Hitachi Hitachi Yutaki ATW-MBS-02 Modbus RTU template

Hitachi Yutaki ATW-MBS-02

Monitors and controls Hitachi Yutaki air-to-water heat pumps, heating circuits, hot water and pool.

The Hitachi ATW-MBS-02 is a Modbus gateway that links a Yutaki air-to-water heat pump to a building system over RS485 or Ethernet. This Modbus RTU template reads temperatures, water flow, compressor data, operating state and alarms, and lets you switch the unit and change heating, hot water and pool setpoints from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
115, read and write
Brand
Hitachi
Key readings
Outdoor temperature · Water inlet and outlet temperature · Hot water temperature · Water flow · Compressor frequency and current · Operation state · Alarm number
Available commands
Unit run and mode · Circuit run and water setpoints · Room thermostat setpoint · Hot water setpoint and boost · Pool setpoint · Anti legionella
Compatible models
ATW-MBS-02 (7E549924) with YUTAKI S · ATW-MBS-02 with YUTAKI S COMBI · ATW-MBS-02 with YUTAKI S80 · ATW-MBS-02 with YUTAKI M · Hitachi YUTAKI S, S COMBI, S80 and M, line-up 2016 and later
Last updated

Registers (115)

115 read, 34 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Outdoor Ambient Temperature°CRead
Water Inlet Temperature°CRead
Water Outlet Temperature°CRead
Heat Pump Water Outlet Temperature°CRead
DHW Temperature°CRead
Pool Temperature°CRead
Water Temperature Setpoint°CRead
Water Flowm³/hRead
Water Pump Speed%Read
Compressor FrequencyHzRead
Compressor CurrentARead
Unit Power ConsumptionkWhRead
Unit CapacitykWhRead
Outdoor Average Temperature°CRead
Second Ambient Temperature°CRead
Second Ambient Average Temperature°CRead
Water Outlet Temperature 2°CRead
Water Outlet Temperature 3°CRead
Gas Temperature°CRead
Liquid Temperature°CRead
Discharge Gas Temperature°CRead
Evaporation Temperature°CRead
Indoor Expansion Valve Opening%Read
Outdoor Expansion Valve Opening%Read
Mixing Valve PositionRead
Capacity DataRead
R134a Discharge Temperature°CRead
R134a Suction Temperature°CRead
R134a Discharge PressureMPaRead
R134a Suction PressureMPaRead
R134a Compressor FrequencyHzRead
R134a Expansion Valve 2 Opening%Read
R134a Compressor CurrentARead
Operation StateRead
Alarm NumberRead
H-LINK Communication StateRead
System Status 2Read
System ConfigurationRead
Cause Of StoppageRead
DefrostingRead
R134a Retry CodeRead
Central ModeRead
Unit Run StatusRead
Unit Mode StatusRead
Unit Run CommandRead and write
Unit Mode CommandRead and write
Circuit 1 Run CommandRead and write
Circuit 1 Heating OTC CommandRead and write
Circuit 1 Cooling OTC CommandRead and write
Circuit 1 Heating Water Fix Setpoint°CRead and write
Circuit 1 Cooling Water Fix Setpoint°CRead and write
Circuit 1 Eco Mode CommandRead and write
Circuit 1 Heat ECO OffsetRead and write
Circuit 1 Cool ECO OffsetRead and write
Circuit 1 Modbus Thermostat EnableRead and write
Circuit 1 Thermostat Setpoint°CRead and write
Circuit 1 Room Temperature Input°CRead and write
Circuit 2 Run CommandRead and write
Circuit 2 Heating OTC CommandRead and write
Circuit 2 Cooling OTC CommandRead and write
Circuit 2 Heating Water Fix Setpoint°CRead and write
Circuit 2 Cooling Water Fix Setpoint°CRead and write
Circuit 2 Eco Mode CommandRead and write
Circuit 2 Heat ECO OffsetRead and write
Circuit 2 Cool ECO OffsetRead and write
Circuit 2 Modbus Thermostat EnableRead and write
Circuit 2 Thermostat Setpoint°CRead and write
Circuit 2 Room Temperature Input°CRead and write
DHW Run CommandRead and write
DHW Setpoint°CRead and write
DHW Boost RequestRead and write
DHW Demand Mode CommandRead and write
Pool Run CommandRead and write
Pool Setpoint°CRead and write
Anti Legionella Run CommandRead and write
Anti Legionella Setpoint°CRead and write
Block Menu 6 CommandRead and write
BMS Alarm CommandRead and write
Circuit 1 Run StatusRead
Circuit 1 Heating OTC StatusRead
Circuit 1 Cooling OTC StatusRead
Circuit 1 Heating Water Fix Setpoint Status°CRead
Circuit 1 Cooling Water Fix Setpoint Status°CRead
Circuit 1 Eco Mode StatusRead
Circuit 1 Heat ECO Offset StatusRead
Circuit 1 Cool ECO Offset StatusRead
Circuit 1 Thermostat Setpoint Status°CRead
Circuit 1 Room Temperature°CRead
Circuit 1 Wireless Setpoint°CRead
Circuit 1 Wireless Room Temperature°CRead
Circuit 2 Run StatusRead
Circuit 2 Heating OTC StatusRead
Circuit 2 Cooling OTC StatusRead
Circuit 2 Heating Water Fix Setpoint Status°CRead
Circuit 2 Cooling Water Fix Setpoint Status°CRead
Circuit 2 Eco Mode StatusRead
Circuit 2 Heat ECO Offset StatusRead
Circuit 2 Cool ECO Offset StatusRead
Circuit 2 Thermostat Setpoint Status°CRead
Circuit 2 Room Temperature°CRead
Circuit 2 Wireless Setpoint°CRead
Circuit 2 Wireless Room Temperature°CRead
DHW Run StatusRead
DHW Setpoint Status°CRead
DHW Boost StatusRead
DHW Demand Mode StatusRead
Pool Run StatusRead
Pool Setpoint Status°CRead
Anti Legionella Run StatusRead
Anti Legionella Setpoint Status°CRead
Block Menu 6 StatusRead
BMS Alarm StatusRead
Unit ModelRead
Software PCBRead
Software LCDRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show outdoor, flow and return temperatures of each heat pump on a ModbusCloud dashboard.
  • Send an email when the alarm number is not 0 so you can see a fault before the customer calls.
  • Compare water inlet and outlet temperature with water flow in the history to check the heat output.
  • Raise or lower the hot water setpoint or start a boost remotely from ModbusCloud.
  • Track compressor frequency and current over a season to spot short cycling.
  • Get an alert when the H-LINK communication state reports no connection with the unit.

