Reset filter warning / device
Compatible models
Wolf CWL-2-325
Last updated

Registers (19)

10 read, 9 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
exhaust air temperature°CRead
actual pressure supply airPaRead
actual pressure exhaust airPaRead
setpoint supply airm³/hRead
actual value in airm³/hRead
exhaust air flow rate setpointm³/hRead
actual value throughput exhaust airm³/hRead
temperature supply air°CRead
Bypass-StatusRead
filter statusRead
Imbalance allowedWrite
Offset imbalance supply airWrite
Offset imbalance exaust airWrite
Bypass modeWrite
Desired throughput settingWrite
change of switch positionWrite
Desired throughput settingWrite
Reset filter warningWrite
Reset the deviceWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor supply and exhaust air temperatures on a live dashboard to verify heat recovery performance.
  • Create an alert when the filter status indicates a clogged filter so maintenance can be scheduled proactively.
  • Adjust the desired throughput setting remotely to match seasonal ventilation requirements.
  • Track supply and exhaust air pressure trends to detect ductwork issues or fan degradation over time.
  • Reset a filter warning remotely after a maintenance visit without accessing the unit directly.
  • Verify bypass status during summer operation to confirm free cooling is active.

Installation

  1. Connect the ModbusCloud Gateway to the RS-485 terminal of the Wolf CWL-2-325 using a twisted-pair cable with correct A/B polarity.

  2. Set the Modbus RTU baud rate on the Wolf CWL-2-325 to 9600, matching the gateway configuration.

  3. Assign a unique Modbus slave address on the Wolf unit and configure the same address in the ModbusCloud gateway.

  4. Import the Wolf CWL-2-325 template from the ModbusCloud template library into your project.

  5. Verify communication by checking that supply and exhaust air temperature values appear on the dashboard.

  6. Confirm which write register (address 8000 or 8002) controls supply air throughput and which controls exhaust air throughput during commissioning.

Things to watch for

Why do I see two registers both labeled 'Desired throughput setting'?

The Wolf CWL-2-325 uses register address 8000 and 8002 for throughput control. One applies to supply air and the other to exhaust air. Write a test value to each register individually and observe which airflow changes on the unit to determine the correct mapping.

What baud rate should I use for the Modbus RTU connection?

The default baud rate is 9600. Make sure both the Wolf unit and the ModbusCloud gateway are set to the same baud rate, parity, and stop bit configuration.

The filter status register does not update after I replaced the filter. What should I do?

After physically replacing the filter, use the reset filter warning register in the template to clear the warning. The Wolf unit will not automatically reset this status upon filter replacement.

I am not getting any response from the Wolf unit over Modbus RTU. What should I check?

Verify the RS-485 wiring polarity (A and B terminals), confirm the correct slave address is set on both the unit and the gateway, and ensure the baud rate matches. Also check that the RS-485 bus is properly terminated if the cable run is long.