ABB D13 15
DIN rail energy meter for energy per phase and tariff, voltage, current, power and power factor.
The ABB D13 15 is a three phase DIN rail energy meter that counts active, reactive and apparent energy per phase and tariff in distribution boards. This Modbus RTU template reads all energy and instantaneous values and lets you switch the output, select the tariff and reset counters from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 253, read and write
- Brand
- ABB
- Key readings
- Active energy import and export · Reactive energy · Energy per tariff · Voltage L-N and L-L · Current per phase · Active power · Power factor · Frequency
- Available commands
- Output 1 · Active tariff · Energy counter resets · Alarm thresholds
- Compatible models
- D13 15 · D11 15
- Last updated
Registers (253)
244 read, 45 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Active Energy Import Total | kWh | Read | |||
| Active Energy Export Total | kWh | Read | |||
| Active Energy Net Total | kWh | Read | |||
| Reactive Energy Import Total | kvarh | Read | |||
| Reactive Energy Export Total | kvarh | Read | |||
| Reactive Energy Net Total | kvarh | Read | |||
| Apparent Energy Total | kVAh | Read | |||
| Active Energy Import CO2 | kg | Read | |||
| Active Energy Import Currency | Read | ||||
| Active Energy Export Currency | Read | ||||
| Active Energy Import Tariff 1 | kWh | Read | |||
| Active Energy Import Tariff 2 | kWh | Read | |||
| Active Energy Import Tariff 3 | kWh | Read | |||
| Active Energy Import Tariff 4 | kWh | Read | |||
| Active Energy Export Tariff 1 | kWh | Read | |||
| Active Energy Export Tariff 2 | kWh | Read | |||
| Active Energy Export Tariff 3 | kWh | Read | |||
| Active Energy Export Tariff 4 | kWh | Read | |||
| Reactive Energy Import Tariff 1 | kvarh | Read | |||
| Reactive Energy Import Tariff 2 | kvarh | Read | |||
| Reactive Energy Import Tariff 3 | kvarh | Read | |||
| Reactive Energy Import Tariff 4 | kvarh | Read | |||
| Reactive Energy Export Tariff 1 | kvarh | Read | |||
| Reactive Energy Export Tariff 2 | kvarh | Read | |||
| Reactive Energy Export Tariff 3 | kvarh | Read | |||
| Reactive Energy Export Tariff 4 | kvarh | Read | |||
| Active Energy Import L1 | kWh | Read | |||
| Active Energy Import L2 | kWh | Read | |||
| Active Energy Import L3 | kWh | Read | |||
| Active Energy Export L1 | kWh | Read | |||
| Active Energy Export L2 | kWh | Read | |||
| Active Energy Export L3 | kWh | Read | |||
| Active Energy Net L1 | kWh | Read | |||
| Active Energy Net L2 | kWh | Read | |||
| Active Energy Net L3 | kWh | Read | |||
| Reactive Energy Import L1 | kvarh | Read | |||
| Reactive Energy Import L2 | kvarh | Read | |||
| Reactive Energy Import L3 | kvarh | Read | |||
| Reactive Energy Export L1 | kvarh | Read | |||
| Reactive Energy Export L2 | kvarh | Read | |||
| Reactive Energy Export L3 | kvarh | Read | |||
| Reactive Energy Net L1 | kvarh | Read | |||
| Reactive Energy Net L2 | kvarh | Read | |||
| Reactive Energy Net L3 | kvarh | Read | |||
| Apparent Energy L1 | kVAh | Read | |||
| Apparent Energy L2 | kVAh | Read | |||
| Apparent Energy L3 | kVAh | Read | |||
| Resettable Active Energy Import | kWh | Read | |||
| Resettable Active Energy Export | kWh | Read | |||
| Resettable Reactive Energy Import | kvarh | Read | |||
| Resettable Reactive Energy Export | kvarh | Read | |||
| Voltage L1-N | V | Read | |||
| Voltage L2-N | V | Read | |||
| Voltage L3-N | V | Read | |||
| Voltage L1-L2 | V | Read | |||
| Voltage L3-L2 | V | Read | |||
| Voltage L1-L3 | V | Read | |||
| Current L1 | A | Read | |||
| Current L2 | A | Read | |||
