ABB ABB D13 15 Modbus RTU template

ABB D13 15

DIN rail energy meter for energy per phase and tariff, voltage, current, power and power factor.

The ABB D13 15 is a three phase DIN rail energy meter that counts active, reactive and apparent energy per phase and tariff in distribution boards. This Modbus RTU template reads all energy and instantaneous values and lets you switch the output, select the tariff and reset counters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
253, read and write
Brand
ABB
Key readings
Active energy import and export · Reactive energy · Energy per tariff · Voltage L-N and L-L · Current per phase · Active power · Power factor · Frequency
Available commands
Output 1 · Active tariff · Energy counter resets · Alarm thresholds
Compatible models
D13 15 · D11 15
Last updated

Registers (253)

244 read, 45 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Active Energy Import TotalkWhRead
Active Energy Export TotalkWhRead
Active Energy Net TotalkWhRead
Reactive Energy Import TotalkvarhRead
Reactive Energy Export TotalkvarhRead
Reactive Energy Net TotalkvarhRead
Apparent Energy TotalkVAhRead
Active Energy Import CO2kgRead
Active Energy Import CurrencyRead
Active Energy Export CurrencyRead
Active Energy Import Tariff 1kWhRead
Active Energy Import Tariff 2kWhRead
Active Energy Import Tariff 3kWhRead
Active Energy Import Tariff 4kWhRead
Active Energy Export Tariff 1kWhRead
Active Energy Export Tariff 2kWhRead
Active Energy Export Tariff 3kWhRead
Active Energy Export Tariff 4kWhRead
Reactive Energy Import Tariff 1kvarhRead
Reactive Energy Import Tariff 2kvarhRead
Reactive Energy Import Tariff 3kvarhRead
Reactive Energy Import Tariff 4kvarhRead
Reactive Energy Export Tariff 1kvarhRead
Reactive Energy Export Tariff 2kvarhRead
Reactive Energy Export Tariff 3kvarhRead
Reactive Energy Export Tariff 4kvarhRead
Active Energy Import L1kWhRead
Active Energy Import L2kWhRead
Active Energy Import L3kWhRead
Active Energy Export L1kWhRead
Active Energy Export L2kWhRead
Active Energy Export L3kWhRead
Active Energy Net L1kWhRead
Active Energy Net L2kWhRead
Active Energy Net L3kWhRead
Reactive Energy Import L1kvarhRead
Reactive Energy Import L2kvarhRead
Reactive Energy Import L3kvarhRead
Reactive Energy Export L1kvarhRead
Reactive Energy Export L2kvarhRead
Reactive Energy Export L3kvarhRead
Reactive Energy Net L1kvarhRead
Reactive Energy Net L2kvarhRead
Reactive Energy Net L3kvarhRead
Apparent Energy L1kVAhRead
Apparent Energy L2kVAhRead
Apparent Energy L3kVAhRead
Resettable Active Energy ImportkWhRead
Resettable Active Energy ExportkWhRead
Resettable Reactive Energy ImportkvarhRead
Resettable Reactive Energy ExportkvarhRead
Voltage L1-NVRead
Voltage L2-NVRead
Voltage L3-NVRead
Voltage L1-L2VRead
Voltage L3-L2VRead
Voltage L1-L3VRead
Current L1ARead
Current L2ARead
Current L3ARead
Current NARead
Active Power TotalWRead
Active Power L1WRead
Active Power L2WRead
Active Power L3WRead
Reactive Power TotalvarRead
Reactive Power L1varRead
Reactive Power L2varRead
Reactive Power L3varRead
Apparent Power TotalVARead
Apparent Power L1VARead
Apparent Power L2VARead
Apparent Power L3VARead
FrequencyHzRead
Power Phase Angle Total°Read
Power Phase Angle L1°Read
Power Phase Angle L2°Read
Power Phase Angle L3°Read
Voltage Phase Angle U1°Read
Voltage Phase Angle U2°Read
Voltage Phase Angle U3°Read
Current Phase Angle I1°Read
Current Phase Angle I2°Read
Current Phase Angle I3°Read
Power Factor TotalRead
Power Factor L1Read
Power Factor L2Read
Power Factor L3Read
Current Quadrant TotalRead
Current Quadrant L1Read
Current Quadrant L2Read
Current Quadrant L3Read
Output 1Read and write
Input 1 StateRead
Input 1 CounterRead
Serial NumberRead
Meter Firmware VersionRead
Type DesignationRead
CO2 Conversion FactorRead and write
Currency Import FactorRead and write
LED TypeRead and write
Wire TypeRead and write
Currency Export FactorRead and write
Reset Input 1 CounterWrite
Reset Resettable Active Energy ImportWrite
Reset Resettable Active Energy ExportWrite
Reset Resettable Reactive Energy ImportWrite
Reset Resettable Reactive Energy ExportWrite
Reset System LogsWrite
Reset Net Quality LogsWrite
Reset All LogsWrite
Reset All Resettable RegistersWrite
Error Log Get Next BlockRead and write
Error Log Entry NumberRead and write
Error Log DirectionRead and write
Error Log Entry 1 CategoryRead
Error Log Entry 1 Event IdRead
Error Log Entry 1 DurationsRead
Error Log Entry 2 CategoryRead
Error Log Entry 2 Event IdRead
Error Log Entry 2 DurationsRead
Error Log Entry 3 CategoryRead
Error Log Entry 3 Event IdRead
Error Log Entry 3 DurationsRead
Error Log Entry 4 CategoryRead
Error Log Entry 4 Event IdRead
