INVT GD20

Frequency inverter that reports frequency, current, voltage and faults, with run and speed control.

The INVT GD20 is a compact frequency inverter that controls the speed of pumps, fans and conveyors in buildings and light industry. This Modbus RTU template reads frequency, current, voltage, power, status and fault code, and lets you start, stop and set the speed from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
41, read and write
Brand
INVT
Key readings
Output frequency · Output current · Output voltage · Bus voltage · Output power · Motor speed · Fault code
Available commands
Run and stop command · Frequency setpoint · PID reference · Torque setpoint · Frequency and torque limits
Compatible models
Goodrive20 (GD20)
Last updated

Registers (41)

41 read, 15 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Operating FrequencyHzRead12288FC03uint16
Set FrequencyHzRead12289FC03uint16
Output CurrentARead12292FC03uint16
Output VoltageVRead12291FC03uint16
Bus VoltageVRead12290FC03uint16
Output Power%Read
Output Torque%Read
Operation SpeedrpmRead
PID Setting%Read
PID Feedback%Read
Torque Setting%Read
AI1 VoltageVRead
AI2 VoltageVRead
AI3 VoltageVRead
Pulse Input FrequencyRead
Input StateRead
Output StateRead
Multi-Step Speed StepRead
External LengthRead
External CountRead
Status Word 1Read
Status Word 2Read
Fault CodeRead
Fault Code 5000HRead
Device IdentificationRead
VFD Identification CodeRead
Control CommandRead and write
Communication Frequency SetpointHzRead and write
PID Reference%Read and write
PID Feedback Value%Read and write
Torque Setpoint%Read and write
Forward Upper Frequency LimitHzRead and write
Reverse Upper Frequency LimitHzRead and write
Motoring Torque Limit%Read and write
Braking Torque Limit%Read and write
Special Control WordRead and write
Virtual Input CommandRead and write
Virtual Output CommandRead and write
VF Separation Voltage Setpoint%Read and write
AO1 Output Setting%Read and write
AO2 Output Setting%Read and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show frequency, current and power of every drive in a pump or fan installation on one dashboard.
  • Get an email alert when the fault code is not 0 or the status word reports a fault.
  • Keep a year of current and power history to see how a pump load changes over the seasons.
  • Change the frequency setpoint from ModbusCloud to adjust a fan without visiting the site.
  • Track the PID setpoint and feedback to check that a pressure or flow loop holds its target.

Installation

  1. Connect RS485 A and B of the ModbusCloud Gateway to the 485 plus and minus terminals of the drive and fit the termination jumper at the end of the bus.

  2. Set P14.00 (address), P14.01 (baud rate) and P14.02 (data format) on the keypad; the defaults are address 1, 19200 baud, 8E1.

  3. In ModbusCloud, add a Modbus RTU device with the same address and settings, and import this template.

  4. Check that Operating Frequency, Bus Voltage and Status Word 1 come in; start the motor to see frequency and current change.

  5. To control the drive over Modbus, set P00.01 to 2 and select Modbus as the frequency source before writing commands.

Things to watch for

The drive does not answer on the bus. What should I check?

Check P14.00 to P14.02 against the device settings in ModbusCloud: address, baud rate and parity must match, the default is 19200 baud 8E1. Swap plus and minus if nothing answers, and fit the termination jumper on the drive at the end of the bus.

Writing the run command or frequency has no effect. Why?

The drive only accepts commands from Modbus when P00.01 is set to 2 (communication run command channel) and the frequency source is set to Modbus. For the PID reference, P09.00 must also select Modbus.

What should I know before writing to the drive?

A run command starts the motor directly, so make sure the machine is safe to run. Write one command at a time and read Status Word 1 to confirm the result. The frequency setpoint is in 0.01 Hz steps and stays within the frequency limits set in P00.

A write is refused with an error code. What does it mean?

Code 07H means the parameter is read-only, 08H that it cannot be changed while the drive runs, and 09H that a user password locks the drive. Stop the drive or enter the password first. Code 04H means the value is not allowed, for example a terminal function that is already in use.

Want to see how it works?

Electrician working in an open distribution board