| Current L3 | A | Read | |||
| Current N | A | Read | |||
| Active Power Total | W | Read | |||
| Active Power L1 | W | Read | |||
| Active Power L2 | W | Read | |||
| Active Power L3 | W | Read | |||
| Reactive Power Total | var | Read | |||
| Reactive Power L1 | var | Read | |||
| Reactive Power L2 | var | Read | |||
| Reactive Power L3 | var | Read | |||
| Apparent Power Total | VA | Read | |||
| Apparent Power L1 | VA | Read | |||
| Apparent Power L2 | VA | Read | |||
| Apparent Power L3 | VA | Read | |||
| Frequency | Hz | Read | |||
| Power Phase Angle Total | ° | Read | |||
| Power Phase Angle L1 | ° | Read | |||
| Power Phase Angle L2 | ° | Read | |||
| Power Phase Angle L3 | ° | Read | |||
| Voltage Phase Angle U1 | ° | Read | |||
| Voltage Phase Angle U2 | ° | Read | |||
| Voltage Phase Angle U3 | ° | Read | |||
| Current Phase Angle I1 | ° | Read | |||
| Current Phase Angle I2 | ° | Read | |||
| Current Phase Angle I3 | ° | Read | |||
| Power Factor Total | Read | ||||
| Power Factor L1 | Read | ||||
| Power Factor L2 | Read | ||||
| Power Factor L3 | Read | ||||
| Current Quadrant Total | Read | ||||
| Current Quadrant L1 | Read | ||||
| Current Quadrant L2 | Read | ||||
| Current Quadrant L3 | Read | ||||
| Output 1 | Read and write | ||||
| Input 1 State | Read | ||||
| Input 1 Counter | Read | ||||
| Serial Number | Read | ||||
| Meter Firmware Version | Read | ||||
| Type Designation | Read | ||||
| CO2 Conversion Factor | Read and write | ||||
| Currency Import Factor | Read and write | ||||
| LED Type | Read and write | ||||
| Wire Type | Read and write | ||||
| Currency Export Factor | Read and write | ||||
| Reset Input 1 Counter | Write | ||||
| Reset Resettable Active Energy Import | Write | ||||
| Reset Resettable Active Energy Export | Write | ||||
| Reset Resettable Reactive Energy Import | Write | ||||
| Reset Resettable Reactive Energy Export | Write | ||||
| Reset System Logs | Write | ||||
| Reset Net Quality Logs | Write | ||||
| Reset All Logs | Write | ||||
| Reset All Resettable Registers | Write | ||||
| Error Log Get Next Block | Read and write | ||||
| Error Log Entry Number | Read and write | ||||
| Error Log Direction | Read and write | ||||
| Error Log Entry 1 Category | Read | ||||
| Error Log Entry 1 Event Id | Read | ||||
| Error Log Entry 1 Duration | s | Read | |||
| Error Log Entry 2 Category | Read | ||||
| Error Log Entry 2 Event Id | Read | ||||
| Error Log Entry 2 Duration | s | Read | |||
| Error Log Entry 3 Category | Read | ||||
| Error Log Entry 3 Event Id | Read | ||||
| Error Log Entry 3 Duration | s | Read | |||
| Error Log Entry 4 Category | Read | ||||
| Error Log Entry 4 Event Id | Read | ||||
| Error Log Entry 4 Duration | s | Read | |||
| Error Log Entry 5 Category | Read | ||||
| Error Log Entry 5 Event Id | Read | ||||
| Error Log Entry 5 Duration | s | Read | |||
| Error Log Entry 6 Category | Read | ||||
| Error Log Entry 6 Event Id | Read | ||||
| Error Log Entry 6 Duration | s | Read | |||
| Error Log Entry 7 Category | Read | ||||
| Error Log Entry 7 Event Id | Read | ||||
| Error Log Entry 7 Duration | s | Read | |||
| Error Log Entry 8 Category | Read | ||||
| Error Log Entry 8 Event Id | Read | ||||
| Error Log Entry 8 Duration | s | Read | |||
| Error Log Entry 9 Category | Read | ||||
| Error Log Entry 9 Event Id | Read | ||||
| Error Log Entry 9 Duration | s | Read | |||
| Error Log Entry 10 Category | Read | ||||
| Error Log Entry 10 Event Id | Read | ||||
| Error Log Entry 10 Duration | s | Read | |||
| Error Log Entry 11 Category | Read | ||||
