Lowara e-SM Smart Pump

Variable speed booster pump that keeps pressure constant, with readings, faults and setpoints.

The Lowara e-SM Smart Pump is a range of multistage booster pumps (e-HME, e-SVE, VME, e-SVIE) with an integrated variable speed drive that keeps pressure constant in buildings and water supply. This Modbus RTU template reads pressure, speed, power, temperatures and faults and lets you start, stop and set the pressure setpoint from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
196, read and write
Brand
Lowara
Key readings
Pressure · Motor speed · Power · Inverter current · Module temperature · Error code
Available commands
Start and stop · Control mode · Pressure setpoint · Speed in constant speed mode · Ramps · Multi-pump settings
Compatible models
e-HME · e-SVE · VME · e-SVIE · Lowara Smart Pump Range with e-SM drive, firmware 101.10 and later
Last updated

Registers (196)

196 read, 41 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Current PressurebarRead
Motor SpeedrpmRead
Current PowerWRead
Inverter CurrentARead
Inverter VoltageVRead
Effective Required ValuebarRead
Power Module Temperature°CRead
Winding 1 Temperature°CRead
Winding 2 Temperature°CRead
Winding 3 Temperature°CRead
Current ErrorRead
Error Bitfield LSWRead
Error Bitfield MSWRead
Current AlarmRead
Alarm Bitfield LSWRead
Alarm Bitfield MSWRead
Start Stop CommandRead and write
Auto StartRead and write
Control ModeRead and write
Speed Set ACT ModerpmRead and write
Pressure SetpointbarRead and write
Pressure UnitRead and write
Sensor SelectionRead and write
Pressure Sensor 1 Full ScalebarRead and write
System PasswordRead and write
Lock FunctionRead and write
Test Run Time StarthRead
Test Run SpeedrpmRead and write
Test Run DurationsRead and write
Keyboard LockRead and write
Default Values ReloadRead and write
Max RPMrpmRead and write
Min RPMrpmRead and write
Ramp 1sRead and write
Ramp 2sRead and write
Ramp 3sRead and write
Ramp 4sRead and write
Ramp Speed Min AccelerationsRead and write
Ramp Speed Min DecelerationsRead and write
Smin TimesRead and write
Window%Read and write
Hysteresis%Read and write
Regulation Restart Value%Read and write
Pressure Minimum Delay TimesRead and write
Speed Min ConfigurationRead and write
Pressure Minimum ThresholdbarRead and write
Pressure Minimum Auto ResetRead and write
Avoid Frequent Parameter SavingRead and write
Multipump Max UnitsRead and write
Multipump Switch IntervalhRead and write
Multipump Sync Speed LimitrpmRead and write
Multipump Sync WindowrpmRead and write
Multipump Actual Value IncreasebarRead and write
Multipump Actual Value DecreasebarRead and write
Lack of Water Switch InputRead and write
Multipump Enable SpeedrpmRead and write
Multipump PriorityRead
Multipump RevisionRead
Speed LiftrpmRead and write
Lift Amount%Read and write
Operating TimesRead
Motor TimesRead
Software VersionRead
Map Version ProgressiveRead
Map VersionRead
Preset Parameter ProgressiveRead
Preset Parameter VersionRead
Hydraulic VersionRead
Error Log 0 Error CodeRead
Error Log 0 Start TimesRead
Error Log 0 End TimesRead
Error Log 0 Error Bitfield LSWRead
Error Log 0 OccurrencesRead
Error Log 0 Speed SetrpmRead
Error Log 0 Speed MeasuredrpmRead
Error Log 0 Phase CurrentARead
Error Log 0 Alarm Bitfield LSWRead
Error Log 0 Alarm Bitfield MSWRead
Error Log 0 IO Status BitfieldRead
Error Log 0 PowerWRead
Error Log 0 PressurebarRead
Error Log 0 Module Temperature°CRead
Error Log 0 Start Stop StatusRead
Error Log 0 Error Bitfield MSWRead
Error Log 1 Error CodeRead
Error Log 1 Start TimesRead
Error Log 1 End TimesRead
Error Log 1 Error Bitfield LSWRead
Error Log 1 OccurrencesRead
Error Log 1 Speed SetrpmRead
Error Log 1 Speed MeasuredrpmRead
Error Log 1 Phase CurrentARead
Error Log 1 Alarm Bitfield LSWRead
Error Log 1 Alarm Bitfield MSWRead
Error Log 1 IO Status BitfieldRead
Error Log 1 PowerWRead
Error Log 1 PressurebarRead
Error Log 1 Module Temperature°CRead
Error Log 1 Start Stop StatusRead
Error Log 1 Error Bitfield MSWRead
Error Log 2 Error CodeRead
Error Log 2 Start TimesRead
Error Log 2 End TimesRead
Error Log 2 Error Bitfield LSWRead
Error Log 2 OccurrencesRead
Error Log 2 Speed SetrpmRead
Error Log 2 Speed MeasuredrpmRead
Error Log 2 Phase CurrentARead
Error Log 2 Alarm Bitfield LSWRead
Error Log 2 Alarm Bitfield MSWRead
Error Log 2 IO Status BitfieldRead
Error Log 2 PowerWRead
Error Log 2 PressurebarRead
Error Log 2 Module Temperature°CRead
Error Log 2 Start Stop StatusRead
Error Log 2 Error Bitfield MSWRead
Error Log 3 Error CodeRead
Error Log 3 Start TimesRead
Error Log 3 End TimesRead
Error Log 3 Error Bitfield LSWRead
Error Log 3 OccurrencesRead
Error Log 3 Speed SetrpmRead
Error Log 3 Speed MeasuredrpmRead
Error Log 3 Phase CurrentARead
Error Log 3 Alarm Bitfield LSWRead
Error Log 3 Alarm Bitfield MSWRead
Error Log 3 IO Status BitfieldRead
Error Log 3 PowerWRead
Error Log 3 PressurebarRead
Error Log 3 Module Temperature°CRead
Error Log 3 Start Stop StatusRead
Error Log 3 Error Bitfield MSWRead
Error Log 4 Error CodeRead
Error Log 4 Start TimesRead
Error Log 4 End TimesRead
Error Log 4 Error Bitfield LSWRead
Error Log 4 OccurrencesRead
Error Log 4 Speed SetrpmRead
Error Log 4 Speed MeasuredrpmRead
Error Log 4 Phase CurrentARead
Error Log 4 Alarm Bitfield LSWRead
Error Log 4 Alarm Bitfield MSWRead
Error Log 4 IO Status BitfieldRead
Error Log 4 PowerWRead
Error Log 4 PressurebarRead
Error Log 4 Module Temperature°CRead
Error Log 4 Start Stop StatusRead
Error Log 4 Error Bitfield MSWRead
Error Log 5 Error CodeRead
Error Log 5 Start TimesRead
Error Log 5 End TimesRead
Error Log 5 Error Bitfield LSWRead
Error Log 5 OccurrencesRead
Error Log 5 Speed SetrpmRead
Error Log 5 Speed MeasuredrpmRead
Error Log 5 Phase CurrentARead
Error Log 5 Alarm Bitfield LSWRead
Error Log 5 Alarm Bitfield MSWRead
Error Log 5 IO Status BitfieldRead
Error Log 5 PowerWRead
Error Log 5 PressurebarRead
Error Log 5 Module Temperature°CRead
Error Log 5 Start Stop StatusRead
Error Log 5 Error Bitfield MSWRead
Error Log 6 Error CodeRead
Error Log 6 Start TimesRead
Error Log 6 End TimesRead
Error Log 6 Error Bitfield LSWRead
Error Log 6 OccurrencesRead
Error Log 6 Speed SetrpmRead
Error Log 6 Speed MeasuredrpmRead
Error Log 6 Phase CurrentARead
Error Log 6 Alarm Bitfield LSWRead
Error Log 6 Alarm Bitfield MSWRead
Error Log 6 IO Status BitfieldRead
Error Log 6 PowerWRead
Error Log 6 PressurebarRead
Error Log 6 Module Temperature°CRead
Error Log 6 Start Stop StatusRead
Error Log 6 Error Bitfield MSWRead
Error Log 7 Error CodeRead
Error Log 7 Start TimesRead
Error Log 7 End TimesRead
Error Log 7 Error Bitfield LSWRead
Error Log 7 OccurrencesRead
Error Log 7 Speed SetrpmRead
Error Log 7 Speed MeasuredrpmRead
Error Log 7 Phase CurrentARead
Error Log 7 Alarm Bitfield LSWRead
Error Log 7 Alarm Bitfield MSWRead
Error Log 7 IO Status BitfieldRead
Error Log 7 PowerWRead
Error Log 7 PressurebarRead
Error Log 7 Module Temperature°CRead
Error Log 7 Start Stop StatusRead
Error Log 7 Error Bitfield MSWRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show pressure, speed and power of each booster pump on a ModbusCloud dashboard.
  • Get an email alert when the current error code is not zero or the pump reports dry running.
  • Keep a year of pressure history to see when demand peaks in the building.
  • Adjust the pressure setpoint from ModbusCloud without going to the pump room.
  • Track operating time per pump to plan maintenance.

