Legrand EMDX3 412052
Three-phase panel measuring unit for voltage, current, power, energy and harmonics.
The Legrand EMDX3 412052 is a three-phase multifunction measuring unit that measures voltage, current, power, energy and harmonics in a switchboard door. This Modbus RTU template reads all measured values and counters and lets you set transformer ratios, alarm output settings and counter resets from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 439, read and write
- Brand
- Legrand
- Key readings
- Voltage per phase · Current per phase · Active power · Power factor · Frequency · Active energy · Harmonic distortion
- Available commands
- CT ratio · VT ratio · Output alarm setpoint · Reset of counters and peaks
- Compatible models
- EMDX3 multifunction measuring unit 4 120 52
- Last updated
Registers (439)
438 read, 29 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Voltage L1 | V | Read | |||
| Voltage L2 | V | Read | |||
| Voltage L3 | V | Read | |||
| Current L1 | A | Read | |||
| Current L2 | A | Read | |||
| Current L3 | A | Read | |||
| Neutral Current | A | Read | |||
| Line Voltage L1-L2 | V | Read | |||
| Line Voltage L2-L3 | V | Read | |||
| Line Voltage L3-L1 | V | Read | |||
| 3-Phase Active Power | W | Read | |||
| 3-Phase Reactive Power | var | Read | |||
| 3-Phase Apparent Power | VA | Read | |||
| 3-Phase Sign of Active Power | Read | ||||
| 3-Phase Sign of Reactive Power | Read | ||||
| 3-Phase Positive Active Energy | Read | ||||
| 3-Phase Positive Reactive Energy | Read | ||||
| 3-Phase Negative Active Energy | Read | ||||
| 3-Phase Negative Reactive Energy | Read | ||||
| 3-Phase Power Factor | Read | ||||
| 3-Phase Sector of Power Factor | Read | ||||
| Frequency | Hz | Read | |||
| Signed Total Active Power | W | Read | |||
| Signed Total Reactive Power | var | Read | |||
| Signed L1 Active Power | W | Read | |||
| Signed L2 Active Power | W | Read | |||
| Signed L3 Active Power | W | Read | |||
| Signed L1 Reactive Power | var | Read | |||
| Signed L2 Reactive Power | var | Read | |||
| Signed L3 Reactive Power | var | Read | |||
| Signed Total Power Factor | Read | ||||
| Signed L1 Power Factor | Read | ||||
| Signed L2 Power Factor | Read | ||||
| Signed L3 Power Factor | Read | ||||
| Low Positive Active Energy | Wh | Read | |||
| High Positive Active Energy | MWh | Read | |||
| Low Positive Reactive Energy | varh | Read | |||
| High Positive Reactive Energy | kvarh | Read | |||
| Low Negative Active Energy | Wh | Read | |||
| High Negative Active Energy | MWh | Read | |||
| Low Negative Reactive Energy | varh | Read | |||
| High Negative Reactive Energy | kvarh | Read | |||
| Low Partial Active Energy | Wh | Read | |||
| High Partial Active Energy | MWh | Read | |||
| Low Partial Reactive Energy | varh | Read | |||
| High Partial Reactive Energy | kvarh | Read | |||
| 3-Phase Average Power | W | Read | |||
| 3-Phase Peak Maximum Demand | W | Read | |||
| Time Counter for Average Power | min | Read | |||
| L1 Active Power | W | Read | |||
| L2 Active Power | W | Read | |||
| L3 Active Power | W | Read | |||
| L1 Sign of Active Power | Read | ||||
| L2 Sign of Active Power | Read | ||||
| L3 Sign of Active Power | Read | ||||
| L1 Reactive Power | var | Read | |||
| L2 Reactive Power | var | Read | |||
| L3 Reactive Power | var | Read | |||
