Midea M-Thermal

Air to water heat pump that reports water temperatures, compressor data and faults and takes setpoints.

The Midea M-Thermal is an air to water heat pump that heats and cools homes and small buildings and makes domestic hot water. This Modbus RTU template reads water and outdoor temperatures, compressor data, water flow and fault codes, and lets you switch zones and hot water on or off and set the mode and setpoints from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
114, read and write
Brand
Midea
Key readings
Water outlet temperature · Water inlet temperature · Outdoor temperature · DHW tank temperature · Compressor frequency · Water flow · Current fault · Operating mode
Available commands
Power on or off · Operating mode · Water temperature setpoint · Room temperature setpoint · DHW setpoint · Forced backup heater
Compatible models
M-Thermal wired controller · Midea M-Thermal air to water heat pumps (split and mono) with the M-Thermal wired controller and Modbus terminals H1 and H2
Last updated

Registers (114)

114 read, 11 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Compressor FrequencyHzRead
Operating ModeRead
Fan SpeedrpmRead
EEV OpeningRead
Water Inlet Temperature°CRead
Water Outlet Temperature°CRead
Condenser Temperature T3°CRead
Outdoor Temperature T4°CRead
Discharge Temperature°CRead
Suction Temperature°CRead
Total Water Outlet Temperature T1°CRead
Water Outlet After Backup Heater T1B°CRead
Refrigerant Liquid Temperature T2°CRead
Refrigerant Gas Temperature T2B°CRead
Room Temperature Ta°CRead
DHW Tank Temperature T5°CRead
High PressurekPaRead
Low PressurekPaRead
Outdoor Unit CurrentARead
Outdoor Unit VoltageVRead
Hydraulic Module Current 1ARead
Hydraulic Module Current 2ARead
Compressor Operating HourshRead
Current FaultRead
Fault 1Read
Fault 2Read
Fault 3Read
Status BitsRead
Load OutputsRead
Unit VersionRead
Wired Controller VersionRead
Compressor Target FrequencyHzRead
DC Bus CurrentARead
DC Bus VoltageVRead
Inverter Module Temperature°CRead
Zone 1 Calculated Setpoint°CRead
Zone 2 Calculated Setpoint°CRead
Water Flowm³/hRead
Current Limit SchemeRead
Hydraulic Module CapacitykWRead
Power On OffRead and write
Mode SettingRead and write
Water Temperature Setpoint T1s°CRead and write
Room Temperature Setpoint Ts°CRead and write
DHW Setpoint T5s°CRead and write
Function SettingRead and write
Curve SelectionRead and write
Forced Water HeatingRead and write
Forced TBHRead and write
Forced IBH1Read and write
Smart Grid Max TimehRead and write
Appliance TypeRead
T1S Cooling Upper Limit°CRead
T1S Cooling Lower Limit°CRead
T1S Heating Upper Limit°CRead
T1S Heating Lower Limit°CRead
Room Setpoint Upper Limit°CRead
Room Setpoint Lower Limit°CRead
DHW Setpoint Upper Limit°CRead
DHW Setpoint Lower Limit°CRead
DHW Pump Running TimeminRead
Parameter Setting 1Read
Parameter Setting 2Read
dT5 On°CRead
dT1S5°CRead
DHW IntervalminRead
T4 DHW Max°CRead
T4 DHW Min°CRead
TBH DelayminRead
dT5 TBH Off°CRead
T4 TBH On°CRead
Disinfection Temperature°CRead
Disinfection Max DurationminRead
Disinfection High Temperature TimeminRead
Cooling Compressor IntervalminRead
dT1SC°CRead
dTSC°CRead
T4 Cooling Max°CRead
T4 Cooling Min°CRead
Heating Compressor IntervalminRead
dT1SH°CRead
dTSH°CRead
T4 Heating Max°CRead
T4 Heating Min°CRead
T4 IBH On°CRead
dT1 IBH On°CRead
IBH DelayminRead
T4 AHS On°CRead
dT1 AHS On°CRead
AHS DelayminRead
DHW Heat Pump Max TimeminRead
DHW Heat Pump Restrict TimeminRead
T4 Auto Cooling Min°CRead
T4 Auto Heating Max°CRead
Holiday Heating Setpoint°CRead
Holiday DHW Setpoint°CRead
Floor Drying Rise DaysdRead
Floor Drying Peak DaysdRead
Floor Drying Drop DaysdRead
Floor Drying Peak Temperature°CRead
First Floor Heating TimehRead
First Floor Heating Setpoint°CRead
Custom Curve Cooling T1Set C1°CRead
Custom Curve Cooling T1Set C2°CRead
Custom Curve Cooling T4 C1°CRead
Custom Curve Cooling T4 C2°CRead
Custom Curve Heating T1Set H1°CRead
Custom Curve Heating T1Set H2°CRead
Custom Curve Heating T4 H1°CRead
Custom Curve Heating T4 H2°CRead
Power Input LimitationRead
T4 Fresh TimesRead
Pump I DelayhRead
Emission TypeRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show water outlet and inlet temperature, outdoor temperature and compressor frequency of a Midea heat pump on one ModbusCloud dashboard.
  • Get an email when Current Fault is no longer 0 or the water outlet temperature drops below a threshold you set.
  • Track water flow, capacity and compressor hours in the 365-day history to check how the heat pump runs over a season.
  • Change the hot water or water temperature setpoint remotely from the portal.
  • Switch hot water production off during a holiday and on again before the return.
  • Check high and low pressure and discharge temperature before a service visit.

Installation

  1. Set the Modbus address with rotary switch S3 on the hydraulic module board; position 0 gives address 16.

  2. Connect H1 (A+) and H2 (B-) of the wired controller to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.

  3. In ModbusCloud, add a Modbus device with the same address at 9600 baud, no parity, 1 stop bit, and import this template.

  4. Check that Water Outlet Temperature and Outdoor Temperature T4 show plausible values.

Things to watch for

The heat pump does not answer. What should I check?

Check the address: switch S3 at position 0 means address 16, not 0. Use 9600 baud, 8 data bits, no parity and 1 stop bit. Swap H1 and H2 if needed and make sure only one Modbus master talks to the wired controller.

Why do some registers return an error?

Registers 123 and 247 to 254 are reserved and return an address error when read. Some values, such as zone 2 or room temperature, only make sense when that zone or sensor is installed.

Water flow or capacity looks 100 times too high. Why?

The unit sends water flow and capacity multiplied by 100. The template divides by 100, so check that the scale in the portal is still 0.01 for these two registers.

How do I switch the heat pump on through Modbus?

Power On Off is a bit field: bit 1 switches zone 1, bit 2 hot water, bit 3 zone 2. Write the whole word, for example 6 for zone 1 and hot water on. Writing registers is off per Gateway until it is enabled on request; write only values you understand.

More RTU templates