ModbusCloud
Back to library
Condair Condair Nortec EL Modbus RTU template
Modbus RTU

Condair Nortec EL

Condair

Electrode steam humidifier: status, demand, setpoints, valves and operating hours over Modbus RTU.

Overview

The Condair Nortec EL is an electrode steam humidifier with a 3-pole Modbus RTU plug on its main processor card. This template follows table 2 of the Condair Modbus Installation and Operation Manual 2560599-G (24 Jan 2019) and covers status, demand, safety loop, setpoints, valves and operating hours per cylinder over RS485 with address 10, 9600 baud and 8E1.

Key readings

  • Operating status per unit
  • System demand A and B
  • Input and limiter signals
  • Safety loop, blower pack and fan
  • Main contactor, inlet and drain valves
  • Operating hours per cylinder

Available commands

  • Remote disable
  • Manual capacity limit per cylinder
  • Humidity setpoints per channel
  • Digital RH or demand via Modbus
  • P-band, I-time and damp time

Use cases

  • Alert when Status A changes to Warning or Fault so a technician knows the humidifier needs attention.
  • Watch Safety Loop A and Blower Pack A to see why the humidifier does not produce steam.
  • Track Operating Hours A and B to plan cylinder replacement.
  • Write Digital RH Demand A1 from the building controller and compare it with System Demand A.

Installation

  1. 1Connect the 3-pole Modbus plug on the main processor card to the RS485 port of your ModbusCloud Gateway; set jumper J4 at the end of the bus.
  2. 2On the display open Menu, enter 0335, go to Configuration, Comms. and switch Modbus on; keep address 10, even parity and 9600 baud or note your values.
  3. 3In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings, then import this template.
  4. 4Check the link: Status A should match the display, for example 1 = Standby when there is no demand.

Things to watch for

The Nortec EL does not answer on the RS485 bus.
Modbus is off by default. Switch it on under Configuration, Comms., then check address, parity and baud rate (default 10, even, 9600) and the wiring of the 3-pole plug. Set jumper J4 only at the end of the bus.
Writing the setpoint or demand has no effect.
The humidifier uses a hardwired control signal by default. Set Source to Modbus under Configuration, Control Settings, and choose the control mode Demand, RH P or RH PI that matches the register you write.
Operating hours show strange values.
Operating Hours A and B are floats over two registers with word order CD AB. Read both registers at once and keep the byte order CDAB from the template.
Why do the B registers read 0 on my unit?
Unit B exists only on the two-cylinder Nortec EL-150 and EL-200. On single-cylinder models the B registers for enable input, signals, demand, valves and operating hours stay at 0 and can be removed from the device.

Registers (43)

43 read / 19 write

NameAddressFunctionTypeUnitAccess
Remote Disable•••••••••R/W
Manual Capacity A•••••••••%R/W
Setpoint Channel A1•••••••••%R/W
Setpoint Channel A2•••••••••%R/W
Digital RH Demand A1•••••••••%R/W
Digital RH Demand A2•••••••••%R/W
Manual Capacity B•••••••••%R/W
Setpoint Channel B1•••••••••%R/W
Setpoint Channel B2•••••••••%R/W
Digital RH Demand B1•••••••••%R/W
Digital RH Demand B2•••••••••%R/W
P-Band Channel A1•••••••••%R/W
P-Band Channel A2•••••••••%R/W
P-Band Channel B1•••••••••%R/W
P-Band Channel B2•••••••••%R/W
I-Time Channel A1•••••••••minR/W
Damp Time Channel A2•••••••••sR/W
I-Time Channel B1•••••••••minR/W
Damp Time Channel B2•••••••••sR/W
Enable Input A•••••••••R
Input Signal Channel A1•••••••••%R
Limiter Signal Channel A2•••••••••%R
System Demand A•••••••••%R
Safety Loop A•••••••••R
Blower Pack A•••••••••R
Fan Activate A•••••••••R
Operating Hours A•••••••••hR
Enable Input B•••••••••R
Input Signal Channel B1•••••••••%R
Limiter Signal Channel B2•••••••••%R
System Demand B•••••••••%R
Safety Loop B•••••••••R
Blower Pack B•••••••••R
Fan Activate B•••••••••R
Operating Hours B•••••••••hR
Status A•••••••••R
Service Status B•••••••••R
Main Contactor A•••••••••R
Main Contactor B•••••••••R
Inlet Valve A•••••••••R
Inlet Valve B•••••••••R
Drain Valve A•••••••••R
Drain Valve B•••••••••R

Loading registers…

Read the Condair Nortec EL remotely

We load the templates onto the gateway and set up your portal, you connect it at your customer's site. Tell us briefly what you need and we'll send a proposal.

From €295 + €149/year.

Prefer to configure it yourself? Order the gateway in the shop·Or see the live demo first

EU-hosted
Data in the Netherlands and Germany
Open standard
Based on Modbus RTU/TCP
Free to browse
No account or payment required
European company
Based in the Netherlands

More Condair templates

More RTU templates