| Error Log Entry 11 Event Id | Read | ||||
| Error Log Entry 11 Duration | s | Read | |||
| Error Log Entry 12 Category | Read | ||||
| Error Log Entry 12 Event Id | Read | ||||
| Error Log Entry 12 Duration | s | Read | |||
| Error Log Entry 13 Category | Read | ||||
| Error Log Entry 13 Event Id | Read | ||||
| Error Log Entry 13 Duration | s | Read | |||
| Error Log Entry 14 Category | Read | ||||
| Error Log Entry 14 Event Id | Read | ||||
| Error Log Entry 14 Duration | s | Read | |||
| Error Log Entry 15 Category | Read | ||||
| Error Log Entry 15 Event Id | Read | ||||
| Error Log Entry 15 Duration | s | Read | |||
| Alarm Log Get Next Block | Read and write | ||||
| Alarm Log Entry Number | Read and write | ||||
| Alarm Log Direction | Read and write | ||||
| Alarm Log Entry 1 Category | Read | ||||
| Alarm Log Entry 1 Event Id | Read | ||||
| Alarm Log Entry 1 Duration | s | Read | |||
| Alarm Log Entry 2 Category | Read | ||||
| Alarm Log Entry 2 Event Id | Read | ||||
| Alarm Log Entry 2 Duration | s | Read | |||
| Alarm Log Entry 3 Category | Read | ||||
| Alarm Log Entry 3 Event Id | Read | ||||
| Alarm Log Entry 3 Duration | s | Read | |||
| Alarm Log Entry 4 Category | Read | ||||
| Alarm Log Entry 4 Event Id | Read | ||||
| Alarm Log Entry 4 Duration | s | Read | |||
| Alarm Log Entry 5 Category | Read | ||||
| Alarm Log Entry 5 Event Id | Read | ||||
| Alarm Log Entry 5 Duration | s | Read | |||
| Alarm Log Entry 6 Category | Read | ||||
| Alarm Log Entry 6 Event Id | Read | ||||
| Alarm Log Entry 6 Duration | s | Read | |||
| Alarm Log Entry 7 Category | Read | ||||
| Alarm Log Entry 7 Event Id | Read | ||||
| Alarm Log Entry 7 Duration | s | Read | |||
| Alarm Log Entry 8 Category | Read | ||||
| Alarm Log Entry 8 Event Id | Read | ||||
| Alarm Log Entry 8 Duration | s | Read | |||
| Alarm Log Entry 9 Category | Read | ||||
| Alarm Log Entry 9 Event Id | Read | ||||
| Alarm Log Entry 9 Duration | s | Read | |||
| Alarm Log Entry 10 Category | Read | ||||
| Alarm Log Entry 10 Event Id | Read | ||||
| Alarm Log Entry 10 Duration | s | Read | |||
| Alarm Log Entry 11 Category | Read | ||||
| Alarm Log Entry 11 Event Id | Read | ||||
| Alarm Log Entry 11 Duration | s | Read | |||
| Alarm Log Entry 12 Category | Read | ||||
| Alarm Log Entry 12 Event Id | Read | ||||
| Alarm Log Entry 12 Duration | s | Read | |||
| Alarm Log Entry 13 Category | Read | ||||
| Alarm Log Entry 13 Event Id | Read | ||||
| Alarm Log Entry 13 Duration | s | Read | |||
| Alarm Log Entry 14 Category | Read | ||||
| Alarm Log Entry 14 Event Id | Read | ||||
| Alarm Log Entry 14 Duration | s | Read | |||
| Alarm Log Entry 15 Category | Read | ||||
| Alarm Log Entry 15 Event Id | Read | ||||
| Alarm Log Entry 15 Duration | s | Read | |||
| Audit Log Get Next Block | Read and write | ||||
| Audit Log Entry Number | Read and write | ||||
| Audit Log Direction | Read and write | ||||
| Audit Log Entry Nr | Read | ||||
| Audit Log Upgrade Counter | Read | ||||
| Audit Log FW Version Major | Read | ||||
| Audit Log FW Version Minor | Read | ||||
| Audit Log FW Version Patch | Read | ||||
| Audit Log Wires | Read | ||||
| Audit Log Trafo V Primary | Read | ||||
| Audit Log Trafo V Secondary | Read | ||||
| Audit Log Trafo I Primary | Read | ||||
| Audit Log Trafo I Secondary | Read | ||||
| Audit Log Active Energy Import Total | kWh | Read | |||
| Audit Log Active Energy Import L1 | kWh | Read | |||
| Audit Log Active Energy Import L2 | kWh | Read | |||
| Audit Log Active Energy Import L3 | kWh | Read | |||
| Audit Log Active Energy Import Tariff 1 | kWh | Read | |||
