Pichler PKOM4

Heat pump combination unit for ventilation, heating, cooling and hot water in low energy homes.

The Pichler PKOM4 is a heat pump combination unit that ventilates, heats, cools and produces hot water in low energy and passive houses. This Modbus RTU template reads all temperatures, air flows, power, energy and errors and lets you write the operating mode, room and hot water setpoints and ventilation level from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
93, read and write
Brand
Pichler
Key readings
Room temperature · Supply and extract air temperature · Outdoor air temperature · Hot water tank temperature · Air flow · Electrical power · COP · CO2 and humidity
Available commands
Operating mode · Room setpoints · Hot water setpoint · Ventilation level
Compatible models
PKOM4
Last updated

Registers (93)

93 read, 50 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Operating ModeRead and write
Room Temperature MeasurementRead and write
Auto Summer/winter Changeover°CRead and write
Active CoolingRead and write
Setpoint Room Normal°CRead and write
Setpoint Room Lowered°CRead and write
Setpoint Room Vacation°CRead and write
Room SensorRead and write
Setpoint Room Active Cooling°CRead and write
Min. ODA Temp. To Enable Cooling°CRead and write
Automatic Room TemperatureRead and write
SUP Setting Ventilation Level 1m³/hRead and write
SUP Setting Ventilation Level 2m³/hRead and write
SUP Setting Ventilation Level 3m³/hRead and write
SUP Setting Ventilation Level 4m³/hRead and write
ETA BalanceRead and write
Selected Ventilation LevelRead and write
Min. SUP Temperature Cooling°CRead and write
Max. SUP Temperature Heating°CRead and write
CO2 Concentration To HighppmRead and write
Relative Humidity To High%RHRead and write
Relative Humidity To Low%RHRead and write
Max. Control Voltage Duct HeaterVRead and write
Setpoint DHW°CRead and write
Setpoint DHW - Ecotarif°CRead and write
E-heater DHWRead and write
Eco TarifRead and write
Legionella Protection FunctionRead and write
Legionella Protection IntervalRead and write
Setpoint Room Temp. Heating Circuit°CRead and write
Max. ODA Temperature To Enable Heating°CRead and write
Reset ErrorsRead and write
Operating Hours DHW_compressorhRead and write
Operating Hours HC_compressorhRead and write
Operating Hours ETA FanhRead and write
Operating Hours ODA FanhRead and write
Operating Hours K5hRead and write
Operating Hours E-heaterhRead and write
Operating Hours 4-way ValvehRead and write
Operating Hours Filter AUL & ABLhRead and write
DHW ReleaseRead and write
DHW Timer Start HourRead and write
DHW Timer Start MinuteRead and write
DHW Timer Stop HourRead and write
DHW Timer Stop MinuteRead and write
Heating Circuit ReleaseRead and write
Heating Circuit Timer Start HourRead and write
Heating Circuit Timer Start MinuteRead and write
Heating Circuit Timer Stop HourRead and write
Heating Circuit Timer Stop MinuteRead and write
Act. Fan Speed ETArpmRead
Act. Fan Speed ODArpmRead
Act. Room Temperature°CRead
Air Flow SUPm³/hRead
Air Flow ETAm³/hRead
Electr. Power DHW Comp.WRead
Electr. Power HC Comp.WRead
Electr. Power PCB+FansWRead
Cooling Energy 12 MonthskWhRead
T2 Display°CRead
Ventilation Energy 12 MonthskWhRead
Booster E-heater Remaining TimeminRead
Error Bits 0 To 15Read
Error Bits 16 To 31Read
Error Bits 32 To 47Read
Error Bits 48 To 63Read
Heating CapacityWRead
DHW Energy 12 MonthskWhRead
SCOP Heat Pump 12 MonthsRead
COP ActualRead
PV InputRead
Heating Energy 12 MonthskWhRead
Energy Consumption 12 MonthskWhRead
T1 Supply Air°CRead
T3 Outdoor Air°CRead
T4 Exhaust Air°CRead
T7 Extract Air°CRead
T9 Duct Heater/solar Collector°CRead
T20 DHW Tank Temperature°CRead
T21 DHW Tank Temperature°CRead
Status RelaisRead
Act. Capacity Compressor HC%Read
Status SystemRead
Status Fan ODARead
Act. Ventilation Level SUPRead
Active Setpoint Room Temperature°CRead
Status Fan ETARead
Active Setpoint DHW°CRead
Status BypassRead
T40 Sensor External°CRead
CO2 ConcentrationppmRead
Relative Humidity%RHRead
External Pump%Read

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show room, supply air and tank temperatures with the air flows of a PKOM4 on one dashboard.
  • Send an email alert when one of the error words changes from zero.
  • Keep 365 days of history of COP and energy for heating and hot water to check the heat pump.
  • Change the operating mode or room setpoint remotely when residents are away on vacation.
  • Raise the ventilation level when the CO2 value stays above the threshold you set.

Installation

  1. Connect RS485 A and B of the PKOM4 to the RS485 port of the ModbusCloud Gateway and terminate both ends of the bus.

  2. Check address, baud rate and parity in parameters 208 to 210 on the unit; from the factory it uses address 41, 19200 baud and even parity.

  3. In ModbusCloud, add a Modbus device on the Gateway with the same address and serial settings, then import this template.

  4. Check that the room temperature, outdoor air temperature and air flows arrive with plausible values.

Things to watch for

The PKOM4 does not answer on the RS485 bus. What should I check?

From the factory the unit answers on address 41, not 1, at 19200 baud with even parity. Match these settings, swap A and B if nothing comes back, and terminate only the two ends of the bus.

Why do temperatures look a hundred times too large?

Temperatures and temperature setpoints are sent with two decimals, so 2150 means 21.50 °C. The template applies that scale. If a value still looks wrong, check that the register uses the scale from the template and was not changed by hand.

Which registers can I write from ModbusCloud?

All setpoints in the holding registers: operating mode, room and hot water setpoints, ventilation levels and air volumes, thresholds, timers and the error reset. Stay inside the range given in each register comment and read the value back after writing.

How do I see which error is active?

Four registers hold 64 error bits, 16 per register. A value of zero means no error. The meaning of each bit is shown on the unit display; set an alert on any value above zero so you know when to look.

Can several units share one RS485 line?

Yes. Give every unit its own address with parameter 208 and use the same baud rate and parity on all devices. Run the bus as one line and terminate both ends.

Want to see how it works?