Olimpia Splendid
Controls Olimpia Splendid heating and cooling systems via Modbus RTU
This template integrates Olimpia Splendid heating and cooling systems via Modbus RTU. It reads device status and ambient temperature, and allows writing temperature setpoints. A Modbus ASCII to RTU converter is required between the gateway and the B0686 electronics.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 4, read and write
- Brand
- Olimpia Splendid
- Key readings
- Status Registers · Device Address
- Available commands
- Status Registers · Temperature Setpoint · Temperature Ambiente
- Compatible models
- B0372 · B0375 · B0685 · B0686
- Last updated
Registers (4)
2 read, 3 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Status Registers | Read and write | ||||
| Address | Read | ||||
| Temperature Setpoint | Write | ||||
| Temperature Ambiente | Write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Monitor the operating status of Olimpia Splendid heating and cooling units on a live cloud dashboard.
- Adjust temperature setpoints remotely without requiring an on-site visit to the installation.
- Create an alert when ambient temperature deviates from the configured setpoint for a defined period.
- Log historical temperature and status data to identify trends and optimize comfort settings.
- Verify correct device communication after initial installation by checking status registers in real time.
Installation
Wire the ModbusCloud Gateway RS-485 output to the Cel-Mar ADA-4040PC1 Modbus ASCII to RTU converter.
Connect the Cel-Mar ADA-4040PC1 converter output to the Olimpia Splendid B0686 electronics board using the appropriate RS-485 cabling.
Configure the baud rate to 9600 and parity to odd on the gateway, the converter, and the B0686 electronics to ensure all devices match.
Set the correct Modbus device address on the Olimpia Splendid unit, ensuring it does not conflict with other devices on the bus.
Import the Olimpia Splendid template in the ModbusCloud platform and assign it to the configured gateway and device address.
Verify communication by checking that status registers and ambient temperature values appear correctly on the ModbusCloud dashboard.
Things to watch for
Why does the gateway fail to communicate with the Olimpia Splendid unit directly over RS-485?
The B0686 electronics use Modbus ASCII, not Modbus RTU. You must install a Cel-Mar ADA-4040PC1 converter between the gateway and the B0686 board to translate between the two protocols.
What baud rate and parity settings should I use?
Set all devices on the bus to 9600 baud with odd parity. This includes the ModbusCloud gateway, the Cel-Mar converter, and the B0686 electronics.
Which Olimpia Splendid models are supported by this template?
The template supports models B0372, B0375, and B0685. The B0686 is the electronics communication board used by these units, not a standalone model.
Can I control multiple Olimpia Splendid units on the same RS-485 bus?
Yes, as long as each unit has a unique Modbus device address. Ensure all units share the same baud rate and parity settings on the bus.
Want to see how it works?