| Audit Log Active Energy Import Tariff 2 | kWh | Read | |||
| Audit Log Active Energy Import Tariff 3 | kWh | Read | |||
| Audit Log Active Energy Import Tariff 4 | kWh | Read | |||
| Audit Log Active Energy Export Total | kWh | Read | |||
| Alarm Number | Read and write | ||||
| Alarm Parameter | Read and write | ||||
| Alarm Threshold | Read and write | ||||
| Alarm Hysteresis | Read and write | ||||
| Alarm Delay | Read and write | ||||
| Alarm Type | Read and write | ||||
| Alarm Action | Read and write | ||||
| Alarm Action Output Number | Read and write | ||||
| I/O Port 1 Function | Read | ||||
| I/O Port 2 Function | Read | ||||
| I/O Ports Set To Pulse Input | Read and write | ||||
| I/O Ports Set To Always On | Read and write | ||||
| I/O Ports Set To Always Off | Read and write | ||||
| I/O Ports Set To Communication | Read and write | ||||
| Pulse Output Port | Read and write | ||||
| Pulse Output Energy Type | Read and write | ||||
| Pulse Output Frequency | Read and write | ||||
| Pulse Output Length | ms | Read and write | |||
| Tariff Source | Read and write | ||||
| Active Tariff | Read and write | ||||
| Modbus Address | Read and write | ||||
| Modbus Baudrate | Read and write | ||||
| Modbus Parity | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show energy import, export and power per phase of every tenant meter on one dashboard.
- Send an email alert when the current of a phase rises above the limit of the circuit breaker.
- Keep 365 days of history of energy per tariff to bill tenants or compare day and night use.
- Switch the active tariff from ModbusCloud when your contract has fixed peak hours.
- Reset the resettable energy counters at the start of a measurement period without touching the totals.
Installation
Connect RS485 A, B and common of the D13 15 to the RS485 port of the ModbusCloud Gateway and terminate both ends of the bus with 120 ohm.
Set or read the Modbus address, baud rate and parity in the meter menu.
In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings, then import this template.
Check that the voltages L1-N to L3-N, the frequency and the total active energy arrive with plausible values.
Things to watch for
The meter does not answer on the RS485 bus. What should I check?
The bus is polarity dependent, so swap A and B if nothing comes back and connect the common wire as well. Match the address, baud rate and parity shown in the meter menu, terminate only the two ends of the bus and keep stubs shorter than 1 m.
Why do some registers show FFFF or a very large value?
The meter fills registers for quantities it does not have with an invalid value: FFFF for unsigned and 7FFF for signed values. On a single phase D11 15 this happens for phases L2 and L3 and the line voltages; ignore those registers or remove them from the device.
Which registers can I write from ModbusCloud?
Output 1, the active tariff, tariff source, alarm, pulse output and I/O settings, the CO2 and currency factors, the reset commands and the Modbus settings. The meter does not confirm a write, so read the value back afterwards. A reset sets counters to zero for good.
Why does output 1 not switch when I write to it?
The output must first be linked to the communication function. Write the port number to the register for I/O ports set to communication, then switch output 1. If the port is used for pulses, tariffs or alarms, Modbus cannot switch it.
Can several meters share one RS485 line?
Yes, up to 247 meters. Give every meter its own address and use the same baud rate and parity on all of them. Run the bus as one line of at most 700 m and terminate both ends.