Chiltrix Chiltrix CX34 CX35 CX50 Modbus RTU template

Chiltrix CX34 CX35 CX50

Controls Chiltrix CX34, CX35 and CX50 heat pumps via Modbus RTU

This template connects Chiltrix CX34, CX35 and CX50 air-to-water heat pumps to ModbusCloud via Modbus RTU. It reads sensor data such as water temperatures, compressor frequency and water flow, and provides control over on/off switching, operating mode and target temperatures.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
13, read and write
Key readings
Ambient Air Temp · Outlet Water Temp · Inlet Water Temp · Compressor Frequency · Water Flow · Input AC Current
Available commands
Switch on/off · Operating Mode · AC Cooling Target Temp · AC Heating Target Temp
Compatible models
CX34 · CX35 · CX50
Last updated

Registers (13)

13 read, 4 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Switch on/offRead and write
Operating ModeRead and write
AC cooling target temperature°FRead and write
AC heating target temprerature°FRead and write
Hot water target temperature°FRead
AC heating Au modeRead
Hot water Au modeRead
Ambient Air Temp°FRead
Compressor FrequencyHzRead
Outlet water Temp°FRead
Water FlowgpmRead
Input Ac CurrentARead
Inlet Water Temp°FRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor outlet and inlet water temperatures on a live dashboard to verify heat pump performance remotely.
  • Create an alert when compressor frequency or input AC current exceeds a predefined threshold for early fault detection.
  • Log water flow and temperature data over time to generate seasonal COP estimates for energy reporting.
  • Switch the Chiltrix heat pump on or off remotely during commissioning or scheduled maintenance windows.
  • Adjust AC cooling and heating target temperatures from the cloud dashboard without an on-site visit.
  • Compare ambient air temperature against water temperatures to diagnose defrost cycles or capacity issues.

Installation

  1. Connect the Modbus RTU wiring (A, B and GND) from the Chiltrix CX34, CX35 or CX50 terminal block to the RS-485 port on your ModbusCloud Gateway.

  2. Verify that the Chiltrix unit is configured for Modbus RTU communication at 9600 baud, 8 data bits, 1 stop bit, no parity, and note the slave address set on the unit.

  3. Set the matching baud rate and slave address in the ModbusCloud gateway configuration so it matches the Chiltrix settings exactly.

  4. Import the Chiltrix CX34 CX35 CX50 template from the ModbusCloud template library and assign it to the gateway port connected to the heat pump.

  5. Power cycle the gateway and confirm that live readings such as outlet water temperature and compressor frequency appear on the ModbusCloud dashboard.

Things to watch for

Why do the temperature values look unusually high on the dashboard?

All Chiltrix temperature registers report values in degrees Fahrenheit. If your dashboard expects Celsius, apply a conversion or check the template scaling settings. A reading of 113 F corresponds to 45 C.

Can I read status and write setpoints on the same register?

Yes. Registers 140 through 146 are dual-purpose. They return current status when read and accept new setpoints when written. The template handles both operations on these addresses.

What baud rate and serial settings should I use?

Configure 9600 baud, 8 data bits, 1 stop bit and no parity on both the Chiltrix unit and the ModbusCloud gateway. Mismatched settings will cause communication timeouts.

Does this template work with other Chiltrix models beyond the CX34, CX35 and CX50?

The template is validated for the CX34, CX35 and CX50. Other models with the same Modbus register map may work, but you should verify compatibility against the Chiltrix Modbus documentation before deploying.

Want to see how it works?