Nordic Nordic Flexit Modbus RTU template

Nordic Flexit

Controls and monitors Nordic Flexit ventilation system units via Modbus RTU

This template connects Nordic Flexit ventilation system units via Modbus RTU. It reads air temperatures, alarm status, filter hours, and operating mode. It also provides control over setpoints, operating mode, fireplace ventilation, and rapid ventilation triggers.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
13, read and write
Brand
Nordic
Key readings
Outside Air Temp · Supply Air Temp · Extract Air Temp · Exhaust Air Temp · Alarm Indication · Operating Time Filter
Available commands
Room Operating Mode · Setpoint Temp Home / Away · Trigger Fireplace / Rapid Vent · Comfort Button
Compatible models
Nordic Flexit · Nordic Flexit S4
Last updated

Registers (13)

10 read, 6 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Room Operating ModeRead and write
Outside Air Temp°CRead
Supply Air Temp°CRead
Alarm IndicationRead
Extract Air Temp°CRead
Exhaust Air Temp°CRead
Setpoint Temp Away°CRead and write
Setpoint Temp Home°CRead and write
Operating Time Filter Replacementhod.Read
Operating Time Filterhod.Read
Trigger FireplaceWrite
Trigger Rapid VentWrite
Comfort buttonWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor supply and extract air temperatures on a live dashboard to verify heat recovery performance.
  • Create an alert when the alarm indication register signals a fault on the Nordic Flexit unit.
  • Track filter operating hours remotely and notify the end user when a filter replacement is due.
  • Adjust home and away temperature setpoints remotely without visiting the installation site.
  • Trigger fireplace ventilation mode from the cloud when coordinating with a wood stove installation.
  • Log outside air temperature alongside supply air temperature to evaluate heat recovery efficiency over time.

Installation

  1. Connect the Modbus RTU wiring (A and B terminals) from the Nordic Flexit unit to the RS485 port on your ModbusCloud Gateway.

  2. Verify that the Nordic Flexit is configured with slave address 1, baud rate 9600, 8 data bits, even parity, and 1 stop bit.

  3. Match the same serial port settings (9600, 8E1) on the ModbusCloud gateway RS485 port configuration.

  4. Import the Nordic Flexit template from the ModbusCloud template library and assign it to the correct gateway and port.

  5. Set the Comfort Button register (address 2040) to 1 in the ModbusCloud interface to enable write access to all control registers.

  6. Confirm live data is appearing on the dashboard by checking that temperature values and filter hours are reading correctly.

Things to watch for

Why are all write commands to the Nordic Flexit being ignored?

All write registers only function when the Comfort Button at Modbus address 2040 is set to 1. Enable this register first before attempting any control operations.

Temperature readings show unrealistic values. What is wrong?

Temperature and filter hour registers use float32 format, which spans two consecutive 16-bit registers. Ensure your gateway is configured for the correct byte order and word order (typically big-endian) to decode float32 values properly.

The gateway cannot communicate with the Nordic Flexit unit. What should I check?

Verify that the serial settings match exactly: baud rate 9600, 8 data bits, even parity, 1 stop bit, and slave address 1. Also check that the A and B wires are not swapped and that a termination resistor is present if the cable run is long.

Can I use this template with the Nordic Flexit S4 model?

Yes. This template is compatible with both the standard Nordic Flexit and the Nordic Flexit S4. The register map and communication settings are the same.