| L1 Sign of Reactive Power | Read | ||||
| L2 Sign of Reactive Power | Read | ||||
| L3 Sign of Reactive Power | Read | ||||
| L1 Apparent Power | VA | Read | |||
| L2 Apparent Power | VA | Read | |||
| L3 Apparent Power | VA | Read | |||
| L1 Power Factor | Read | ||||
| L2 Power Factor | Read | ||||
| L3 Power Factor | Read | ||||
| L1 Sector of Power Factor | Read | ||||
| L2 Sector of Power Factor | Read | ||||
| L3 Sector of Power Factor | Read | ||||
| THD Voltage L1 | % | Read | |||
| THD Voltage L2 | % | Read | |||
| THD Voltage L3 | % | Read | |||
| THD Current L1 | % | Read | |||
| THD Current L2 | % | Read | |||
| THD Current L3 | % | Read | |||
| Current L1 Average | A | Read | |||
| Current L2 Average | A | Read | |||
| Current L3 Average | A | Read | |||
| Current L1 Peak Max | A | Read | |||
| Current L2 Peak Max | A | Read | |||
| Current L3 Peak Max | A | Read | |||
| Current Average 3-Phase | A | Read | |||
| Voltage L1 Min | V | Read | |||
| Voltage L2 Min | V | Read | |||
| Voltage L3 Min | V | Read | |||
| Voltage L1 Max | V | Read | |||
| Voltage L2 Max | V | Read | |||
| Voltage L3 Max | V | Read | |||
| 3-Phase Partial Active Energy | Read | ||||
| 3-Phase Partial Reactive Energy | Read | ||||
| Operating Timer Counter | h | Read | |||
| Alarm Status and Output Remote Command | Read and write | ||||
| 3-Phase Average Active Power | W | Read | |||
| 3-Phase Average Reactive Power | var | Read | |||
| 3-Phase Average Apparent Power | VA | Read | |||
| 3-Phase Active PMD Power | W | Read | |||
| 3-Phase Reactive PMD Power | var | Read | |||
| 3-Phase Apparent PMD Power | VA | Read | |||
| Total Apparent Power Fixed | VA | Read | |||
| 3-Phase Average Active Power Scaled | W | Read | |||
| 3-Phase Average Reactive Power Scaled | var | Read | |||
| 3-Phase Average Apparent Power Scaled | VA | Read | |||
| 3-Phase Max Active Power Scaled | W | Read | |||
| 3-Phase Max Reactive Power Scaled | var | Read | |||
| 3-Phase Max Apparent Power Scaled | VA | Read | |||
| Device Identifier | Read | ||||
| Current Transformer Ratio (CT) | Read | ||||
| Voltage Transformer Ratio (VT) | Read | ||||
| Device Identifier Settings | Read | ||||
| Voltages Sequence Diagnostic | Read | ||||
| CT Ratio Setting | Read and write | ||||
| VT Ratio Setting | Read and write | ||||
| Custom Page Line 1 Measure | Read and write | ||||
| Custom Page Line 2 Measure | Read and write | ||||
| Custom Page Line 3 Measure | Read and write | ||||
| Insertion Type | Read and write | ||||
| Demand Calculation Time | Read and write | ||||
| Display Contrast | Read and write | ||||
| Backlight Intensity | Read and write | ||||
| Rated CT Secondary Current | Read and write | ||||
| Run Hour Meter Start | Read and write | ||||
| Output Measure Type | Read and write | ||||
| Output Alarm Setpoint Sign | Read and write | ||||
| Output Alarm Setpoint Unit | Read and write | ||||
| Output Alarm Setpoint | Read and write | ||||
| Output Alarm on Min or Max | Read and write | ||||
| Output Relay Contact | Read and write | ||||
| Output Alarm Hysteresis | % | Read and write | |||
| Output Alarm Activation Delay | s | Read and write | |||
| Output Deactivation Delay or Closing Time | s | Read and write | |||
| Pulse Output Energy | Read and write | ||||
| Pulse Weight | Read and write | ||||
