Mitsubishi MelcoBEMS Mini (A1M) Modbus RTU template

MelcoBEMS Mini (A1M)

Controls Mitsubishi HVAC units via MelcoBEMS Mini (A1M) Modbus interface

This template connects to the Mitsubishi MelcoBEMS Mini (A1M) Modbus RTU interface. It provides read and write access to HVAC parameters such as room temperature, setpoint, fan speed, air direction, drive mode, and on/off control.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
6, read and write
Key readings
Room Temperature · Drive Mode · Temperature Setpoint · Fan Speed · Air Direction · Drive On/Off
Available commands
Temperature Setpoint · Fan Speed · Air Direction · Drive On/Off
Compatible models
MelcoBEMS Mini (A1M)
Last updated

Registers (6)

6 read, 5 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Room Temperature°CRead and write
Drive ModeRead
Temperature Setpoint°CRead and write
Fan SpeedRead and write
Air DirectionRead and write
Drive On_OffRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor room temperature and setpoint on a live cloud dashboard for each Mitsubishi indoor unit.
  • Adjust temperature setpoints remotely to reduce energy consumption outside of occupied hours.
  • Create an alert when room temperature deviates from the setpoint by more than 2 degrees for over 15 minutes.
  • Log fan speed and air direction changes over time to verify scheduled HVAC profiles.
  • Switch drive on or off remotely for seasonal shutdown or startup without an on-site visit.
  • Compare drive mode and room temperature across multiple zones in a multi-unit installation.

Installation

  1. Wire the RS-485 A and B terminals from your ModbusCloud Gateway to the corresponding Modbus terminals on the MelcoBEMS Mini (A1M) module.

  2. Set the Modbus slave address on the A1M module using its DIP switches or configuration menu, and note the address for use in the template.

  3. Confirm that the baud rate on the A1M is set to 9600, matching the default for this template.

  4. Import the Mitsubishi MelcoBEMS Mini (A1M) template in the ModbusCloud platform and assign the correct slave address.

  5. Verify communication by checking that room temperature and drive status values appear on the cloud dashboard.

  6. If controlling multiple indoor units, repeat the wiring and address assignment for each A1M module and add each as a separate device in ModbusCloud.

Things to watch for

Why do room temperature and drive mode appear to come from the same register?

Both parameters are mapped to register address 0 on the A1M. The template handles this by reading the same address and interpreting the value according to the parameter context. No manual adjustment is needed.

What baud rate and serial settings should I use?

The default is 9600 baud, 8 data bits, no parity, 1 stop bit (9600 8N1). Make sure both the gateway and the A1M module are configured identically.

Can I control multiple indoor units from one gateway?

Yes. Each indoor unit requires its own MelcoBEMS Mini (A1M) module with a unique Modbus slave address. Connect all modules on the same RS-485 bus and add each as a separate device in ModbusCloud.

Write commands do not seem to take effect. What should I check?

Verify that the A1M module is set to allow external Modbus write access. Some installations have write protection enabled by default. Also confirm the correct slave address and that no other BMS is holding write priority on the bus.

Want to see how it works?