Exor Energy meter 3-phase

Reads 3-phase energy metering data from Exor meters via Modbus RTU.

This template reads 3-phase energy metering data from Exor energy meters via Modbus RTU. It covers per-phase and total values for voltage, current, active/reactive/apparent power, and dual-tariff energy counters. No control registers are included.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
73, read only
Brand
Exor
Key readings
Voltage L-N and L-L per phase · Current per phase · Active Power per phase and total · Reactive Power per phase and total · Apparent Power per phase and total · Active Energy per phase and total (T1/T2)
Last updated

Registers (73)

73 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Active Energy 1st phase T1kWhRead
Active Energy 2nd phase T1kWhRead
Active Energy 3rd phase T1kWhRead
Active Energy Σ T1kWhRead
Active Energy 1st phase T2kWhRead
Active Energy 2nd phase T2kWhRead
Active Energy 3rd phase T2kWhRead
Active Energy Σ T2kWhRead
Active Energy 1st phase T1, expkWhRead
Active Energy 2nd phase T1, expkWhRead
Active Energy 3rd phase T1, expkWhRead
Active Energy Σ T1, expkWhRead
Active Energy 1st phase T2, expkWhRead
Active Energy 2nd phase T2, expkWhRead
Active Energy 3rd phase T2, expkWhRead
Active Energy Σ T2, expkWhRead
Total Active Energy Σ (T1_T2), impkWhRead
Total Active Energy Σ (T1_T2), expkWhRead
Active Power 1st phasekWRead
Active Power 2nd phasekWRead
Active Power 3rd phasekWRead
Active Power ΣkWRead
Reactive Energy 1st phase T1, impkvarhRead
Reactive Energy 2nd phase T1, impkvarhRead
Reactive Energy 3rd phase T1, impkvarhRead
Reactive Energy Σ T1, impkvarhRead
Reactive Energy 1st phase T2, impkvarhRead
Reactive Energy 2nd phase T2, impkvarhRead
Reactive Energy 3rd phase T2, impkvarhRead
Reactive Energy Σ T2, impkvarhRead
Reactive Energy 1st phase T1, expkvarhRead
Reactive Energy 2nd phase T1, expkvarhRead
Reactive Energy 3rd phase T1, expkvarhRead
Reactive Energy Σ T1, expkvarhRead
Reactive Energy 1st phase T2, expkvarhRead
Reactive Energy 2nd phase T2, expkvarhRead
Reactive Energy 3rd phase T2, expkvarhRead
Reactive Energy Σ T2, expkvarhRead
Reactive Energy Σ T1, capacitivekvarhRead
Reactive Energy Σ T2, capacitivekvarhRead
Reactive Energy Σ T1, inductivekvarhRead
Reactive Energy Σ T2, inductivekvarhRead
Reactive Power 1st phasekvarRead
Reactive Power 2nd phasekvarRead
Reactive Power 3rd phasekvarRead
Reactive Power ΣkvarRead
Apparent Energy Σ T1kVAhRead
Apparent Energy Σ T2kVAhRead
Apparent Power phase1kVARead
Apparent Power phase2kVARead
Apparent Power phase3kVARead
Apparent Power ΣkVARead
L1-N VoltageVRead
L2-N VoltageVRead
L3-N VoltageVRead
L1-L2 VoltageVRead
L2-L3 VoltageVRead
L3-L1 VoltageVRead
Phase1 CurrentARead
Phase2 CurrentARead
Phase3 CurrentARead
Residual currentARead
Power Factor cos φ phase1Read
Power Factor cos φ phase2Read
Power Factor cos φ phase3Read
Power Factor cos φ ΣRead
FrequencyHzRead
Total Harmonic Distortion Voltage phase1%Read
Total Harmonic Distortion Voltage phase2%Read
Total Harmonic Distortion Voltage phase3%Read
Total Harmonic Distortion Current phase1%Read
Total Harmonic Distortion Current phase2%Read
Total Harmonic Distortion Current phase3%Read

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor per-phase voltage and current on a live dashboard to detect load imbalance across phases.
  • Track active energy consumption with dual-tariff counters (T1/T2) for time-of-use billing verification.
  • Create an alert when total apparent power exceeds a defined threshold to prevent breaker trips.
  • Generate monthly energy reports for customers across multiple metered sites from one platform.
  • Compare import and export energy to evaluate the performance of on-site generation systems.

Installation

  1. Wire the RS-485 A and B terminals of the Exor energy meter to the corresponding terminals on the ModbusCloud Gateway.

  2. Set the Modbus slave address on the Exor meter using its front-panel buttons or DIP switches, and note the address for gateway configuration.

  3. Confirm the Exor meter is configured for 19200 baud rate and odd parity (these are the default settings used by this template).

  4. In the ModbusCloud platform, add a new device, select the Exor Energy meter 3-phase template, and enter the correct Modbus slave address.

  5. Verify that voltage and current readings appear on the dashboard and match expected values at the installation site.

Things to watch for

I see zero or missing values for some reactive energy registers. What is wrong?

Some reactive energy and reactive power per-phase registers use uint16 format instead of float32. Ensure your gateway is reading these registers with the correct data type. The template handles this automatically, but manual register additions may need adjustment.

The gateway cannot communicate with the Exor meter. What should I check?

Verify that the RS-485 wiring polarity (A and B) is correct and that a termination resistor is installed if the cable run is long. Confirm the baud rate is set to 19200 and parity is set to odd on both the meter and the gateway.

Can I use this template for a single-phase Exor meter?

This template is designed for 3-phase Exor meters. Using it with a single-phase model may result in empty or invalid readings on L2 and L3 registers. Use a single-phase specific template if available.

What are the T1 and T2 tariff counters?

T1 and T2 represent two separate energy tariff registers, typically used for peak and off-peak billing periods. The Exor meter increments the appropriate counter based on a tariff switching input or schedule configured on the meter.

Want to see how it works?