| Pulse Duration | Read and write | ||||
| Output Type | Read and write | ||||
| Reset Measurements | Write | ||||
| Save Configuration | Read and write | ||||
| Enable Remote Writing | Read and write | ||||
| Restore Default Parameters | Read and write | ||||
| Current L1 Fundamental | % | Read | |||
| Current L1 Harmonic 2 Percent | % | Read | |||
| Current L1 Harmonic 3 Percent | % | Read | |||
| Current L1 Harmonic 4 Percent | % | Read | |||
| Current L1 Harmonic 5 Percent | % | Read | |||
| Current L1 Harmonic 6 Percent | % | Read | |||
| Current L1 Harmonic 7 Percent | % | Read | |||
| Current L1 Harmonic 8 Percent | % | Read | |||
| Current L1 Harmonic 9 Percent | % | Read | |||
| Current L1 Harmonic 10 Percent | % | Read | |||
| Current L1 Harmonic 11 Percent | % | Read | |||
| Current L1 Harmonic 12 Percent | % | Read | |||
| Current L1 Harmonic 13 Percent | % | Read | |||
| Current L1 Harmonic 14 Percent | % | Read | |||
| Current L1 Harmonic 15 Percent | % | Read | |||
| Current L1 Harmonic 16 Percent | % | Read | |||
| Current L1 Harmonic 17 Percent | % | Read | |||
| Current L1 Harmonic 18 Percent | % | Read | |||
| Current L1 Harmonic 19 Percent | % | Read | |||
| Current L1 Harmonic 20 Percent | % | Read | |||
| Current L1 Harmonic 21 Percent | % | Read | |||
| Current L1 Harmonic 22 Percent | % | Read | |||
| Current L1 Harmonic 23 Percent | % | Read | |||
| Current L1 Harmonic 24 Percent | % | Read | |||
| Current L1 Harmonic 25 Percent | % | Read | |||
| Current L2 Fundamental | % | Read | |||
| Current L2 Harmonic 2 Percent | % | Read | |||
| Current L2 Harmonic 3 Percent | % | Read | |||
| Current L2 Harmonic 4 Percent | % | Read | |||
| Current L2 Harmonic 5 Percent | % | Read | |||
| Current L2 Harmonic 6 Percent | % | Read | |||
| Current L2 Harmonic 7 Percent | % | Read | |||
| Current L2 Harmonic 8 Percent | % | Read | |||
| Current L2 Harmonic 9 Percent | % | Read | |||
| Current L2 Harmonic 10 Percent | % | Read | |||
| Current L2 Harmonic 11 Percent | % | Read | |||
| Current L2 Harmonic 12 Percent | % | Read | |||
| Current L2 Harmonic 13 Percent | % | Read | |||
| Current L2 Harmonic 14 Percent | % | Read | |||
| Current L2 Harmonic 15 Percent | % | Read | |||
| Current L2 Harmonic 16 Percent | % | Read | |||
| Current L2 Harmonic 17 Percent | % | Read | |||
| Current L2 Harmonic 18 Percent | % | Read | |||
| Current L2 Harmonic 19 Percent | % | Read | |||
| Current L2 Harmonic 20 Percent | % | Read | |||
| Current L2 Harmonic 21 Percent | % | Read | |||
| Current L2 Harmonic 22 Percent | % | Read | |||
| Current L2 Harmonic 23 Percent | % | Read | |||
| Current L2 Harmonic 24 Percent | % | Read | |||
| Current L2 Harmonic 25 Percent | % | Read | |||
| Current L3 Fundamental | % | Read | |||
| Current L3 Harmonic 2 Percent | % | Read | |||
| Current L3 Harmonic 3 Percent | % | Read | |||
| Current L3 Harmonic 4 Percent | % | Read | |||
| Current L3 Harmonic 5 Percent | % | Read | |||
| Current L3 Harmonic 6 Percent | % | Read | |||
| Current L3 Harmonic 7 Percent | % | Read | |||
| Current L3 Harmonic 8 Percent | % | Read | |||
| Current L3 Harmonic 9 Percent | % | Read | |||
| Current L3 Harmonic 10 Percent | % | Read | |||
| Current L3 Harmonic 11 Percent | % | Read | |||
| Current L3 Harmonic 12 Percent | % | Read | |||
| Current L3 Harmonic 13 Percent | % | Read | |||
