Copeland EXD-SH1/2

Superheat controller for electrical expansion valves in one or two refrigeration circuits.

The Copeland EXD-SH1/2 is a superheat and temperature controller that drives electrical expansion valves in one or two refrigeration or air conditioning circuits. This Modbus RTU template reads superheat, valve opening, suction pressure and temperatures, alarms and state per circuit, and lets you set superheat, manual valve control and all parameters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
167, read and write
Key readings
Superheat · Valve opening · Suction pressure · Suction temperature · Saturation temperature · Alarm status · Application state
Available commands
Superheat setpoint · Manual valve opening · Demand · Refrigerant · Alarm reset
Compatible models
EXD-SH1 · EXD-SH2 · Emerson EXD-SH1 · Emerson EXD-SH2
Last updated

Registers (167)

167 read, 140 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Software VersionRead256FC03uint16
Main Function Circuit 1Read257FC03uint16
Valve Opening Circuit 1%Read258FC03uint16
Digital Input Circuit 1Read259FC03uint16
Digital Output Circuit 1Read260FC03uint16
Suction Pressure Circuit 1barRead
Suction Temperature Circuit 1°CRead
Saturation Temperature Circuit 1°CRead
Pressure Sensor 1 FailureRead
Temperature Sensor 1 FailureRead
Functional Alarms Circuit 1Read
Hardware AlarmsRead
Application State Circuit 1Read
Superheat Setpoint Circuit 1KRead
Superheat Circuit 1KRead
Valve Opening Circuit 2%Read
Digital Input Circuit 2Read
Digital Output Circuit 2Read
Suction Pressure Circuit 2barRead
Suction Temperature Circuit 2°CRead
Saturation Temperature Circuit 2°CRead
Pressure Sensor 2 FailureRead
Temperature Sensor 2 FailureRead
Functional Alarms Circuit 2Read
Application State Circuit 2Read
Superheat Setpoint Circuit 2KRead
Superheat Circuit 2KRead
Factory DefaultRead and write
Alarm ResetRead and write
Manual Mode Circuit 1Read and write
Manual Valve Opening Circuit 1%Read and write
Modbus Demand Circuit 1Read and write
Modbus Pressure Circuit 1barRead and write
Digital Output Command Circuit 1Read and write
Manual Mode Circuit 2Read and write
Manual Valve Opening Circuit 2%Read and write
Modbus Demand Circuit 2Read and write
Modbus Pressure Circuit 2barRead and write
Digital Output Command Circuit 2Read and write
PasswordRead and write
Modbus AddressRead and write
Modbus Baud RateRead and write
Modbus ParityRead and write
Circuit 2 EnabledRead and write
Display UnitsRead and write
Function Circuit 1Read and write
Control Mode Circuit 1Read and write
Refrigerant Circuit 1Read and write
Pressure Sensor Type Circuit 1Read and write
Ratiometric Range Circuit 1barRead and write
Valve Type Circuit 1Read and write
Valve Scaling Circuit 1%Read and write
Start Opening Circuit 1%Read and write
Start Opening Duration Circuit 1sRead and write
Low Superheat Alarm Mode Circuit 1Read and write
Superheat Setpoint Config Circuit 1KRead and write
MOP Mode Circuit 1Read and write
MOP Temperature Limit Circuit 1°CRead and write
Low Pressure Alarm Mode Circuit 1Read and write
Low Pressure Cut-out Circuit 1barRead and write
Low Pressure Alarm Delay Circuit 1sRead and write
Low Pressure Cut-in Circuit 1barRead and write
Freeze Alarm Mode Circuit 1Read and write
Freeze Alarm Cut-out Circuit 1°CRead and write
Freeze Alarm Delay Circuit 1sRead and write
High Superheat Alarm Mode Circuit 1Read and write
High Superheat Alarm Setpoint Circuit 1KRead and write
High Superheat Alarm Delay Circuit 1minRead and write
Temperature Setpoint Circuit 1°CRead and write
Temperature Band Circuit 1KRead and write
Temperature Alarm Enable Circuit 1Read and write
Min Temperature Alarm Setpoint°CRead and write
Min Temperature Alarm DelayminRead and write
Max Temperature Alarm Setpoint°CRead and write
Max Temperature Alarm DelayminRead and write
Temperature Sensor Type Circuit 1Read and write
PID Kp Circuit 1Read and write
PID Ti Circuit 1sRead and write
PID Td Circuit 1sRead and write
Control Mode Circuit 2Read and write
Refrigerant Circuit 2Read and write
Pressure Sensor Type Circuit 2Read and write
Ratiometric Range Circuit 2barRead and write
Valve Type Circuit 2Read and write
Valve Scaling Circuit 2%Read and write
Start Opening Circuit 2%Read and write
Start Opening Duration Circuit 2sRead and write
