DAB DAB Evoplus Modbus RTU template

DAB Evoplus

Electronic circulator pump for heating and cooling circuits, with remote setpoint and pump data.

The DAB Evoplus is an electronic circulator pump that moves water in heating, cooling and domestic hot water circuits in residential and commercial buildings. This Modbus RTU template reads power, head, estimated flow, speed, temperatures and alarms, and lets you switch the pump and set the regulation mode and setpoint from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
55, read and write
Brand
DAB
Key readings
Power · Pump head · Estimated flow · Motor speed · Liquid temperature · Pump status · Alarm history
Available commands
On, off or external · Regulation mode · Regulation setpoint · Economy setpoint reduction · Twin pump mode
Compatible models
Evoplus M/L (B, D) · Evoplus Small (B, D) · Evoplus B · Evoplus D · Evoplus Small
Last updated

Registers (55)

55 read, 17 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Pump PowerWRead
Pump HeadmRead
Estimated Flowm³/hRead
Motor SpeedrpmRead
Output CurrentmARead
Line VoltageVRead
Liquid Temperature°CRead
Liquid Temperature External Sensor°CRead
Electronic Board Temperature°CRead
Heatsink Temperature°CRead
Operating TimehRead
Pump StatusRead
Pump FaultRead
Alarm History 1 (Most Recent)Read
Alarm History 2Read
Alarm History 3Read
Alarm History 4Read
Alarm History 5Read
Alarm History 6Read
Alarm History 7Read
Alarm History 8Read
Alarm History 9Read
Alarm History 10Read
Alarm History 11Read
Alarm History 12Read
Alarm History 13Read
Alarm History 14Read
Alarm History 15 (Oldest)Read
On Off ExtRead and write
Regulation ModeRead and write
Regulation SetpointmRead and write
Regulation Tmax°CRead and write
Auto Economy ModeRead
Economy Setpoint Reduction%Read and write
External Signal TypeRead and write
Twin Pump System ModeRead and write
Max RPM Percent%Read and write
System Reset AlarmRead and write
System Clear HistoryRead and write
Pump Reset BitsRead and write
Minimum Reply DelaymsRead and write
Modbus AddressRead and write
Modbus Baud RateRead and write
Modbus ParityRead and write
Modbus Stop BitsRead and write
Auto Ack Control BitsRead and write
Software Version ARead
Software Version BRead
Software Version CRead
Software Version DRead
Software Version ERead
Software Version FRead
Unit FamilyRead
Unit TypeRead
Unit VersionRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show power, head and estimated flow of every circulator in a building on one dashboard.
  • Get an email alert when Pump Fault is not 0 or a new alarm code appears in the alarm history.
  • Compare operating hours and power over months to plan maintenance of the pumps.
  • Lower the differential pressure setpoint from ModbusCloud during the night or in summer.
  • Check that a twin pump really alternates every 24 hours by watching status and operating time.

Installation

  1. Connect RS485 A (+), B (-) and the screen to terminals 2, 1 and 3 of the 13-pole connector and run the bus to the ModbusCloud Gateway. Terminate both ends of the line.

  2. On the pump display, open the Modbus menu and set the address, baud rate, parity and stop bits. Defaults are address 1, 19200 baud, even parity, 1 stop bit.

  3. Set parameter En to Enable. The Modbus port stays silent until you do.

  4. In ModbusCloud, add a Modbus device with the same address and settings and import the DAB Evoplus template.

  5. Check that Line Voltage reads about 230 V and that Pump Status shows 2 while the pump runs.

Things to watch for

The pump does not answer on the bus. What should I check?

First check that Modbus is enabled on the display (parameter En). Then compare address, baud rate, parity and stop bits with the ModbusCloud device; the pump defaults to 19200 baud with even parity. If the settings match, swap A and B and check the termination at both ends of the line.

Why do some registers show 32767?

The value 32767 (hex 7FFF) means the value is not available, for example the external temperature when no external sensor is connected. It is not a measurement and can be ignored or excluded from alarms.

What does the number in Regulation Mode mean?

The codes differ per software version. Read Software Version A and B first: Evoplus M/L 1.xx and 2.xx use codes 0 to 9, M/L 3.xx and Small 2.xx use 0 to 7, Small 1.xx uses 0 to 5. Look up the code in the DAB Modbus instructions for that version before you write a new mode.

What should I watch out for when writing to the pump?

A new mode or setpoint takes effect immediately and changes the flow in the whole circuit, so agree on values with whoever maintains the installation. Reset registers only act on a change from 0 to 1. On Evoplus Small the communication settings can only be changed on the display, and Power is reported in mW instead of W.