| Current L3 Harmonic 14 Percent | % | Read | |||
| Current L3 Harmonic 15 Percent | % | Read | |||
| Current L3 Harmonic 16 Percent | % | Read | |||
| Current L3 Harmonic 17 Percent | % | Read | |||
| Current L3 Harmonic 18 Percent | % | Read | |||
| Current L3 Harmonic 19 Percent | % | Read | |||
| Current L3 Harmonic 20 Percent | % | Read | |||
| Current L3 Harmonic 21 Percent | % | Read | |||
| Current L3 Harmonic 22 Percent | % | Read | |||
| Current L3 Harmonic 23 Percent | % | Read | |||
| Current L3 Harmonic 24 Percent | % | Read | |||
| Current L3 Harmonic 25 Percent | % | Read | |||
| Voltage L1 Fundamental | % | Read | |||
| Voltage L1 Harmonic 2 Percent | % | Read | |||
| Voltage L1 Harmonic 3 Percent | % | Read | |||
| Voltage L1 Harmonic 4 Percent | % | Read | |||
| Voltage L1 Harmonic 5 Percent | % | Read | |||
| Voltage L1 Harmonic 6 Percent | % | Read | |||
| Voltage L1 Harmonic 7 Percent | % | Read | |||
| Voltage L1 Harmonic 8 Percent | % | Read | |||
| Voltage L1 Harmonic 9 Percent | % | Read | |||
| Voltage L1 Harmonic 10 Percent | % | Read | |||
| Voltage L1 Harmonic 11 Percent | % | Read | |||
| Voltage L1 Harmonic 12 Percent | % | Read | |||
| Voltage L1 Harmonic 13 Percent | % | Read | |||
| Voltage L1 Harmonic 14 Percent | % | Read | |||
| Voltage L1 Harmonic 15 Percent | % | Read | |||
| Voltage L1 Harmonic 16 Percent | % | Read | |||
| Voltage L1 Harmonic 17 Percent | % | Read | |||
| Voltage L1 Harmonic 18 Percent | % | Read | |||
| Voltage L1 Harmonic 19 Percent | % | Read | |||
| Voltage L1 Harmonic 20 Percent | % | Read | |||
| Voltage L1 Harmonic 21 Percent | % | Read | |||
| Voltage L1 Harmonic 22 Percent | % | Read | |||
| Voltage L1 Harmonic 23 Percent | % | Read | |||
| Voltage L1 Harmonic 24 Percent | % | Read | |||
| Voltage L1 Harmonic 25 Percent | % | Read | |||
| Voltage L2 Fundamental | % | Read | |||
| Voltage L2 Harmonic 2 Percent | % | Read | |||
| Voltage L2 Harmonic 3 Percent | % | Read | |||
| Voltage L2 Harmonic 4 Percent | % | Read | |||
| Voltage L2 Harmonic 5 Percent | % | Read | |||
| Voltage L2 Harmonic 6 Percent | % | Read | |||
| Voltage L2 Harmonic 7 Percent | % | Read | |||
| Voltage L2 Harmonic 8 Percent | % | Read | |||
| Voltage L2 Harmonic 9 Percent | % | Read | |||
| Voltage L2 Harmonic 10 Percent | % | Read | |||
| Voltage L2 Harmonic 11 Percent | % | Read | |||
| Voltage L2 Harmonic 12 Percent | % | Read | |||
| Voltage L2 Harmonic 13 Percent | % | Read | |||
| Voltage L2 Harmonic 14 Percent | % | Read | |||
| Voltage L2 Harmonic 15 Percent | % | Read | |||
| Voltage L2 Harmonic 16 Percent | % | Read | |||
| Voltage L2 Harmonic 17 Percent | % | Read | |||
| Voltage L2 Harmonic 18 Percent | % | Read | |||
| Voltage L2 Harmonic 19 Percent | % | Read | |||
| Voltage L2 Harmonic 20 Percent | % | Read | |||
| Voltage L2 Harmonic 21 Percent | % | Read | |||
| Voltage L2 Harmonic 22 Percent | % | Read | |||
| Voltage L2 Harmonic 23 Percent | % | Read | |||
| Voltage L2 Harmonic 24 Percent | % | Read | |||
| Voltage L2 Harmonic 25 Percent | % | Read | |||
| Voltage L3 Fundamental | % | Read | |||
| Voltage L3 Harmonic 2 Percent | % | Read | |||
| Voltage L3 Harmonic 3 Percent | % | Read | |||
| Voltage L3 Harmonic 4 Percent | % | Read | |||
| Voltage L3 Harmonic 5 Percent | % | Read | |||
| Voltage L3 Harmonic 6 Percent | % | Read | |||
