Innova Innova AirLeaf Modbus RTU template

Innova AirLeaf

DC inverter fancoil: air and water temperature, fan speed, alarms, setpoint and season.

The Innova AirLeaf is a DC inverter fancoil that heats and cools rooms in homes, offices and hotels with water from a heat pump, boiler or chiller. This Modbus RTU template reads air and water temperatures, fan speed and alarms, and lets you write the setpoint, season mode and program from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
33, read and write
Brand
Innova
Key readings
Air temperature · Hot water temperature · Actual setpoint · Fan motor speed · Alarm flags
Available commands
Setpoint · Season mode · Program and standby · Setpoint limits · Keypad lock
Compatible models
AirLeaf with ECA644 or ECA647 control (INN-FR-B32 board) · AirLeaf with EDA649 or EDB649 wall control (ESE645)
Last updated

Registers (33)

33 read, 25 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Air Temperature°CRead0FC03int16
Hot Water Temperature°CRead1FC03int16
Cold Water Temperature°CRead2FC03int16
Actual Setpoint°CRead8FC03int16
Output StatusRead9FC03uint16
Fan Motor SpeedRead
Status FlagsRead
Alarm FlagsRead
Device AddressRead and write
Operating Mode FlagsRead and write
Minimum Setpoint°CRead and write
Maximum Setpoint°CRead and write
Energy Saving OffsetKRead and write
Fan Speed Night MinRead and write
Fan Speed Night MaxRead and write
Fan Speed Min MaxRead and write
Fan Speed Min Max PerformanceRead and write
Fan Speed Auto MaxRead and write
Fan Speed Auto Max PerformanceRead and write
Fan Speed MaxRead and write
Fan Speed Max PerformanceRead and write
Heating Min Water Temperature°CRead and write
Cooling Max Water Temperature°CRead and write
Maintenance IntervalhRead and write
Fan Operating HourshRead and write
Setpoint°CRead and write
Season ModeRead and write
Air Probe OffsetKRead and write
H2 Probe OffsetKRead and write
H4 Probe OffsetKRead and write
Web Minimum Setpoint°CRead and write
Web Maximum Setpoint°CRead and write
Web FlagsRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show the air temperature and setpoint of every fancoil in a building on one dashboard.
  • Get an email when the alarm flags show a motor fault, a probe fault or a dirty filter.
  • Switch all fancoils between heating and cooling with one automation when the season changes.
  • Lower setpoints in empty rooms or at night with an automation on a schedule.
  • Lock the keypad or limit the setpoint range in hotel rooms and offices.

Installation

  1. Connect the +AB- terminals of the INN-FR-B32 board, or the serial port of the EDA649 or EDB649 wall control, to the RS485 A and B terminals of the ModbusCloud Gateway with shielded cable, and terminate with 120 Ohm.

  2. Give each fancoil its own address from 2 to 255: in standby hold AUTO for 5 seconds and set the address with the arrow keys.

  3. In ModbusCloud, add a Modbus device (RTU) with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit, and import this template.

  4. Check that the air temperature and setpoint match the control panel.

Things to watch for

The fancoil does not answer. What should I check?

The serial settings are fixed at 9600 baud, 8 data bits, no parity and 1 stop bit. Check the address on the keypad, swap A and B if nothing comes back, and terminate the bus with 120 Ohm at the end. Star wiring is not allowed.

Why do some values read 0?

Water temperatures, outputs, fan speed and some settings are only available with the INN-FR-B32 board of the ECA644 and ECA647. The cold water probe H4 exists only on the 4-pipe ECA647.

Can several fancoils share one RS485 line?

Yes, up to 50 per line and 500 m in total. Give each fancoil its own address and keep address 1 free for replacements, as Innova advises. Wire the bus as one line from unit to unit.

What should I keep in mind when I write a setting?

Write the setpoint in register 231 within SPL and SPH. In the program register only change bits 0 to 2, 4 and 7; bits 8 to 15 are system flags. The web flags block keys on the panel, so the user sees a flashing icon when a key is disabled.

Want to see how it works?

Electrician working in an open distribution board