Low Superheat Alarm Mode Circuit 2Read and write
Superheat Setpoint Config Circuit 2KRead and write
MOP Mode Circuit 2Read and write
MOP Temperature Limit Circuit 2°CRead and write
Low Pressure Alarm Mode Circuit 2Read and write
Low Pressure Cut-out Circuit 2barRead and write
Low Pressure Alarm Delay Circuit 2sRead and write
Low Pressure Cut-in Circuit 2barRead and write
Freeze Alarm Mode Circuit 2Read and write
Freeze Alarm Cut-out Circuit 2°CRead and write
Freeze Alarm Delay Circuit 2sRead and write
High Superheat Alarm Mode Circuit 2Read and write
High Superheat Alarm Setpoint Circuit 2KRead and write
High Superheat Alarm Delay Circuit 2minRead and write
Temperature Sensor Type Circuit 2Read and write
PID Kp Circuit 2Read and write
PID Ti Circuit 2sRead and write
PID Td Circuit 2sRead and write
Circuit 2 Enabled (RAM)Read and write
Display Units (RAM)Read and write
Function Circuit 1 (RAM)Read and write
Control Mode Circuit 1 (RAM)Read and write
Refrigerant Circuit 1 (RAM)Read and write
Pressure Sensor Type Circuit 1 (RAM)Read and write
Ratiometric Range Circuit 1 (RAM)barRead and write
Valve Type Circuit 1 (RAM)Read and write
Valve Scaling Circuit 1 (RAM)%Read and write
Start Opening Circuit 1 (RAM)%Read and write
Start Opening Duration Circuit 1 (RAM)sRead and write
Low Superheat Alarm Mode Circuit 1 (RAM)Read and write
Superheat Setpoint Config Circuit 1 (RAM)KRead and write
MOP Mode Circuit 1 (RAM)Read and write
MOP Temperature Limit Circuit 1 (RAM)°CRead and write
Low Pressure Alarm Mode Circuit 1 (RAM)Read and write
Low Pressure Cut-out Circuit 1 (RAM)barRead and write
Low Pressure Alarm Delay Circuit 1 (RAM)sRead and write
Low Pressure Cut-in Circuit 1 (RAM)barRead and write
Freeze Alarm Mode Circuit 1 (RAM)Read and write
Freeze Alarm Cut-out Circuit 1 (RAM)°CRead and write
Freeze Alarm Delay Circuit 1 (RAM)sRead and write
High Superheat Alarm Mode Circuit 1 (RAM)Read and write
High Superheat Alarm Setpoint Circuit 1 (RAM)KRead and write
High Superheat Alarm Delay Circuit 1 (RAM)minRead and write
Temperature Setpoint Circuit 1 (RAM)°CRead and write
Temperature Band Circuit 1 (RAM)KRead and write
Temperature Alarm Enable Circuit 1 (RAM)Read and write
Min Temperature Alarm Setpoint (RAM)°CRead and write
Min Temperature Alarm Delay (RAM)minRead and write
Max Temperature Alarm Setpoint (RAM)°CRead and write
Max Temperature Alarm Delay (RAM)minRead and write
Temperature Sensor Type Circuit 1 (RAM)Read and write
PID Kp Circuit 1 (RAM)Read and write
PID Ti Circuit 1 (RAM)sRead and write
PID Td Circuit 1 (RAM)sRead and write
Control Mode Circuit 2 (RAM)Read and write
Refrigerant Circuit 2 (RAM)Read and write
Pressure Sensor Type Circuit 2 (RAM)Read and write
Ratiometric Range Circuit 2 (RAM)barRead and write
Valve Type Circuit 2 (RAM)Read and write
Valve Scaling Circuit 2 (RAM)%Read and write
Start Opening Circuit 2 (RAM)%Read and write
Start Opening Duration Circuit 2 (RAM)sRead and write
Low Superheat Alarm Mode Circuit 2 (RAM)Read and write
Superheat Setpoint Config Circuit 2 (RAM)KRead and write
MOP Mode Circuit 2 (RAM)Read and write
MOP Temperature Limit Circuit 2 (RAM)°CRead and write
Low Pressure Alarm Mode Circuit 2 (RAM)Read and write
Low Pressure Cut-out Circuit 2 (RAM)barRead and write
Low Pressure Alarm Delay Circuit 2 (RAM)sRead and write
Low Pressure Cut-in Circuit 2 (RAM)barRead and write
Freeze Alarm Mode Circuit 2 (RAM)Read and write
Freeze Alarm Cut-out Circuit 2 (RAM)°CRead and write
Freeze Alarm Delay Circuit 2 (RAM)sRead and write
High Superheat Alarm Mode Circuit 2 (RAM)Read and write
High Superheat Alarm Setpoint Circuit 2 (RAM)KRead and write
High Superheat Alarm Delay Circuit 2 (RAM)minRead and write
Temperature Sensor Type Circuit 2 (RAM)Read and write
PID Kp Circuit 2 (RAM)Read and write
PID Ti Circuit 2 (RAM)sRead and write
PID Td Circuit 2 (RAM)sRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show superheat, valve opening and suction pressure of each circuit on a dashboard.
  • Get an email when a circuit reports low pressure, freeze or low superheat.
  • Alert on the hardware alarm register for sensor, stepper or power failures.
  • Compare superheat setpoint and actual superheat over months to spot a drifting valve.
  • Change the superheat setpoint remotely in the RAM copy without wearing the flash memory.