| Voltage L3 Harmonic 7 Percent | % | Read | |||
| Voltage L3 Harmonic 8 Percent | % | Read | |||
| Voltage L3 Harmonic 9 Percent | % | Read | |||
| Voltage L3 Harmonic 10 Percent | % | Read | |||
| Voltage L3 Harmonic 11 Percent | % | Read | |||
| Voltage L3 Harmonic 12 Percent | % | Read | |||
| Voltage L3 Harmonic 13 Percent | % | Read | |||
| Voltage L3 Harmonic 14 Percent | % | Read | |||
| Voltage L3 Harmonic 15 Percent | % | Read | |||
| Voltage L3 Harmonic 16 Percent | % | Read | |||
| Voltage L3 Harmonic 17 Percent | % | Read | |||
| Voltage L3 Harmonic 18 Percent | % | Read | |||
| Voltage L3 Harmonic 19 Percent | % | Read | |||
| Voltage L3 Harmonic 20 Percent | % | Read | |||
| Voltage L3 Harmonic 21 Percent | % | Read | |||
| Voltage L3 Harmonic 22 Percent | % | Read | |||
| Voltage L3 Harmonic 23 Percent | % | Read | |||
| Voltage L3 Harmonic 24 Percent | % | Read | |||
| Voltage L3 Harmonic 25 Percent | % | Read | |||
| Current L1 Harmonic 1 RMS | A | Read | |||
| Current L1 Harmonic 2 RMS | A | Read | |||
| Current L1 Harmonic 3 RMS | A | Read | |||
| Current L1 Harmonic 4 RMS | A | Read | |||
| Current L1 Harmonic 5 RMS | A | Read | |||
| Current L1 Harmonic 6 RMS | A | Read | |||
| Current L1 Harmonic 7 RMS | A | Read | |||
| Current L1 Harmonic 8 RMS | A | Read | |||
| Current L1 Harmonic 9 RMS | A | Read | |||
| Current L1 Harmonic 10 RMS | A | Read | |||
| Current L1 Harmonic 11 RMS | A | Read | |||
| Current L1 Harmonic 12 RMS | A | Read | |||
| Current L1 Harmonic 13 RMS | A | Read | |||
| Current L1 Harmonic 14 RMS | A | Read | |||
| Current L1 Harmonic 15 RMS | A | Read | |||
| Current L1 Harmonic 16 RMS | A | Read | |||
| Current L1 Harmonic 17 RMS | A | Read | |||
| Current L1 Harmonic 18 RMS | A | Read | |||
| Current L1 Harmonic 19 RMS | A | Read | |||
| Current L1 Harmonic 20 RMS | A | Read | |||
| Current L1 Harmonic 21 RMS | A | Read | |||
| Current L1 Harmonic 22 RMS | A | Read | |||
| Current L1 Harmonic 23 RMS | A | Read | |||
| Current L1 Harmonic 24 RMS | A | Read | |||
| Current L1 Harmonic 25 RMS | A | Read | |||
| Current L2 Harmonic 1 RMS | A | Read | |||
| Current L2 Harmonic 2 RMS | A | Read | |||
| Current L2 Harmonic 3 RMS | A | Read | |||
| Current L2 Harmonic 4 RMS | A | Read | |||
| Current L2 Harmonic 5 RMS | A | Read | |||
| Current L2 Harmonic 6 RMS | A | Read | |||
| Current L2 Harmonic 7 RMS | A | Read | |||
| Current L2 Harmonic 8 RMS | A | Read | |||
| Current L2 Harmonic 9 RMS | A | Read | |||
| Current L2 Harmonic 10 RMS | A | Read | |||
| Current L2 Harmonic 11 RMS | A | Read | |||
| Current L2 Harmonic 12 RMS | A | Read | |||
| Current L2 Harmonic 13 RMS | A | Read | |||
| Current L2 Harmonic 14 RMS | A | Read | |||
| Current L2 Harmonic 15 RMS | A | Read | |||
| Current L2 Harmonic 16 RMS | A | Read | |||
| Current L2 Harmonic 17 RMS | A | Read | |||
| Current L2 Harmonic 18 RMS | A | Read | |||
| Current L2 Harmonic 19 RMS | A | Read | |||
| Current L2 Harmonic 20 RMS | A | Read | |||
| Current L2 Harmonic 21 RMS | A | Read | |||
| Current L2 Harmonic 22 RMS | A | Read | |||
| Current L2 Harmonic 23 RMS | A | Read | |||
| Current L2 Harmonic 24 RMS | A | Read | |||
| Current L2 Harmonic 25 RMS | A | Read | |||
| Current L3 Harmonic 1 RMS | A | Read | |||
| Current L3 Harmonic 2 RMS | A | Read | |||
