Condair Condair ME Modbus RTU template

Condair ME

Adiabatic evaporative humidifier and cooler for air handling units.

The Condair ME is an adiabatic evaporative humidifier and cooler for air handling units, with an integrated controller. This Modbus RTU template reads status, faults, pumps, humidity, temperatures and service counters, and lets you change setpoints, send the demand signal and start draining or a reset from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
60, read and write
Brand
Condair
Key readings
System mode and device status · Maintenance and error status · Error or warning code · Pump faults and speeds · Actual humidity or demand · Air and water temperature · Water capacity per stage · Operating hours and next service
Available commands
Humidity setpoint and control · Temperature setpoint in cooling mode · Demand signal via Modbus · Remote draining · Remote matrix wash over · Remote error reset
Compatible models
ME · ME II
Last updated

Registers (60)

60 read, 11 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
System ModeRead2000FC04uint16
Device StatusRead2001FC04uint16
Maintenance And Error StatusRead2002FC04uint16
Error Or Warning CodeRead2003FC04uint16
Safety LoopRead2004FC04uint16
Number Of Running StagesRead
Fault Pump 1Read
Fault Pump 2Read
Fault Pump 3Read
Fault Pump 4Read
Fault Pump 5Read
Fault Pump 6Read
Fault Pump 7Read
Fault Water InletRead
Fault Water TemperatureRead
Fault Water OutletRead
Fault Level SensorRead
Fault Water ConductivityRead
Speed Pump 1%Read
Speed Pump 2%Read
Speed Pump 3%Read
Speed Pump 4%Read
Speed Pump 5%Read
Speed Pump 6%Read
Speed Pump 7%Read
Water Level TankRead
WET Tank LevelRead
Disinfection Tank LevelRead
Leakage SensorRead
Inlet ValveRead
Drain ValveRead
Drain PumpRead
Actual Humidity Or Demand%Read
Actual Air TemperatureRead
Incoming Air TemperatureRead
Actual Water TemperatureRead
Water ConductivityµS/cmRead
UV CurrentARead
Water Capacity Stage 1Read
Water Capacity Stage 2Read
Water Capacity Stage 3Read
Water Capacity Stage 4Read
Water Capacity Stage 5Read
Water Capacity Stage 6Read
Water Capacity Stage 7Read
Operating HourshRead
Next MaintenancehRead
Next UV Lamp ExchangedRead
Next PureFlo ExchangedRead
Setpoint Humidity Control%Read and write
P-Band Humidity Control%Read and write
I-Time Humidity ControlminRead and write
Actual Humidity Or Demand Via Modbus%Read and write
I-Time Temperature ControlminRead and write
Setpoint Temperature ControlRead and write
P-Band Temperature ControlRead and write
Actual Temperature Via ModbusRead and write
Remote DrainingRead and write
Remote Matrix Wash OverRead and write
Remote Error Warning ResetRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Get an email alert on an error or warning, with the error code, before a service visit.
  • Watch the fault and speed of each pump to spot a failing pump early.
  • Plan service visits from the hours until the next maintenance and the days until the next UV lamp exchange.
  • Compare actual humidity with the setpoint to check that the air handling unit reaches its target.
  • Start draining remotely before a long standstill and follow the progress.
  • Reset an error remotely after the cause has been fixed.

Installation

  1. Connect Data+, Data- and GND of the controller to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.

  2. On the controller, open Menu, enter password 8808, go to Network, Modbus Settings and set protocol Modbus/RTU, address, baud rate, parity and register sequence MSR first.

  3. In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings and import this template.

  4. Check that system mode and device status match the controller display, for example Standby when there is no demand.

Things to watch for

The Condair ME does not answer on the RS485 bus. What should I check?

Check that the protocol under Network, Modbus Settings is Modbus/RTU and not Off or Modbus/TCP, and that address, baud rate and parity match, by default 10, 19200 baud and even parity. Then swap Data+ and Data- and check the termination. The controller restarts after a change.

Temperatures and capacities show strange values.

Set the register sequence on the controller to MSR first. With LSR first the two halves of each value arrive swapped. The unit follows the Metric or Imperial setting of the controller.

Writing the demand signal has no effect or warning W35 appears.

The controller only uses the signal from Modbus when Source is set to Modbus under Controls, Signal Settings. ModbusCloud must write it again within the Signal Timeout, 300 seconds by default, or warning W35 stops humidification.

How do I start draining or reset an error remotely?

Write 1 to Remote Draining to start draining and 0 to stop; reading it gives 100 when off or the progress in percent. Write 1 to Remote Error Warning Reset to reset errors and warnings.

Want to see how it works?

Electrician working in an open distribution board