
Condair Nortec EL
Electrode steam humidifier: status, demand, valves, operating hours and humidity setpoints.
The Condair Nortec EL is an electrode steam humidifier that adds steam to the air of buildings, clean rooms and production halls. This Modbus RTU template reads operating status, system demand, safety loop, valves and operating hours per cylinder, and lets you write remote disable, capacity limits and humidity setpoints from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 43, read and write
- Brand
- Condair
- Key readings
- Operating status · System demand · Input signal · Safety loop · Inlet and drain valves · Operating hours
- Available commands
- Remote disable · Capacity limit · Humidity setpoint · Humidity or demand signal · P-band and I-time
- Compatible models
- Nortec EL · EL-150 · EL-200
- Last updated
Registers (43)
43 read, 19 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Remote Disable | Read and write | 0 | FC03 / FC06 | uint16 | |
| Manual Capacity A | % | Read and write | 1 | FC03 / FC06 | uint16 |
| Setpoint Channel A1 | % | Read and write | 2 | FC03 / FC06 | uint16 |
| Setpoint Channel A2 | % | Read and write | 3 | FC03 / FC06 | uint16 |
| Digital RH Demand A1 | % | Read and write | 4 | FC03 / FC06 | uint16 |
| Digital RH Demand A2 | % | Read and write | |||
| Manual Capacity B | % | Read and write | |||
| Setpoint Channel B1 | % | Read and write | |||
| Setpoint Channel B2 | % | Read and write | |||
| Digital RH Demand B1 | % | Read and write | |||
| Digital RH Demand B2 | % | Read and write | |||
| P-Band Channel A1 | % | Read and write | |||
| P-Band Channel A2 | % | Read and write | |||
| P-Band Channel B1 | % | Read and write | |||
| P-Band Channel B2 | % | Read and write | |||
| I-Time Channel A1 | min | Read and write | |||
| Damp Time Channel A2 | s | Read and write | |||
| I-Time Channel B1 | min | Read and write | |||
| Damp Time Channel B2 | s | Read and write | |||
| Enable Input A | Read | ||||
| Input Signal Channel A1 | % | Read | |||
| Limiter Signal Channel A2 | % | Read | |||
| System Demand A | % | Read | |||
| Safety Loop A | Read | ||||
| Blower Pack A | Read | ||||
| Fan Activate A | Read | ||||
| Operating Hours A | h | Read | |||
| Enable Input B | Read | ||||
| Input Signal Channel B1 | % | Read | |||
| Limiter Signal Channel B2 | % | Read | |||
| System Demand B | % | Read | |||
| Safety Loop B | Read | ||||
| Blower Pack B | Read | ||||
| Fan Activate B | Read | ||||
| Operating Hours B | h | Read | |||
| Status A | Read | ||||
| Service Status B | Read | ||||
| Main Contactor A | Read | ||||
| Main Contactor B | Read | ||||
| Inlet Valve A | Read | ||||
| Inlet Valve B | Read | ||||
| Drain Valve A | Read | ||||
| Drain Valve B | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Get an email when the operating status changes to Warning or Fault, so a technician knows the humidifier needs attention.
- Watch the safety loop and blower pack on a dashboard to see at a glance why no steam is produced.
- Track operating hours per cylinder in the history to plan cylinder replacement before it fails.
- Send the room humidity or demand from your controller and compare it with the system demand of the humidifier.
- Disable steam production remotely during maintenance or outside the heating season.
Installation
Connect the 3-pole Modbus plug on the main processor card to the RS485 A and B terminals of the ModbusCloud Gateway, and set jumper J4 only at the end of the bus.
On the display open Menu, enter 0335, go to Configuration, Comms. and switch Modbus on; keep address 10, even parity and 9600 baud or note your own values.
Restart the humidifier so the new communication settings take effect.
In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, and import this template.
Check that the operating status matches the display, for example Standby when there is no demand.
Things to watch for
The humidifier does not answer on the RS485 bus. What should I check?
Modbus is off by default. Switch it on under Configuration, Comms., then check address, parity and baud rate (default 10, even, 9600). Swap A and B if nothing comes back, and set jumper J4 only on the last device on the bus.
Why do the cylinder B values read 0?
Cylinder B exists only on the two-cylinder EL-150 and EL-200. On single-cylinder units the B values for enable input, signals, demand, valves and operating hours stay at 0 and you can remove them from the device.
Can several humidifiers share one RS485 line?
Yes. Give each humidifier its own address under Configuration, Comms. and use the same baud rate and parity on all of them. Wire the bus as one line from unit to unit and terminate both ends.
Why does writing a setpoint or demand have no effect?
The humidifier follows a wired control signal by default. Set Source to Modbus under Configuration, Control Settings, and choose the control mode Demand, RH P or RH PI that matches the value you write. Write within the allowed range, for example 0 to 95 % for a setpoint.
More Condair templates
Want to see how it works?