Installation

  1. Connect A1, B1 and GND of the drive terminals to the RS485 port of the ModbusCloud Gateway and terminate both bus ends with 120 ohm.

  2. On the pump, select Modbus RTU in P50 and set address, baud rate and parity in P51, P52 and P54.

  3. Set P69 Avoid frequent parameter saving to yes if you will write values from ModbusCloud.

  4. In ModbusCloud, add a Modbus device on the Gateway with the same settings and import this template.

  5. Check that current pressure and motor speed match the pump display.

Things to watch for

The pump does not answer on Modbus. What should I check?

Check that P50 is set to Modbus RTU and that address, baud rate and parity in P51, P52 and P54 match ModbusCloud. Default is address 1, 9600 baud, 8N1. Then check A1 and B1 and the termination.

Why does the pressure read 100 times too high?

Pressure registers count in hundredths of a bar, 520 is 5.20 bar. The template already applies that. If P41 is set to PSI, the registers count in tenths of a psi and the bar unit in the template no longer applies.

Why can I no longer change settings on the pump itself?

While Modbus communication is active, the drive locks most parameters on its push buttons to avoid conflicts with the external device. Stop the Modbus communication to edit them locally again.

What should I watch out for when writing values?

The drive only accepts writes with function code 16. Every write is stored in EEPROM, so set P69 to yes and do not write setpoints in short cycles. Writing 1 to Default Values Reload resets the pump to factory settings.