Installation

  1. Connect the RS485 terminals of the controller to the RS485 port of the ModbusCloud Gateway, A to A and B to B, with termination at the bus ends.

  2. Set address (Adr), baud rate (br) and parity (PAr) on the controller; the defaults are address 1 and even parity.

  3. In ModbusCloud, add a Modbus device (RTU) with that address, 19200 baud, even parity, 8 data bits and 1 stop bit, then import this template.

  4. Check that superheat and suction pressure show plausible values and that the application state reads Control.

Things to watch for

The controller does not answer. What should I check?

Check address, baud rate and parity on the controller: address 1 to 127, 19200 or 9600 baud, even or no parity. Swap A and B if nothing answers and fit termination at both bus ends. Each controller on the bus needs its own address.

Why are circuit 2 values zero?

Circuit 2 only exists on the EXD-SH2 and only when parameter Circuit 2 Enabled is 1. On an EXD-SH1 the circuit 2 registers carry no data and can be hidden.

Can I write configuration parameters often?

The flash copy of a parameter allows about 1000 writes. For values you change often, write the RAM copy instead; it has no limit but falls back to the flash value after a power failure. Writing from the portal must be enabled for your Gateway.

Why is my refrigerant change refused?

Refrigerant, pressure sensor type, valve type and main function can only be changed while the circuit is in the Off state. Stop the circuit first, write the value and start it again.