Regin Corrigo Ventilation

Air handling unit controller for supply and extract air, fans, heating, cooling and heat recovery.

The Regin Corrigo is a configurable controller that runs air handling units: fans, heating, cooling, heat recovery and dampers in commercial buildings. This Modbus RTU template reads temperatures, fan pressures and flows, CO2, humidity and every alarm, and lets you write setpoints, running modes, schedules and alarm limits from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
1000, read and write
Brand
Regin
Key readings
Supply air temperature · Extract air temperature · Outdoor temperature · Fan pressure and air flow · CO2 concentration · Run mode · Alarm status
Available commands
Supply air setpoint · Fan pressure and flow setpoints · Running mode · Time schedules · Alarm limits and delays · Alarm acknowledge
Compatible models
Corrigo E81-3 · Corrigo E81D-3 · Corrigo E151-3 · Corrigo E151D-3 · Corrigo E281-3 · Corrigo E281D-3 · Corrigo E151W-3 · Corrigo E151DW-3 · Corrigo E152W-3 · Corrigo E152DW-3 · Corrigo E281W-3 · Corrigo E281DW-3 · Corrigo E282W-3 · Corrigo E282DW-3 · Corrigo E283W-3 · Corrigo E283DW-3
Last updated

Registers (1000)

1000 read, 427 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Outdoor Temperature°CRead
Efficiency in % for Exchanger%Read
Run ModeRead
Running Time Supply Air FanhRead
Running Time Extract Air FanhRead
Number of Minutes Extended OperationminRead
Supply Air Temperature°CRead
Calculated Setpoint Supply Air Temperature when Outdoor°CRead
Extract Air Temperature°CRead
Room Temperature 1°CRead
Room Temperature 2°CRead
Number of Minutes in Ongoing Support Heating/coolingminRead
Supply Air Fan PressurePaRead
Extract Air Fan PressurePaRead
Supply Air Fan Flowm³/hRead
Extract Air Fan Flowm³/hRead
CO2ppmRead
Number of Minutes Support Run Time CO2minRead
Frost Protection Temperature°CRead
Exhaust Air Temperature°CRead
De-icing Temperature Exchanger°CRead
Minutes of Ongoing De-icingminRead
Humidity Room%RHRead
Humidity Duct%RHRead
Extra Sensor 1/External Setpoint Sensor/ External SetpointRead
AI1 ValueRead
AI2 ValueRead
AI3 ValueRead
AI4 ValueRead
UAI1 ValueRead
UAI2 ValueRead
UAI3 ValueRead
UAI4 ValueRead
Signal on AI1Read
Signal on AI2Read
Signal on AI3Read
Signal on AI4Read
Signal on UAI1Read
Signal on UAI2Read
Signal on UAI3Read
Signal on UAI4Read
Signal on DI1Read
Signal on DI2Read
Signal on DI3Read
Signal on DI4Read
Signal on DI5Read
Signal on DI6Read
Signal on DI7Read
Signal on DI8Read
Signal on UDI1Read
Signal on UDI2Read
Signal on UDI3Read
Signal on UDI4Read
AO1 ValueRead
AO2 ValueRead
AO3 ValueRead
AO4 ValueRead
AO5 ValueRead
Signal on AO1Read
Signal on AO2Read
Signal on AO3Read
Signal on AO4Read
Signal on AO5Read
Signal on DO1Read
Signal on DO2Read
Signal on DO3Read
Signal on DO4Read
Signal on DO5Read
Signal on DO6Read
Signal on DO7Read
Alarm Status Supply Air Fan MalfunctionRead
Alarm Status Extract Air Fan MalfunctionRead
Alarm Status P1 Heater MalfunctionRead
Alarm Status P1 Cooler MalfunctionRead
