
Innova AirLeaf
DC inverter fancoil: air and water temperature, fan speed, alarms, setpoint and season.
The Innova AirLeaf is a DC inverter fancoil that heats and cools rooms in homes, offices and hotels with water from a heat pump, boiler or chiller. This Modbus RTU template reads air and water temperatures, fan speed and alarms, and lets you write the setpoint, season mode and program from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 33, read and write
- Brand
- Innova
- Key readings
- Air temperature · Hot water temperature · Actual setpoint · Fan motor speed · Alarm flags
- Available commands
- Setpoint · Season mode · Program and standby · Setpoint limits · Keypad lock
- Compatible models
- AirLeaf with ECA644 or ECA647 control (INN-FR-B32 board) · AirLeaf with EDA649 or EDB649 wall control (ESE645)
- Last updated
Registers (33)
33 read, 25 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Air Temperature | °C | Read | 0 | FC03 | int16 |
| Hot Water Temperature | °C | Read | 1 | FC03 | int16 |
| Cold Water Temperature | °C | Read | 2 | FC03 | int16 |
| Actual Setpoint | °C | Read | 8 | FC03 | int16 |
| Output Status | Read | 9 | FC03 | uint16 | |
| Fan Motor Speed | Read | ||||
| Status Flags | Read | ||||
| Alarm Flags | Read | ||||
| Device Address | Read and write | ||||
| Operating Mode Flags | Read and write | ||||
| Minimum Setpoint | °C | Read and write | |||
| Maximum Setpoint | °C | Read and write | |||
| Energy Saving Offset | K | Read and write | |||
| Fan Speed Night Min | Read and write | ||||
| Fan Speed Night Max | Read and write | ||||
| Fan Speed Min Max | Read and write | ||||
| Fan Speed Min Max Performance | Read and write | ||||
| Fan Speed Auto Max | Read and write | ||||
| Fan Speed Auto Max Performance | Read and write | ||||
| Fan Speed Max | Read and write | ||||
| Fan Speed Max Performance | Read and write | ||||
| Heating Min Water Temperature | °C | Read and write | |||
| Cooling Max Water Temperature | °C | Read and write | |||
| Maintenance Interval | h | Read and write | |||
| Fan Operating Hours | h | Read and write | |||
| Setpoint | °C | Read and write | |||
| Season Mode | Read and write | ||||
| Air Probe Offset | K | Read and write | |||
| H2 Probe Offset | K | Read and write | |||
| H4 Probe Offset | K | Read and write | |||
| Web Minimum Setpoint | °C | Read and write | |||
| Web Maximum Setpoint | °C | Read and write | |||
| Web Flags | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show the air temperature and setpoint of every fancoil in a building on one dashboard.
- Get an email when the alarm flags show a motor fault, a probe fault or a dirty filter.
- Switch all fancoils between heating and cooling with one automation when the season changes.
- Lower setpoints in empty rooms or at night with an automation on a schedule.
- Lock the keypad or limit the setpoint range in hotel rooms and offices.
Installation
Connect the +AB- terminals of the INN-FR-B32 board, or the serial port of the EDA649 or EDB649 wall control, to the RS485 A and B terminals of the ModbusCloud Gateway with shielded cable, and terminate with 120 Ohm.
Give each fancoil its own address from 2 to 255: in standby hold AUTO for 5 seconds and set the address with the arrow keys.
In ModbusCloud, add a Modbus device (RTU) with the same address, 9600 baud, 8 data bits, no parity and 1 stop bit, and import this template.
Check that the air temperature and setpoint match the control panel.
Things to watch for
The fancoil does not answer. What should I check?
The serial settings are fixed at 9600 baud, 8 data bits, no parity and 1 stop bit. Check the address on the keypad, swap A and B if nothing comes back, and terminate the bus with 120 Ohm at the end. Star wiring is not allowed.
Why do some values read 0?
Water temperatures, outputs, fan speed and some settings are only available with the INN-FR-B32 board of the ECA644 and ECA647. The cold water probe H4 exists only on the 4-pipe ECA647.
Can several fancoils share one RS485 line?
Yes, up to 50 per line and 500 m in total. Give each fancoil its own address and keep address 1 free for replacements, as Innova advises. Wire the bus as one line from unit to unit.
What should I keep in mind when I write a setting?
Write the setpoint in register 231 within SPL and SPH. In the program register only change bits 0 to 2, 4 and 7; bits 8 to 15 are system flags. The web flags block keys on the panel, so the user sees a flashing icon when a key is disabled.
Want to see how it works?












