ABB ABB UMC100.3 Modbus RTU template

ABB UMC100.3

Motor controller for MCCs: motor current, thermal load, trips and run commands.

The ABB UMC100.3 is a universal motor controller that protects, switches and monitors low-voltage motors in motor control centres and machines. This Modbus RTU template reads motor current, thermal load, run state, warnings and trips, and lets you start, stop and reset the motor from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
46, read and write
Brand
ABB
Key readings
Motor current · Thermal load · Time to trip · Active power · Run state · Trips and warnings · Fault code
Available commands
Run forward and reverse · Off · Fault reset · Digital outputs
Compatible models
UMC100.3 with MRP31.0
Last updated

Registers (46)

26 read, 20 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Motor Current%Read
Thermal Load%Read
Time To TripsRead
Time To RestartsRead
Active PowerRead
DX1xx Inputs And Actuator StatusRead
Protection Status WordRead
Run Reverse ClosingRead
OffRead
Run Forward OpeningRead
Overload WarningRead
Reverse Lockout TimeRead
Local ControlRead
Summary FaultRead
Summary WarningRead
Run Fast ForwardRead
UMC100 DI0Read
UMC100 DI1Read
UMC100 DI2Read
UMC100 DI3Read
UMC100 DI4Read
UMC100 DI5Read
Cmd Run Reverse ClosingWrite
Cmd OffWrite
Cmd Run Forward OpeningWrite
Cmd Prepare Emergency StartWrite
Cmd Auto ModeWrite
Cmd Fault ResetWrite
Cmd Run Fast ForwardWrite
Cmd UMC100 24V DC OutWrite
Cmd UMC100 DO0Write
Cmd UMC100 DO1Write
Cmd UMC100 DO2Write
Cmd DX1xx DO0Write
Cmd DX1xx DO1Write
Cmd DX1xx DO2Write
Cmd DX1xx DO3Write
Cmd VI15x DO0Write
Diagnosis Word 1Read
Diagnosis Word 2Read
Diagnosis Word 3Read
Diagnosis Word 4 And Fault CodeRead
Analog Output Word 1Write
Analog Output Word 2Write
Analog Output Word 3Write
Analog Output Word 4Write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show motor current, thermal load and run state of every feeder in an MCC on one dashboard.
  • Get an alarm by email when a motor trips on overload, phase loss or earth fault.
  • Track motor current and active power in the history to spot pumps or fans that start to wear.
  • Reset a tripped motor or switch it off remotely after checking the cause.
  • Watch the time to trip and the thermal load to see when a motor runs close to its limit.

Installation

  1. Fit the MRP31.0 interface on the UMC100.3 or on an SMK3.0 kit and connect Data A and Data B to the RS485 port of the ModbusCloud Gateway, with 120 ohm termination at both bus ends.

  2. On the UMC100-PAN panel, go to Communication, Modbus RTU, and set the bus address and baud rate.

  3. In ModbusCloud, add a Modbus device with the same address and speed and import this template.

  4. Check that the run state and motor current come in when the motor runs, then set up dashboards and alarms.

Things to watch for

The controller does not answer. What should I check?

Check that address and baud rate on the UMC100-PAN match the device in ModbusCloud. The interface detects parity and stop bits itself. Swap Data A and Data B if needed and check the 120 ohm resistors, because the MRP31.0 has no built-in termination. The bus LED flashes green while there is no connection to a master.

The motor current shows 100 while the motor runs normally. Is that right?

Yes. The current is given as a percentage of the rated current Ie set in the controller, not in ampere. 100 means the motor draws its rated current. Check the rated current setting if the values look too high or too low.

How do I start or reset the motor from ModbusCloud?

Write 1 to Cmd Run Forward Opening or Cmd Run Reverse Closing to start, to Cmd Off to stop and to Cmd Fault Reset after a trip. The controller only follows bus commands when it is in remote or auto mode. Make sure the motor can start safely before you send a run command.

Can several controllers share one bus?

Yes. Give every UMC100.3 its own bus address on its panel and use the same speed on all of them. Add each controller as a separate Modbus device in ModbusCloud.