NORDline NORDline WWBA Modbus RTU template

NORDline WWBA

Controls NORDline air-to-water heat pumps via Modbus RTU

NORDline WWBA is a series of air-to-water heat pumps controllable via Modbus RTU at 9600 baud. This template reads temperature sensors, compressor status, and error codes while providing full mode and setpoint control. Compatible models include WWBA9.5 H-B/P, WWBA13.5 H-B-S, and WWBA19.5 H-B-S.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
17, read and write
Key readings
Output temperature · DHW tank temperature · UFA tank temperature · Evaporator coil temperature · Discharge gas temperature · Error codes 1 to 5
Available commands
Mode (cooling, heating, FCU) · Water pump mode · FCU heating temp set point · Floor heating outlet temperature
Compatible models
WWBA9.5 H-B/P · WWBA13.5 H-B-S · WWBA19.5 H-B-S
Last updated

Registers (17)

16 read, 4 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
ModeRead and write
Output temperature°CRead
Control markRead
Status output 1Read
control mark 2Read
Error 1Read
Error 4Read
Error 5Read
Error 2Read
DHW tank temperature°CRead
UFA tank temperature_°CRead
Water pump modeRead and write
Evaporator coil temperature°CRead
Reverse temperature°CRead
Temperature of discharge gas°CRead
FCU heating temp set point°CRead and write
Outlet temperature of floor heating°CWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor outlet water and DHW tank temperatures on a live cloud dashboard for remote customer support.
  • Switch between cooling, heating, and FCU heating modes remotely without a site visit.
  • Create an alert when any of the five error codes becomes active to reduce response time.
  • Adjust floor heating outlet temperature setpoints based on outdoor conditions or customer requests.
  • Track compressor run status and discharge gas temperature to schedule preventive maintenance.
  • Log evaporator coil temperature over time to detect early signs of refrigerant issues.

Installation

  1. Wire the ModbusCloud Gateway to the NORDline WWBA RS-485 terminals, observing correct A and B polarity.

  2. Terminate the RS-485 bus with a 120 ohm resistor at both ends if the gateway is the last device on the bus.

  3. On the NORDline WWBA controller, set a unique Modbus slave address and confirm the baud rate is 9600, 8N1.

  4. In the ModbusCloud portal, import the NORDline WWBA template and enter the matching slave address.

  5. Verify communication by checking that output temperature and compressor status values appear on the dashboard.

  6. Configure alerts or automations for error codes and temperature thresholds as needed.

Things to watch for

The gateway cannot communicate with the heat pump. What should I check first?

Verify that the RS-485 A and B wires are not swapped. Also confirm the baud rate on the heat pump is set to 9600 with 8 data bits, no parity, and 1 stop bit (8N1). Check that the slave address in ModbusCloud matches the address configured on the unit.

Can I use one template for different WWBA models?

Yes. The WWBA9.5 H-B/P, WWBA13.5 H-B-S, and WWBA19.5 H-B-S share the same Modbus register map. A single template instance works for any of these models.

Do I need a bus termination resistor?

If the ModbusCloud gateway is at one end of the RS-485 bus, place a 120 ohm termination resistor across the A and B lines. The heat pump end should also be terminated if it is the other physical end of the bus.

Temperature values look incorrect or scaled wrong. How do I fix this?

The template already includes the correct scaling factors for all temperature registers. If values still appear wrong, confirm you have imported the latest version of the NORDline WWBA template from the ModbusCloud library.