Copeland EXD-SH1/2
Superheat controller for electrical expansion valves in one or two refrigeration circuits.
The Copeland EXD-SH1/2 is a superheat and temperature controller that drives electrical expansion valves in one or two refrigeration or air conditioning circuits. This Modbus RTU template reads superheat, valve opening, suction pressure and temperatures, alarms and state per circuit, and lets you set superheat, manual valve control and all parameters from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 167, read and write
- Brand
- Copeland
- Key readings
- Superheat · Valve opening · Suction pressure · Suction temperature · Saturation temperature · Alarm status · Application state
- Available commands
- Superheat setpoint · Manual valve opening · Demand · Refrigerant · Alarm reset
- Compatible models
- EXD-SH1 · EXD-SH2 · Emerson EXD-SH1 · Emerson EXD-SH2
- Last updated
Registers (167)
167 read, 140 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Software Version | Read | 256 | FC03 | uint16 | |
| Main Function Circuit 1 | Read | 257 | FC03 | uint16 | |
| Valve Opening Circuit 1 | % | Read | 258 | FC03 | uint16 |
| Digital Input Circuit 1 | Read | 259 | FC03 | uint16 | |
| Digital Output Circuit 1 | Read | 260 | FC03 | uint16 | |
| Suction Pressure Circuit 1 | bar | Read | |||
| Suction Temperature Circuit 1 | °C | Read | |||
| Saturation Temperature Circuit 1 | °C | Read | |||
| Pressure Sensor 1 Failure | Read | ||||
| Temperature Sensor 1 Failure | Read | ||||
| Functional Alarms Circuit 1 | Read | ||||
| Hardware Alarms | Read | ||||
| Application State Circuit 1 | Read | ||||
| Superheat Setpoint Circuit 1 | K | Read | |||
| Superheat Circuit 1 | K | Read | |||
| Valve Opening Circuit 2 | % | Read | |||
| Digital Input Circuit 2 | Read | ||||
| Digital Output Circuit 2 | Read | ||||
| Suction Pressure Circuit 2 | bar | Read | |||
| Suction Temperature Circuit 2 | °C | Read | |||
| Saturation Temperature Circuit 2 | °C | Read | |||
| Pressure Sensor 2 Failure | Read | ||||
| Temperature Sensor 2 Failure | Read | ||||
| Functional Alarms Circuit 2 | Read | ||||
| Application State Circuit 2 | Read | ||||
| Superheat Setpoint Circuit 2 | K | Read | |||
| Superheat Circuit 2 | K | Read | |||
| Factory Default | Read and write | ||||
| Alarm Reset | Read and write | ||||
| Manual Mode Circuit 1 | Read and write | ||||
| Manual Valve Opening Circuit 1 | % | Read and write | |||
| Modbus Demand Circuit 1 | Read and write | ||||
| Modbus Pressure Circuit 1 | bar | Read and write | |||
| Digital Output Command Circuit 1 | Read and write | ||||
| Manual Mode Circuit 2 | Read and write | ||||
| Manual Valve Opening Circuit 2 | % | Read and write | |||
| Modbus Demand Circuit 2 | Read and write | ||||
| Modbus Pressure Circuit 2 | bar | Read and write | |||
| Digital Output Command Circuit 2 | Read and write | ||||
| Password | Read and write | ||||
| Modbus Address | Read and write | ||||
| Modbus Baud Rate | Read and write | ||||
| Modbus Parity | Read and write | ||||
| Circuit 2 Enabled | Read and write | ||||
| Display Units | Read and write | ||||
| Function Circuit 1 | Read and write | ||||
| Control Mode Circuit 1 | Read and write | ||||
| Refrigerant Circuit 1 | Read and write | ||||
| Pressure Sensor Type Circuit 1 | Read and write | ||||
| Ratiometric Range Circuit 1 | bar | Read and write | |||
| Valve Type Circuit 1 | Read and write | ||||
| Valve Scaling Circuit 1 | % | Read and write | |||
| Start Opening Circuit 1 | % | Read and write | |||
| Start Opening Duration Circuit 1 | s | Read and write | |||
| Low Superheat Alarm Mode Circuit 1 | Read and write | ||||
| Superheat Setpoint Config Circuit 1 | K | Read and write | |||
| MOP Mode Circuit 1 | Read and write | ||||
| MOP Temperature Limit Circuit 1 | °C | Read and write | |||
| Low Pressure Alarm Mode Circuit 1 | Read and write | ||||
| Low Pressure Cut-out Circuit 1 | bar | Read and write | |||
| Low Pressure Alarm Delay Circuit 1 | s | Read and write | |||
| Low Pressure Cut-in Circuit 1 | bar | Read and write | |||
| Freeze Alarm Mode Circuit 1 | Read and write | ||||