Alarm Status P1 Exchanger MalfunctionRead
Alarm Status Filter Guard 1Read
Alarm Status Flow GuardRead
Alarm Status External Frost GuardRead
Alarm Status Deicing Pressure GuardRead
Alarm Status Fire AlarmRead
Alarm Status External SwitchRead
Alarm Status External AlarmRead
Alarm Status Supply Air Control ErrorRead
Alarm Status Humidity Control ErrorRead
Alarm Status High Supply Air TempRead
Alarm Status Low Supply Air TempRead
Alarm Status Supply Air Fan Max LimitRead
Alarm Status Supply Air Fan Min LimitRead
Alarm Status High Room TempRead
Alarm Status Low Room TempRead
Alarm Status High Extract Air TempRead
Alarm Status Low Extract Air TempRead
Alarm Status Electric Heating is OverheatedRead
Alarm Status Frost RiskRead
Alarm Status Low Frost Guard TempRead
Alarm Status Low EfficiencyRead
Alarm Status Sensor Error Outdoor TempRead
Alarm Status Analogue DeicingRead
Alarm Status Rotation Guard ExchangerRead
Alarm Status Fire Damper MalfunctionRead
Alarm Status Supply Air Fan Control ErrorRead
Alarm Status Extract Air Fan Control ErrorRead
Alarm Status Supply Air Fan External OperationRead
Alarm Status Extract Air Fan External OperationRead
Alarm Status Ventilation Manual ModeRead
Alarm Status Manual Supply Air ControlRead
Alarm Status Manual Supply Air Fan ModeRead
Alarm Status Manual Supply Air Fan Freq. ControlRead
Alarm Status Manual Extract Air Fan ModeRead
Alarm Status Manual Extract Air Fan Freq. ControlRead
Alarm Status Manual Heater ControlRead
Alarm Status Manual Exchanger ControlRead
Alarm Status Manual Cooler ControlRead
Alarm Status Manual P1 HeaterRead
Alarm Status Manual P1 ExchangerRead
Alarm Status Manual P1 CoolerRead
Alarm Status Manual Fire DamperRead
Alarm Status Internal Battery ErrorRead
Control Signal Heating Y1VRead
Control Signal Exchanger Y2Read
Control Signal Cooler Y3VRead
Control Signal Supply Air FanVRead
Control Signal Extract Air FanVRead
Control Signal HumidityVRead
Control Signal SplitVRead
Supply Controller Output%Read
Extract Controller Output%Read
SAF Controller Output%Read
EAF Controller Output%Read
Frost Protection Controller Output if Ventilation Unit%Read
CO2 Controller Output%Read
Room Controller Output%Read
De-icing Controller Output%Read
Humidity Controller Output%Read
Room Temperature 1 and 2°CRead
Alarm Status Sensor Error Supply Air TempRead
Alarm Status Sensor Error Extract Air TempRead
Alarm Status Sensor Error Room Temp. 1Read
Alarm Status Sensor Error Room Temp. 2Read
Alarm Status Sensor Error Extract Air Temp Pt53Read
Alarm Status Sensor Error Extra SensorRead
Alarm Status Sensor Error SAF PressureRead
Alarm Status Sensor Error EAF PressureRead
Alarm Status Sensor Error Deicing TempRead
Alarm Status Sensor Error Frost Protection TempRead
Alarm Status Sensor Error CO2Read
Alarm Status Sensor Error Humidity RoomRead
Alarm Status Sensor Error Humidity DuctRead
Extra Unit Temp°CRead
External SAF Signal Control%Read
External EAF Signal Control%Read
Transmitter 2 Supply AirPaRead