Error Log Entry 4 DurationsRead
Error Log Entry 5 CategoryRead
Error Log Entry 5 Event IdRead
Error Log Entry 5 DurationsRead
Error Log Entry 6 CategoryRead
Error Log Entry 6 Event IdRead
Error Log Entry 6 DurationsRead
Error Log Entry 7 CategoryRead
Error Log Entry 7 Event IdRead
Error Log Entry 7 DurationsRead
Error Log Entry 8 CategoryRead
Error Log Entry 8 Event IdRead
Error Log Entry 8 DurationsRead
Error Log Entry 9 CategoryRead
Error Log Entry 9 Event IdRead
Error Log Entry 9 DurationsRead
Error Log Entry 10 CategoryRead
Error Log Entry 10 Event IdRead
Error Log Entry 10 DurationsRead
Error Log Entry 11 CategoryRead
Error Log Entry 11 Event IdRead
Error Log Entry 11 DurationsRead
Error Log Entry 12 CategoryRead
Error Log Entry 12 Event IdRead
Error Log Entry 12 DurationsRead
Error Log Entry 13 CategoryRead
Error Log Entry 13 Event IdRead
Error Log Entry 13 DurationsRead
Error Log Entry 14 CategoryRead
Error Log Entry 14 Event IdRead
Error Log Entry 14 DurationsRead
Error Log Entry 15 CategoryRead
Error Log Entry 15 Event IdRead
Error Log Entry 15 DurationsRead
Alarm Log Get Next BlockRead and write
Alarm Log Entry NumberRead and write
Alarm Log DirectionRead and write
Alarm Log Entry 1 CategoryRead
Alarm Log Entry 1 Event IdRead
Alarm Log Entry 1 DurationsRead
Alarm Log Entry 2 CategoryRead
Alarm Log Entry 2 Event IdRead
Alarm Log Entry 2 DurationsRead
Alarm Log Entry 3 CategoryRead
Alarm Log Entry 3 Event IdRead
Alarm Log Entry 3 DurationsRead
Alarm Log Entry 4 CategoryRead
Alarm Log Entry 4 Event IdRead
Alarm Log Entry 4 DurationsRead
Alarm Log Entry 5 CategoryRead
Alarm Log Entry 5 Event IdRead
Alarm Log Entry 5 DurationsRead
Alarm Log Entry 6 CategoryRead
Alarm Log Entry 6 Event IdRead
Alarm Log Entry 6 DurationsRead
Alarm Log Entry 7 CategoryRead
Alarm Log Entry 7 Event IdRead
Alarm Log Entry 7 DurationsRead
Alarm Log Entry 8 CategoryRead
Alarm Log Entry 8 Event IdRead
Alarm Log Entry 8 DurationsRead
Alarm Log Entry 9 CategoryRead
Alarm Log Entry 9 Event IdRead
Alarm Log Entry 9 DurationsRead
Alarm Log Entry 10 CategoryRead
Alarm Log Entry 10 Event IdRead
Alarm Log Entry 10 DurationsRead
Alarm Log Entry 11 CategoryRead
Alarm Log Entry 11 Event IdRead
Alarm Log Entry 11 DurationsRead
Alarm Log Entry 12 CategoryRead
Alarm Log Entry 12 Event IdRead
Alarm Log Entry 12 DurationsRead
Alarm Log Entry 13 CategoryRead
Alarm Log Entry 13 Event IdRead
Alarm Log Entry 13 DurationsRead
Alarm Log Entry 14 CategoryRead
Alarm Log Entry 14 Event IdRead
Alarm Log Entry 14 DurationsRead
Alarm Log Entry 15 CategoryRead
Alarm Log Entry 15 Event IdRead
Alarm Log Entry 15 DurationsRead
Audit Log Get Next BlockRead and write
Audit Log Entry NumberRead and write
Audit Log DirectionRead and write
Audit Log Entry NrRead
Audit Log Upgrade CounterRead
Audit Log FW Version MajorRead
Audit Log FW Version MinorRead
Audit Log FW Version PatchRead
Audit Log WiresRead
Audit Log Trafo V PrimaryRead
Audit Log Trafo V SecondaryRead
Audit Log Trafo I PrimaryRead
Audit Log Trafo I SecondaryRead
Audit Log Active Energy Import TotalkWhRead
Audit Log Active Energy Import L1kWhRead
Audit Log Active Energy Import L2kWhRead
Audit Log Active Energy Import L3kWhRead
Audit Log Active Energy Import Tariff 1kWhRead
Audit Log Active Energy Import Tariff 2kWhRead
Audit Log Active Energy Import Tariff 3kWhRead
Audit Log Active Energy Import Tariff 4kWhRead
Audit Log Active Energy Export TotalkWhRead
Alarm NumberRead and write
Alarm ParameterRead and write
Alarm ThresholdRead and write
Alarm HysteresisRead and write
Alarm DelayRead and write
Alarm TypeRead and write
Alarm ActionRead and write
Alarm Action Output NumberRead and write
I/O Port 1 FunctionRead
I/O Port 2 FunctionRead
I/O Ports Set To Pulse InputRead and write
I/O Ports Set To Always OnRead and write
I/O Ports Set To Always OffRead and write
I/O Ports Set To CommunicationRead and write
Pulse Output PortRead and write
Pulse Output Energy TypeRead and write
Pulse Output FrequencyRead and write
Pulse Output LengthmsRead and write
Tariff SourceRead and write
Active TariffRead and write
Modbus AddressRead and write
Modbus BaudrateRead and write
Modbus ParityRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show energy import, export and power per phase of every tenant meter on one dashboard.
  • Send an email alert when the current of a phase rises above the limit of the circuit breaker.
  • Keep 365 days of history of energy per tariff to bill tenants or compare day and night use.
  • Switch the active tariff from ModbusCloud when your contract has fixed peak hours.
  • Reset the resettable energy counters at the start of a measurement period without touching the totals.