| Freeze Alarm Cut-out Circuit 1 | °C | Read and write | |||
| Freeze Alarm Delay Circuit 1 | s | Read and write | |||
| High Superheat Alarm Mode Circuit 1 | Read and write | ||||
| High Superheat Alarm Setpoint Circuit 1 | K | Read and write | |||
| High Superheat Alarm Delay Circuit 1 | min | Read and write | |||
| Temperature Setpoint Circuit 1 | °C | Read and write | |||
| Temperature Band Circuit 1 | K | Read and write | |||
| Temperature Alarm Enable Circuit 1 | Read and write | ||||
| Min Temperature Alarm Setpoint | °C | Read and write | |||
| Min Temperature Alarm Delay | min | Read and write | |||
| Max Temperature Alarm Setpoint | °C | Read and write | |||
| Max Temperature Alarm Delay | min | Read and write | |||
| Temperature Sensor Type Circuit 1 | Read and write | ||||
| PID Kp Circuit 1 | Read and write | ||||
| PID Ti Circuit 1 | s | Read and write | |||
| PID Td Circuit 1 | s | Read and write | |||
| Control Mode Circuit 2 | Read and write | ||||
| Refrigerant Circuit 2 | Read and write | ||||
| Pressure Sensor Type Circuit 2 | Read and write | ||||
| Ratiometric Range Circuit 2 | bar | Read and write | |||
| Valve Type Circuit 2 | Read and write | ||||
| Valve Scaling Circuit 2 | % | Read and write | |||
| Start Opening Circuit 2 | % | Read and write | |||
| Start Opening Duration Circuit 2 | s | Read and write | |||
| Low Superheat Alarm Mode Circuit 2 | Read and write | ||||
| Superheat Setpoint Config Circuit 2 | K | Read and write | |||
| MOP Mode Circuit 2 | Read and write | ||||
| MOP Temperature Limit Circuit 2 | °C | Read and write | |||
| Low Pressure Alarm Mode Circuit 2 | Read and write | ||||
| Low Pressure Cut-out Circuit 2 | bar | Read and write | |||
| Low Pressure Alarm Delay Circuit 2 | s | Read and write | |||
| Low Pressure Cut-in Circuit 2 | bar | Read and write | |||
| Freeze Alarm Mode Circuit 2 | Read and write | ||||
| Freeze Alarm Cut-out Circuit 2 | °C | Read and write | |||
| Freeze Alarm Delay Circuit 2 | s | Read and write | |||
| High Superheat Alarm Mode Circuit 2 | Read and write | ||||
| High Superheat Alarm Setpoint Circuit 2 | K | Read and write | |||
| High Superheat Alarm Delay Circuit 2 | min | Read and write | |||
| Temperature Sensor Type Circuit 2 | Read and write | ||||
| PID Kp Circuit 2 | Read and write | ||||
| PID Ti Circuit 2 | s | Read and write | |||
| PID Td Circuit 2 | s | Read and write | |||
| Circuit 2 Enabled (RAM) | Read and write | ||||
| Display Units (RAM) | Read and write | ||||
| Function Circuit 1 (RAM) | Read and write | ||||
| Control Mode Circuit 1 (RAM) | Read and write | ||||
| Refrigerant Circuit 1 (RAM) | Read and write | ||||
| Pressure Sensor Type Circuit 1 (RAM) | Read and write | ||||
| Ratiometric Range Circuit 1 (RAM) | bar | Read and write | |||
| Valve Type Circuit 1 (RAM) | Read and write | ||||
| Valve Scaling Circuit 1 (RAM) | % | Read and write | |||
| Start Opening Circuit 1 (RAM) | % | Read and write | |||
| Start Opening Duration Circuit 1 (RAM) | s | Read and write | |||
| Low Superheat Alarm Mode Circuit 1 (RAM) | Read and write | ||||
| Superheat Setpoint Config Circuit 1 (RAM) | K | Read and write | |||
| MOP Mode Circuit 1 (RAM) | Read and write | ||||
| MOP Temperature Limit Circuit 1 (RAM) | °C | Read and write | |||
| Low Pressure Alarm Mode Circuit 1 (RAM) | Read and write | ||||
| Low Pressure Cut-out Circuit 1 (RAM) | bar | Read and write | |||
| Low Pressure Alarm Delay Circuit 1 (RAM) | s | Read and write | |||
| Low Pressure Cut-in Circuit 1 (RAM) | bar | Read and write | |||
| Freeze Alarm Mode Circuit 1 (RAM) | Read and write | ||||
| Freeze Alarm Cut-out Circuit 1 (RAM) | °C | Read and write | |||
| Freeze Alarm Delay Circuit 1 (RAM) | s | Read and write | |||
| High Superheat Alarm Mode Circuit 1 (RAM) | Read and write | ||||
| High Superheat Alarm Setpoint Circuit 1 (RAM) | K | Read and write | |||
| High Superheat Alarm Delay Circuit 1 (RAM) | min | Read and write | |||
| Temperature Setpoint Circuit 1 (RAM) | °C | Read and write | |||
| Temperature Band Circuit 1 (RAM) | K | Read and write | |||