Counted Air Flow Supply Air 2m³/hRead
Humidity Outdoor%RHRead
Alarm Status Sensor Error Extra Unit TempRead
Alarm Status Sensor Error External Control SAFRead
Alarm Status Sensor Error External Control EAFRead
Alarm Status Sensor Error SAF Pressure 2Read
Alarm Status Sensor Error Outdoor HumidityRead
Alarm Status Sensor Error Intake TempRead
Alarm Status Sensor Error Extra SAF PressureRead
Alarm Status Sensor Error Extra EAF PressureRead
Alarm Status Sensor Error Filter Guard 1Read
Alarm Status Sensor Error Filter Guard 2Read
Alarm Status Sensor Error Exchanger PressureRead
Alarm Status Alarm Frequency Converter SAFRead
Alarm Status Alarm Frequency Converter EAFRead
Alarm Status Communication Error Frequency SAFRead
Alarm Status Communication Error Frequency EAFRead
Alarm Status Communication Error Expansion Unit 1Read
Alarm Status Communication Error Expansion Unit 2Read
Alarm Status Warning Frequency Converter SAFRead
Alarm Status Warning Frequency Converter EAFRead
Alarm Status Output in Manual ModeRead
Alarm Status Time for ServiceRead
Alarm Status Y4 Extra Sequence Control ManualRead
AI1 Exp.Unit 1 ValueRead
AI2 Exp.Unit 1 ValueRead
AI3 Exp.Unit 1 ValueRead
AI4 Exp.Unit 1 ValueRead
UAI1 Exp.Unit 1 ValueRead
UAI2 Exp.Unit 1 ValueRead
UAI3 Exp.Unit 1 ValueRead
UAI3 Exp.Unit 1 Value ActualRead
AI1 Exp.Unit 2 ValueRead
AI2 Exp.Unit 2 ValueRead
AI3 Exp.Unit 2 ValueRead
AI4 Exp.Unit 2 ValueRead
UAI1 Exp.Unit 2 ValueRead
UAI2 Exp.Unit 2 ValueRead
UAI3 Exp.Unit 2 ValueRead
UAI3 Exp.Unit 2 Value ActualRead
Signal on AI1 Exp. Unit 1Read
Signal on AI2 Exp. Unit 1Read
Signal on AI3 Exp. Unit 1Read
Signal on AI4 Exp. Unit 1Read
Signal on UAI1 Exp. Unit 1Read
Signal on UAI2 Exp. Unit 1Read
Signal on UAI3 Exp. Unit 1Read
Signal on UAI4 Exp. Unit 1Read
Signal on AI1 Exp. Unit 2Read
Signal on AI2 Exp. Unit 2Read
Signal on AI3 Exp. Unit 2Read
Signal on AI4 Exp. Unit 2Read
Signal on UAI1 Exp. Unit 2Read
Signal on UAI2 Exp. Unit 2Read
Signal on UAI3 Exp. Unit 2Read
Signal on UAI4 Exp. Unit 2Read
Signal on DI1 Exp. Unit 1Read
Signal on DI2 Exp. Unit 1Read
Signal on DI3 Exp. Unit 1Read
Signal on DI4 Exp. Unit 1Read
Signal on DI5 Exp. Unit 1Read
Signal on DI6 Exp. Unit 1Read
Signal on DI7 Exp. Unit 1Read
Signal on DI8 Exp. Unit 1Read
Signal on UDI1 Exp. Unit 1Read
Signal on UDI2 Exp. Unit 1Read
Signal on UDI3 Exp. Unit 1Read
Signal on UDI4 Exp. Unit 1Read
Signal on DI1 Exp. Unit 2Read
Signal on DI2 Exp. Unit 2Read
Signal on DI3 Exp. Unit 2Read
Signal on DI4 Exp. Unit 2Read
Signal on DI5 Exp. Unit 2Read
Signal on DI6 Exp. Unit 2Read
Signal on DI7 Exp. Unit 2Read
Signal on DI8 Exp. Unit 2Read
Signal on UDI1 Exp. Unit 2Read
Signal on UDI2 Exp. Unit 2Read
Signal on UDI3 Exp. Unit 2Read
Signal on UDI4 Exp. Unit 2Read
AO1 Exp. Unit 1 ValueRead
AO2 Exp. Unit 1 ValueRead
AO3 Exp. Unit 1 ValueRead
AO4 Exp. Unit 1 ValueRead
AO5 Exp. Unit 1 ValueRead
AO1 Exp. Unit 2 ValueRead
AO2 Exp. Unit 2 ValueRead
AO3 Exp. Unit 2 ValueRead
AO4 Exp. Unit 2 ValueRead
AO5 Exp. Unit 2 ValueRead
Signal on AO1 Exp. Unit 1Read