| Current L3 Harmonic 3 RMS | A | Read | |||
| Current L3 Harmonic 4 RMS | A | Read | |||
| Current L3 Harmonic 5 RMS | A | Read | |||
| Current L3 Harmonic 6 RMS | A | Read | |||
| Current L3 Harmonic 7 RMS | A | Read | |||
| Current L3 Harmonic 8 RMS | A | Read | |||
| Current L3 Harmonic 9 RMS | A | Read | |||
| Current L3 Harmonic 10 RMS | A | Read | |||
| Current L3 Harmonic 11 RMS | A | Read | |||
| Current L3 Harmonic 12 RMS | A | Read | |||
| Current L3 Harmonic 13 RMS | A | Read | |||
| Current L3 Harmonic 14 RMS | A | Read | |||
| Current L3 Harmonic 15 RMS | A | Read | |||
| Current L3 Harmonic 16 RMS | A | Read | |||
| Current L3 Harmonic 17 RMS | A | Read | |||
| Current L3 Harmonic 18 RMS | A | Read | |||
| Current L3 Harmonic 19 RMS | A | Read | |||
| Current L3 Harmonic 20 RMS | A | Read | |||
| Current L3 Harmonic 21 RMS | A | Read | |||
| Current L3 Harmonic 22 RMS | A | Read | |||
| Current L3 Harmonic 23 RMS | A | Read | |||
| Current L3 Harmonic 24 RMS | A | Read | |||
| Current L3 Harmonic 25 RMS | A | Read | |||
| Voltage L1 Harmonic 1 RMS | V | Read | |||
| Voltage L1 Harmonic 2 RMS | V | Read | |||
| Voltage L1 Harmonic 3 RMS | V | Read | |||
| Voltage L1 Harmonic 4 RMS | V | Read | |||
| Voltage L1 Harmonic 5 RMS | V | Read | |||
| Voltage L1 Harmonic 6 RMS | V | Read | |||
| Voltage L1 Harmonic 7 RMS | V | Read | |||
| Voltage L1 Harmonic 8 RMS | V | Read | |||
| Voltage L1 Harmonic 9 RMS | V | Read | |||
| Voltage L1 Harmonic 10 RMS | V | Read | |||
| Voltage L1 Harmonic 11 RMS | V | Read | |||
| Voltage L1 Harmonic 12 RMS | V | Read | |||
| Voltage L1 Harmonic 13 RMS | V | Read | |||
| Voltage L1 Harmonic 14 RMS | V | Read | |||
| Voltage L1 Harmonic 15 RMS | V | Read | |||
| Voltage L1 Harmonic 16 RMS | V | Read | |||
| Voltage L1 Harmonic 17 RMS | V | Read | |||
| Voltage L1 Harmonic 18 RMS | V | Read | |||
| Voltage L1 Harmonic 19 RMS | V | Read | |||
| Voltage L1 Harmonic 20 RMS | V | Read | |||
| Voltage L1 Harmonic 21 RMS | V | Read | |||
| Voltage L1 Harmonic 22 RMS | V | Read | |||
| Voltage L1 Harmonic 23 RMS | V | Read | |||
| Voltage L1 Harmonic 24 RMS | V | Read | |||
| Voltage L1 Harmonic 25 RMS | V | Read | |||
| Voltage L2 Harmonic 1 RMS | V | Read | |||
| Voltage L2 Harmonic 2 RMS | V | Read | |||
| Voltage L2 Harmonic 3 RMS | V | Read | |||
| Voltage L2 Harmonic 4 RMS | V | Read | |||
| Voltage L2 Harmonic 5 RMS | V | Read | |||
| Voltage L2 Harmonic 6 RMS | V | Read | |||
| Voltage L2 Harmonic 7 RMS | V | Read | |||
| Voltage L2 Harmonic 8 RMS | V | Read | |||
| Voltage L2 Harmonic 9 RMS | V | Read | |||
| Voltage L2 Harmonic 10 RMS | V | Read | |||
| Voltage L2 Harmonic 11 RMS | V | Read | |||
| Voltage L2 Harmonic 12 RMS | V | Read | |||
| Voltage L2 Harmonic 13 RMS | V | Read | |||
| Voltage L2 Harmonic 14 RMS | V | Read | |||
| Voltage L2 Harmonic 15 RMS | V | Read | |||
| Voltage L2 Harmonic 16 RMS | V | Read | |||
| Voltage L2 Harmonic 17 RMS | V | Read | |||
| Voltage L2 Harmonic 18 RMS | V | Read | |||
| Voltage L2 Harmonic 19 RMS | V | Read | |||
| Voltage L2 Harmonic 20 RMS | V | Read | |||
| Voltage L2 Harmonic 21 RMS | V | Read | |||
| Voltage L2 Harmonic 22 RMS | V | Read | |||
| Voltage L2 Harmonic 23 RMS | V | Read | |||
| Voltage L2 Harmonic 24 RMS | V | Read | |||
| Voltage L2 Harmonic 25 RMS | V | Read | |||