| Temperature Alarm Enable Circuit 1 (RAM) | Read and write | ||||
| Min Temperature Alarm Setpoint (RAM) | °C | Read and write | |||
| Min Temperature Alarm Delay (RAM) | min | Read and write | |||
| Max Temperature Alarm Setpoint (RAM) | °C | Read and write | |||
| Max Temperature Alarm Delay (RAM) | min | Read and write | |||
| Temperature Sensor Type Circuit 1 (RAM) | Read and write | ||||
| PID Kp Circuit 1 (RAM) | Read and write | ||||
| PID Ti Circuit 1 (RAM) | s | Read and write | |||
| PID Td Circuit 1 (RAM) | s | Read and write | |||
| Control Mode Circuit 2 (RAM) | Read and write | ||||
| Refrigerant Circuit 2 (RAM) | Read and write | ||||
| Pressure Sensor Type Circuit 2 (RAM) | Read and write | ||||
| Ratiometric Range Circuit 2 (RAM) | bar | Read and write | |||
| Valve Type Circuit 2 (RAM) | Read and write | ||||
| Valve Scaling Circuit 2 (RAM) | % | Read and write | |||
| Start Opening Circuit 2 (RAM) | % | Read and write | |||
| Start Opening Duration Circuit 2 (RAM) | s | Read and write | |||
| Low Superheat Alarm Mode Circuit 2 (RAM) | Read and write | ||||
| Superheat Setpoint Config Circuit 2 (RAM) | K | Read and write | |||
| MOP Mode Circuit 2 (RAM) | Read and write | ||||
| MOP Temperature Limit Circuit 2 (RAM) | °C | Read and write | |||
| Low Pressure Alarm Mode Circuit 2 (RAM) | Read and write | ||||
| Low Pressure Cut-out Circuit 2 (RAM) | bar | Read and write | |||
| Low Pressure Alarm Delay Circuit 2 (RAM) | s | Read and write | |||
| Low Pressure Cut-in Circuit 2 (RAM) | bar | Read and write | |||
| Freeze Alarm Mode Circuit 2 (RAM) | Read and write | ||||
| Freeze Alarm Cut-out Circuit 2 (RAM) | °C | Read and write | |||
| Freeze Alarm Delay Circuit 2 (RAM) | s | Read and write | |||
| High Superheat Alarm Mode Circuit 2 (RAM) | Read and write | ||||
| High Superheat Alarm Setpoint Circuit 2 (RAM) | K | Read and write | |||
| High Superheat Alarm Delay Circuit 2 (RAM) | min | Read and write | |||
| Temperature Sensor Type Circuit 2 (RAM) | Read and write | ||||
| PID Kp Circuit 2 (RAM) | Read and write | ||||
| PID Ti Circuit 2 (RAM) | s | Read and write | |||
| PID Td Circuit 2 (RAM) | s | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show superheat, valve opening and suction pressure of each circuit on a dashboard.
- Get an email when a circuit reports low pressure, freeze or low superheat.
- Alert on the hardware alarm register for sensor, stepper or power failures.
- Compare superheat setpoint and actual superheat over months to spot a drifting valve.
- Change the superheat setpoint remotely in the RAM copy without wearing the flash memory.
Installation
Connect the RS485 terminals of the controller to the RS485 port of the ModbusCloud Gateway, A to A and B to B, with termination at the bus ends.
Set address (Adr), baud rate (br) and parity (PAr) on the controller; the defaults are address 1 and even parity.
In ModbusCloud, add a Modbus device (RTU) with that address, 19200 baud, even parity, 8 data bits and 1 stop bit, then import this template.
Check that superheat and suction pressure show plausible values and that the application state reads Control.
Things to watch for
The controller does not answer. What should I check?
Check address, baud rate and parity on the controller: address 1 to 127, 19200 or 9600 baud, even or no parity. Swap A and B if nothing answers and fit termination at both bus ends. Each controller on the bus needs its own address.
Why are circuit 2 values zero?
Circuit 2 only exists on the EXD-SH2 and only when parameter Circuit 2 Enabled is 1. On an EXD-SH1 the circuit 2 registers carry no data and can be hidden.
Can I write configuration parameters often?
The flash copy of a parameter allows about 1000 writes. For values you change often, write the RAM copy instead; it has no limit but falls back to the flash value after a power failure. Writing from the portal must be enabled for your Gateway.
Why is my refrigerant change refused?
Refrigerant, pressure sensor type, valve type and main function can only be changed while the circuit is in the Off state. Stop the circuit first, write the value and start it again.