MENNEKES MENNEKES AMTRON® 4You 300 Modbus RTU template

MENNEKES AMTRON® 4You 300

Monitor and control MENNEKES AMTRON 4You 300 EV charging station via Modbus RTU

Template for the MENNEKES AMTRON 4You 300 EV charging station via Modbus RTU. Reads voltage, current, power, temperature, session energy, and EVSE state. Controls charging current, charging release, solar charging mode, and dynamic phase switching.

Protocol
Modbus RTU
Connection
RS485, 57600 baud
Registers
55, read and write
Key readings
Voltage L1 to L3 · Current L1 to L3 · Power L1 to L3 and Overall · EVSE State · Charged Energy Session and Total · Temperature
Available commands
Charging Current Energy Manager · Charging Release Energy Manager · Solar Charging Mode · Requested Phases
Compatible models
AMTRON 4You 300
Last updated

Registers (55)

53 read, 7 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
53_Voltage L1VRead
54_Voltage L2VRead
55_Voltage L3VRead
50_Current L1ARead
52_Current L3ARead
51_Current L2ARead
56_Power L1WRead
57_Power L2WRead
58_Power L3WRead
59_Power OverallWRead
10_EVSE StateRead
71_Charged Energy SessionkWhRead
72_Duration SessionsRead
01_Modbus VersionRead
20_SignaledCurrentARead
60_Maximal EVSE CurrentARead
11_Authorization StatusRead
12_DowngradeRead
13_Phase RotationRead
30_Downgrade CurrentARead
31_Charging Current Energy ManagerARead and write
32_Max Current House (DIP)ARead
33_Max Current EVSEARead
34_Phase Switching ModeRead
70_Max Current SessionARead
82_Cable LockRead
83_Solar Charging ModeRead and write
84_Requested PhasesRead and write
85_Charging Release Energy ManagerRead and write
86_Lock EVSERead and write
90_Active Error CodeRead
18_CP StateRead
36_Phase Options HWRead
37_Cable LockRead
38_Master Lost Fallback CurrentRead
39_Grid ImbalanceRead
40_Grid Imbalance ThresholdARead
41_Grid Phases ConnectedRead
42_AuthorizationRead
44_Phase Switching PausesRead
43_Solar Supported Charging CurrentARead
67_Temperature°CRead
73_Detected EV PhasescountRead
91_Master Lost Fallback StateRead
92_Switched PhasesRead
100_Charged Energy TotalkWhRead
101_Charging Sessions TotalcountRead
61_Phase RotationRead
62_Connected PhasesRead
63_Phase Usage Solar ChargingRead
64_Fallback Current Master LostARead
65_Solar Charging ActiveRead
66_Phase Switching PausesRead
80_Heartbeat 0x55AAWrite
87_System RestartWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time charging power and session energy on a live dashboard for each customer site.
  • Create an alert when EVSE state indicates a fault or when the wallbox temperature exceeds a safe threshold.
  • Log cumulative charged energy per station to generate monthly consumption reports for billing.
  • Control solar-optimized charging by adjusting charging current and phase switching based on PV surplus.
  • Remotely enable or disable charging via the charging release register for access management.
  • Track per-phase voltage and current to detect load imbalance across multiple installations.

Installation

  1. Connect the ModbusCloud Gateway to the MENNEKES AMTRON 4You 300 RS-485 terminals using a twisted-pair cable with correct A/B polarity.

  2. Set DIP switches 4, 5, and 7 of bank S1 on the wallbox to ON and restart the wallbox to enable solar-controlled Modbus satellite mode.

  3. Configure the gateway serial port to match the wallbox defaults: 57600 baud, 8 data bits, 2 stop bits, Modbus address 50.

  4. If dynamic phase switching is required, connect the MENNEKES configuration cable and enable the option in the MENNEKES configuration tool before commissioning.

  5. Import the MENNEKES AMTRON 4You 300 template in the ModbusCloud portal and assign it to the correct gateway and Modbus address.

  6. Verify that readings such as voltage, current, and EVSE state appear on the ModbusCloud dashboard.

Things to watch for

The wallbox does not respond to Modbus commands. What should I check?

Verify that DIP switches 4, 5, and 7 on bank S1 are set to ON and that the wallbox has been restarted afterward. Also confirm the baud rate is set to 57600 with 2 stop bits, and that the Modbus address matches (default 50).

Charging stops unexpectedly after a few seconds of external control.

The heartbeat register at address 3328 must receive the value 0x55AA at least every 10 seconds. If this cyclic write is interrupted, the wallbox reverts to standalone mode. ModbusCloud writes registers at most once per minute, so it cannot keep up this heartbeat. Controlling this wallbox through ModbusCloud is therefore not possible, while reading its values works.

Dynamic phase switching does not work even though I send the requested phases command.

Phase switching must first be activated via the MENNEKES configuration cable and configuration tool. Without this activation, the wallbox ignores phase switch requests over Modbus. This feature is only available on the 11 kW variant.

What firmware version is required for Modbus RTU support?

The wallbox firmware must be at least version 2.0 (March 2024). MENNEKES recommends using the latest version of the configuration tool (v2.2) to update firmware. The current wallbox firmware is v2.2 (July 2025).