Helios KWL EC easyControls 3.0

Heat recovery ventilation controller that reports air temperatures, humidity and CO2 and sets profiles.

The Helios KWL EC easyControls 3.0 is the controller of Helios heat recovery ventilation units that runs the fans, bypass and ventilation profiles in homes and small buildings. This Modbus RTU template reads fan speed, air temperatures, humidity, CO2 and fault state, and lets you set the profile, boost timer, fan speeds and supply air temperature from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
68, read and write
Brand
Helios
Key readings
Fan speed · Extract air temperature · Exhaust air temperature · Outdoor air temperature · Supply air temperature · Relative humidity · CO2 concentration · Device fault
Available commands
Home or away profile · Unit on or off · Boost timer · Fan speed per profile · Supply air temperature per profile · Bypass mode
Compatible models
KWL EC easyControls 3.0 · Helios KWL heat recovery ventilation units with the easyControls 3.0 controller (Modbus RTU)
Last updated

Registers (68)

68 read, 36 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Fan Speed%Read
Extract Air TemperatureKRead
Exhaust Air TemperatureKRead
Outdoor Air TemperatureKRead
Supply Air TemperatureKRead
Optional TemperatureKRead
Relative Humidity%RHRead
CO2 ConcentrationppmRead
Internal Sensor Temperature RawRead
Internal Sensor Humidity RawRead
RH Sensor 0%RHRead
RH Sensor 1%RHRead
RH Sensor 2%RHRead
RH Sensor 3%RHRead
RH Sensor 4%RHRead
RH Sensor 5%RHRead
CO2 Sensor 0ppmRead
CO2 Sensor 1ppmRead
CO2 Sensor 2ppmRead
CO2 Sensor 3ppmRead
CO2 Sensor 4ppmRead
CO2 Sensor 5ppmRead
Heat Exchanger StateRead
Device Fault ActiveRead
Ventilation ProfileRead and write
Unit On OffRead and write
Boost Timer RemainingminRead and write
Custom Timer RemainingminRead and write
Weekly Timer EnabledRead and write
Boost Timer EnabledRead and write
Custom Timer EnabledRead and write
Input Timer EnabledRead and write
Home Fan Speed Setting%Read and write
Home Supply Air Temperature SettingKRead and write
Home RH ControlRead and write
Home CO2 ControlRead and write
Away Fan Speed Setting%Read and write
Away Supply Air Temperature SettingKRead and write
Away RH ControlRead and write
Away CO2 ControlRead and write
Boost Fan Speed Setting%Read and write
Boost Supply Air Temperature SettingKRead and write
Boost RH ControlRead and write
Boost CO2 ControlRead and write
Custom Extract Fan Speed%Read and write
Custom Supply Fan Speed%Read and write
Boost DurationminRead and write
Custom DurationminRead and write
RH Basic Level%Read and write
RH Level ModeRead and write
CO2 ThresholdppmRead and write
Partial BypassRead and write
Filter Change IntervaldRead
Filter Changed DaydRead and write
Filter Changed MonthRead and write
Filter Changed YearRead and write
Clock MinuteminRead and write
Clock HourhRead and write
Date DayRead and write
Date MonthRead and write
Date YearRead and write
WeekdayRead
IP Address HighRead
IP Address LowRead
Subnet Mask HighRead
Subnet Mask LowRead
Gateway Address HighRead
Gateway Address LowRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show fan speed, supply and extract air temperature and CO2 of a Helios unit on one ModbusCloud dashboard.
  • Get an email when Device Fault Active turns on or humidity rises above a threshold you set.
  • Track outdoor, supply and exhaust air temperature in the 365-day history to see how well heat is recovered.
  • Switch a unit between the home and away profile remotely from the portal.
  • Start boost ventilation for 30 minutes after a meeting or event by writing the boost timer.
  • Check the filter change date and bypass state before a maintenance visit.

Installation

  1. Check the Modbus settings of the unit on the KWL-BE Touch panel or in the web server: address 1, 19200 baud, even parity by default.

  2. Connect RS485 A and B of the unit controller to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.

  3. In ModbusCloud, add a Modbus device with the same address, speed and parity, and import this template.

  4. Check that Fan Speed and Outdoor Air Temperature show plausible values; subtract 273.15 from the kelvin value for degrees Celsius.

Things to watch for

The unit does not answer. What should I check?

Compare address, baud rate and parity with the Modbus settings on the KWL-BE Touch panel or in the web server; the default is address 1, 19200 baud, even parity, 1 stop bit. Swap A and B and add a termination resistor at both ends of the bus.

Why do temperatures show around 290?

The unit sends temperatures in centikelvin. The template shows them in kelvin, so 293.15 means 20 °C. Subtract 273.15 for degrees Celsius. A value of 0 or 65535 on a sensor register means no sensor is connected.

Can my older KWL EC unit with Modbus TCP use this template?

No. Units with easyControls 2.x use a different Modbus TCP protocol in which values are requested by variable name. This template is for units with easyControls 3.0 and the RS485 Modbus RTU interface.

How do I change the ventilation through Modbus?

Write 0 or 1 to Ventilation Profile for home or away, or minutes to Boost Timer Remaining to start boost. Fan speed and supply temperature are set per profile. Writing registers is off per Gateway until it is enabled on request; write only values you understand.

Can several units share one bus?

Yes, give each unit its own Modbus address on the panel or in the web server, and add each one as a separate Modbus device in ModbusCloud with this template.