E.G.O. Smart Heater
3.5 kW PV surplus heating element for hot water tanks, 500 W steps, Modbus RTU over RS485.
The E.G.O. Smart Heater is a 3.5 kW screw-in heating element for hot water tanks. It turns PV surplus into heat in 500 W steps by switching three internal relays. This template follows the official E.G.O. register map (protocol release 1.6): tank and sensor temperatures, relay status, power setpoint and grid power inputs, temperature limits, relay timing and counters. Default link: address 247, 19200 baud, 8 data bits, even parity, 1 stop bit. The heater expects a new power value at least every 60 seconds and switches off without it.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 34, read and write
- Brand
- E.G.O.
- Key readings
- Tank water temperature · External sensor 1 and 2 temperature · Relay status (which of the three relays is on) · Rated power per relay · Rotary selector setpoint · Operating hours, switching cycles and error counter · Manufacturer ID for a connection check
- Available commands
- Power setpoint in W (-1 = automatic, 0 = off) · Grid power input for automatic mode · Temperature setpoint, minimum and maximum temperature · Minimum on and off time per relay
- Compatible models
- Smart Heater 29.60335.0xx · Smart Heater 29.65335.0xx · Smart Heater 29.6x335.1xx (LAN)
- Last updated
Registers (34)
34 read, 11 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Boiler Temperature | °C | Read | 5124 | FC03 | int16 |
| Relay Status | Read | 5128 | FC03 | uint16 | |
| Knob Temperature Setpoint | °C | Read | 5127 | FC03 | int16 |
| External Sensor 1 Temperature | °C | Read | 5125 | FC03 | int16 |
| External Sensor 2 Temperature | °C | Read | 5126 | FC03 | int16 |
| PCB Temperature | °C | Read | |||
| Power Setpoint | W | Read and write | |||
| Grid Power | W | Read and write | |||
| Temperature Setpoint | °C | Read and write | |||
| Minimum Temperature | °C | Read and write | |||
| Maximum Temperature | °C | Read and write | |||
| Relay 1 Rated Power | W | Read | |||
| Relay 2 Rated Power | W | Read | |||
| Relay 3 Rated Power | W | Read | |||
| Relay 1 Min On Time | s | Read and write | |||
| Relay 1 Min Off Time | s | Read and write | |||
| Relay 2 Min On Time | s | Read and write | |||
| Relay 2 Min Off Time | s | Read and write | |||
| Relay 3 Min On Time | s | Read and write | |||
| Relay 3 Min Off Time | s | Read and write | |||
| Total Operating Hours | h | Read | |||
| Error Counter | Read | ||||
| Relay 1 Operating Hours | h | Read | |||
| Relay 2 Operating Hours | h | Read | |||
| Relay 3 Operating Hours | h | Read | |||
| Relay 1 Switching Cycles | Read | ||||
| Relay 2 Switching Cycles | Read | ||||
| Relay 3 Switching Cycles | Read | ||||
| Restart Counter | Read | ||||
| Manufacturer ID | Read | ||||
| Product ID | Read | ||||
| Product Variant | Read | ||||
| Firmware Version | Read | ||||
| Relay Count | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Log tank temperature and relay status to see how much PV surplus ends up as hot water.
- Get an alert when the tank stays cold for too long or an external sensor reports a fault.
- Check that an energy manager or evcc really drives the heater: watch the power setpoint and which relays switch.
- Track operating hours and switching cycles per relay for maintenance planning.
Installation
Connect the RS485 terminals A and B of the heater to the RS485 port of your ModbusCloud gateway. Ground the cable shield at one end only.
Turn the rotary selector into the heating range (40 to 80 °C). In OFF or frost protection the heater ignores power commands.
In ModbusCloud, add a Modbus device (RTU) with address 247, 19200 baud, 8 data bits, even parity and 1 stop bit, then import this template.
Check the link: Manufacturer ID must read 5359. If nothing answers, swap A and B.
To control the heater, exactly one master must write Power Setpoint or Grid Power at least every 60 seconds. Without that the heater stays off. ModbusCloud writes registers at most once per minute, so keeping this 60-second window is borderline and not guaranteed.
Things to watch for
The heater does not answer. What should I check?
First the serial settings: 19200 baud, even parity, 1 stop bit, address 247. Many tools default to no parity. Then swap A and B. A steady red LED means the heater has no communication; at first start it can stay red for several minutes until a master polls it. A flashing red LED is a fault that needs a power cycle.
The heater switches off after about a minute.
The heater needs a new value at least every 60 seconds: Power Setpoint in manual mode, Grid Power in automatic mode (Power Setpoint -1). Without it, it switches off. evcc rewrites the setpoint every 30 seconds. This behaviour is reported by evcc and other integrations; the E.G.O. protocol document does not mention it. ModbusCloud writes registers at most once per minute, so keeping this 60-second window is borderline and not guaranteed.
Why does the heater ignore my power setpoint?
The rotary selector must be in the heating range, 40 to 80 °C. The heater also switches in 500 W steps and keeps a minimum on and off time per relay, so the setpoint is met best effort and anything below 500 W means off. While Temperature Setpoint is 0, the rotary selector caps the water temperature.
Where is the actual heating power?
There is no measured power register. Add up the Rated Power of the relays that Relay Status reports as on. With the default 500, 1000 and 2000 W elements that is simply Relay Status times 500 W.
Does it work with evcc?
Yes. evcc has the charger template ego-smartheater (sponsor token required), but it only speaks Modbus TCP. For the RS485 version, run an RTU-to-TCP bridge such as mbusd on the evcc host, for example mbusd -L - -A 127.0.0.1 -p /dev/ttyUSB0 -s 19200 -m 8e1 -P 5020, and point evcc at 127.0.0.1, port 5020, id 247. Modbus TCP has no password, so keep the bridge on 127.0.0.1 and open it to the network only behind a firewall when another host really needs it. An RS485 bus allows only one master, so that host must also go through the bridge.
How do I write a negative Grid Power?
Grid Power is a signed 32-bit value, high word first. Write both registers in one FC 16 request. -500 W is 0xFFFF 0xFE0C; 0xFE0C 0x0000 is a common mistake. Negative means export, so the heater heats.