| Voltage L3 Harmonic 1 RMS | V | Read | |||
| Voltage L3 Harmonic 2 RMS | V | Read | |||
| Voltage L3 Harmonic 3 RMS | V | Read | |||
| Voltage L3 Harmonic 4 RMS | V | Read | |||
| Voltage L3 Harmonic 5 RMS | V | Read | |||
| Voltage L3 Harmonic 6 RMS | V | Read | |||
| Voltage L3 Harmonic 7 RMS | V | Read | |||
| Voltage L3 Harmonic 8 RMS | V | Read | |||
| Voltage L3 Harmonic 9 RMS | V | Read | |||
| Voltage L3 Harmonic 10 RMS | V | Read | |||
| Voltage L3 Harmonic 11 RMS | V | Read | |||
| Voltage L3 Harmonic 12 RMS | V | Read | |||
| Voltage L3 Harmonic 13 RMS | V | Read | |||
| Voltage L3 Harmonic 14 RMS | V | Read | |||
| Voltage L3 Harmonic 15 RMS | V | Read | |||
| Voltage L3 Harmonic 16 RMS | V | Read | |||
| Voltage L3 Harmonic 17 RMS | V | Read | |||
| Voltage L3 Harmonic 18 RMS | V | Read | |||
| Voltage L3 Harmonic 19 RMS | V | Read | |||
| Voltage L3 Harmonic 20 RMS | V | Read | |||
| Voltage L3 Harmonic 21 RMS | V | Read | |||
| Voltage L3 Harmonic 22 RMS | V | Read | |||
| Voltage L3 Harmonic 23 RMS | V | Read | |||
| Voltage L3 Harmonic 24 RMS | V | Read | |||
| Voltage L3 Harmonic 25 RMS | V | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show voltage, current and power per phase of a switchboard on a ModbusCloud dashboard.
- Get an email alert when a phase current or the total power goes above a threshold you set.
- Keep a year of energy counter history to compare consumption per week or month.
- Watch voltage and current THD to see when harmonic load in the building increases.
- Check the alarm status of the meter output and switch the output remotely.
Installation
Connect the RS485 terminals of the meter to the RS485 port of the ModbusCloud Gateway, A to A and B to B, and terminate both ends of the bus with 120 ohm.
Set a unique Modbus address, the baud rate and the parity on the meter.
In ModbusCloud, add a Modbus device on the Gateway with that address and serial settings and import this template.
Check that the CT and VT ratio read the values of your transformers, otherwise set them in the meter.
Compare voltage and current in ModbusCloud with the display of the meter.
Things to watch for
The meter does not answer. What should I check first?
Check that address, baud rate and parity in ModbusCloud match the meter, and that A and B are not swapped. Only one master may poll the bus, and both ends of a long bus need a 120 ohm termination.
Why is the power value 100 times too high or too low?
The meter reports power in 0.01 W while CT ratio times VT ratio is below 5000, and in whole watts above that. The template uses 0.01. With large transformers, set the scale of those power registers to 1, or use the signed power registers, which are always in watts.
Why do the energy counters jump in large steps?
The energy counters of the measures block count in steps that depend on CT times VT, from 10 Wh up to 1,000,000 Wh. For exact energy use the Low and High energy registers, which give Wh and MWh, and add them.
Why does writing a setting have no effect?
The meter only accepts settings after the access key 23205 in Enable Remote Writing. Write the setting, write the access key again and then 10 to Save Configuration. The setup blocks are documented as one block, so writing a single word can be refused. Change settings with care, a wrong CT ratio changes every reading.