Installation

  1. Connect RS485 A, B and common of the D13 15 to the RS485 port of the ModbusCloud Gateway and terminate both ends of the bus with 120 ohm.

  2. Set or read the Modbus address, baud rate and parity in the meter menu.

  3. In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings, then import this template.

  4. Check that the voltages L1-N to L3-N, the frequency and the total active energy arrive with plausible values.

Things to watch for

The meter does not answer on the RS485 bus. What should I check?

The bus is polarity dependent, so swap A and B if nothing comes back and connect the common wire as well. Match the address, baud rate and parity shown in the meter menu, terminate only the two ends of the bus and keep stubs shorter than 1 m.

Why do some registers show FFFF or a very large value?

The meter fills registers for quantities it does not have with an invalid value: FFFF for unsigned and 7FFF for signed values. On a single phase D11 15 this happens for phases L2 and L3 and the line voltages; ignore those registers or remove them from the device.

Which registers can I write from ModbusCloud?

Output 1, the active tariff, tariff source, alarm, pulse output and I/O settings, the CO2 and currency factors, the reset commands and the Modbus settings. The meter does not confirm a write, so read the value back afterwards. A reset sets counters to zero for good.

Why does output 1 not switch when I write to it?

The output must first be linked to the communication function. Write the port number to the register for I/O ports set to communication, then switch output 1. If the port is used for pulses, tariffs or alarms, Modbus cannot switch it.

Can several meters share one RS485 line?

Yes, up to 247 meters. Give every meter its own address and use the same baud rate and parity on all of them. Run the bus as one line of at most 700 m and terminate both ends.