Installation

  1. Wire the ATW-MBS-02 to the H-LINK terminals of the Yutaki and give it 230 V power.

  2. Connect RS485 + and - of the gateway to B and A on the ModbusCloud Gateway and set SW1-1 for termination at the end of the bus.

  3. Check address, speed and parity with the Net configuration tool; default is ID 1, 19200 baud, even parity.

  4. In ModbusCloud, add a Modbus device with these settings and import this template.

  5. Check that outdoor temperature and operation state come in, and set central operation to Full on the Yutaki controller before writing.

Things to watch for

The gateway does not answer on RS485. What should I check?

Check ID, speed and parity: 1, 19200 baud and even parity by default. Swap + and - if nothing answers, and check that termination is only on at the ends of the bus. The gateway must be powered before the Yutaki is configured, otherwise it does not see the unit.

All values read 65535 or the H-LINK state says no communication.

The gateway answers but has no data from the heat pump. Check the H-LINK wiring to the Yutaki and that no other Hitachi gateway or central controller is on the same H-LINK. After a power cycle the state shows data initialization for a few minutes.

My writes are accepted but the heat pump changes them back.

Set central operation to Full in the system configuration of the Yutaki controller; in Local mode the controller overrules setpoints and run commands. Write the command registers and read the status registers to see what the unit actually uses.

Why do the registers not match my older Yutaki?

Units from before the 2016 line-up use a different register map on the same gateway. This template covers the 2016 line-up of Yutaki S, S Combi, S80 and M.

Want to see how it works?