Condair Condair DL Modbus RTU template

Condair DL

Hybrid humidifier for air handling units with nozzle spray and ceramic evaporation stage.

The Condair DL is a hybrid humidifier that humidifies the air in air handling units with atomising nozzles and a ceramic evaporation stage. This Modbus RTU template reads status, errors, capacity, pressures and water values, and lets you change the setpoint, capacity limit and remote enable from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
41, read and write
Brand
Condair
Key readings
Actual humidity or demand · Humidification capacity · Device status · Error code · Inlet and nozzle pressure · Water conductivity · Operating hours
Available commands
Humidity setpoint · Capacity limitation · Demand signal · Remote enable · Remote flushing
Compatible models
DL · DL II
Last updated

Registers (41)

41 read, 8 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Actual Humidity Or Demand%Read
Actual Humidification CapacityRead
Max Humidification CapacityRead
Device StatusRead
Maintenance And Error StatusRead
Error Or Warning CodeRead
Safety LoopRead
PS4 Inlet PressureRead
PS5 Nozzle PressureRead
Water TemperatureRead
Water ConductivityµS/cmRead
Pump CurrentARead
Ag-Ion CurrentmARead
Target Ag-Ion CurrentmARead
Remaining Ag-Ion CapacityRead
Operating HourshRead
Next MaintenancehRead
DL TypeRead
Y1 Inlet ValveRead
Y2 ReserveRead
Y3 Valve Air CleaningRead
Y4 Valve External Pipe FlushRead
Y5 Spray ValveRead
Y6 Spray ValveRead
Y7 Spray ValveRead
Y8 Spray ValveRead
Y9 Spray ValveRead
Y10 Drain ValveRead
Y11 Auxiliary Outlet ValveRead
Frequency Converter EnableRead
Frequency Converter StatusRead
FanRead
Disinfection PumpRead
Setpoint%Read and write
P-Band%Read and write
I-TimeminRead and write
Capacity Limitation%Read and write
Actual Humidity Or Demand Via Modbus%Read and write
Remote EnableRead and write
Remote FlushingRead and write
Remote Ceramic Wash OverRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show actual humidity, humidification capacity and device status of every humidifier in one dashboard.
  • Send an email when the error code is not 0 or the maintenance status shows that service is due.
  • Track nozzle pressure and water conductivity over months to spot clogged nozzles or bad water treatment early.
  • Raise the capacity limitation or the humidity setpoint remotely when the building use changes.
  • Plan maintenance from the hours until the next service and the remaining silver ion capacity.

Installation

  1. Connect Data+, Data- and GND of the controller to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.

  2. On the controller, open Menu, password 8808, Network, Modbus Settings, choose Modbus/RTU and check address, baud rate and parity.

  3. In ModbusCloud, add a Modbus device with address 10, 19200 baud, 8 data bits, even parity and 1 stop bit, and import this template.

  4. Check that device status and actual humidity show plausible values.

  5. To control the humidifier via Modbus, set Source and Remote Enable to Modbus in the control settings.

Things to watch for

The humidifier does not answer. What should I check?

Check that Modbus Protocol is set to Modbus/RTU (the controller restarts after changing it), that address, baud rate and parity match ModbusCloud, and that Data+ and Data- are not swapped. Settings only take effect after a restart.

Why are the float values like pressure or capacity nonsense?

The 32-bit values follow the Register Sequence setting. The template expects MSR first, the factory setting. If someone set LSR first, set it back or change the word order of these registers.

The humidifier stops with warning W35 after writing a demand signal.

When the demand or humidity signal comes via Modbus, it must be written again within the signal timeout (default 300 s). Make sure your automation rewrites it well within that time, or use the setpoint with the built-in humidity control instead.

Writing Remote Enable has no effect. Why?

Remote Enable only works when the control settings have Remote Enable set to Modbus and the controller runs software 1.4.0 or higher. Without that, the register is ignored.