Signal on AO2 Exp. Unit 1Read
Signal on AO3 Exp. Unit 1Read
Signal on AO4 Exp. Unit 1Read
Signal on AO5 Exp. Unit 1Read
Signal on AO1 Exp. Unit 2Read
Signal on AO2 Exp. Unit 2Read
Signal on AO3 Exp. Unit 2Read
Signal on AO4 Exp. Unit 2Read
Signal on AO5 Exp. Unit 2Read
Signal on DO1 Exp. Unit 1Read
Signal on DO2 Exp. Unit 1Read
Signal on DO3 Exp. Unit 1Read
Signal on DO4 Exp. Unit 1Read
Signal on DO5 Exp. Unit 1Read
Signal on DO6 Exp. Unit 1Read
Signal on DO7 Exp. Unit 1Read
Signal on DO1 Exp. Unit 2Read
Signal on DO2 Exp. Unit 2Read
Signal on DO3 Exp. Unit 2Read
Signal on DO4 Exp. Unit 2Read
Signal on DO5 Exp. Unit 2Read
Signal on DO6 Exp. Unit 2Read
Signal on DO7 Exp. Unit 2Read
SAF Motor Speed HzHzRead
SAF Motor CurrentARead
SAF Motor Power % of Nominal%Read
SAF Accumulated Power ConsumptionRead
EAF Motor Speed HzHzRead
EAF Motor CurrentARead
EAF Motor Power % of Nominal%Read
EAF Accumulated Power ConsuptionRead
Control Signal Extra UnitVRead
Extra Unit Controller Output%Read
Control Signal Heating or Cooling Controlled by ChangeoverVRead
Control Signal Extra Sequence Y4 AnalogueVRead
Unit Run ModeRead
Alarm Status Restart Blocked After Power-onRead
Intake Air Temperature°CRead
Extrasensor 2 Temperature°CRead
Extrasensor 3 Temperature°CRead
Extrasensor 4 Temperature°CRead
Extrasensor 5 Temperature°CRead
Extrasensor SAF PressureRead
Extrasensor EAF PressureRead
Extrasensor SAF FlowRead
Extrasensor EAF FlowRead
External Setpoint SAF Airflowm³/hRead
Control Valve Extra Sequence Y5VRead
Alarm Status Y5 Extra Sequence Control ManualRead
SFP ActualRead
SFP Day AverageRead
SFP Month AverageRead
Analogue Filter 1 ValuePaRead
Analogue Filter 2 ValuePaRead
Alarm Status Filter Guard 2Read
Alarm Status High Temp Extra Sensor 1Read
Alarm Status Low Temp Extra Sensor 1Read
Alarm Status High Temp Extra Sensor 2Read
Alarm Status Low Temp Extra Sensor 2Read
Alarm Status High Temp Extra Sensor 3Read
Alarm Status Low Temp Extra Sensor 3Read
Alarm Status High Temp Extra Sensor 4Read
Alarm Status Low Temp Extra Sensor 4Read
Alarm Status High Temp Extra Sensor 5Read
Alarm Status Low Temp Extra Sensor 5Read
Alarm Status Extra Alarm 1Read
Alarm Status Extra Alarm 2Read
Alarm Status Extra Alarm 3Read
Alarm Status Extra Alarm 4Read
Alarm Status Extra Alarm 5Read
Alarm Status Extra Alarm 6Read
Alarm Status Extra Alarm 7Read
Alarm Status Extra Alarm 8Read
Alarm Status Extra Alarm 9Read
Alarm Status Extra Alarm 10Read
Alarm Status Extra Unit in Manual ModeRead
Alarm Status Malfunction Motor Control 1Read
Alarm Status Malfunction Motor Control 2Read
Alarm Status Motor Control 1 External OperationRead
Alarm Status Motor Control 2 External OperationRead
Temperature Efficiency SensorRead
Temperature Output SignalRead
Total Calculated Power ConsumptionkWRead
Alarm Status Motor Control 1 in Manual ModeRead
Alarm Status Motor Control 2 in Manual ModeRead
Alarm Status Communication Error Expansion Unit 3Read
Alarm Status Communication Error Expansion Unit 4Read
Alarm Status Low Outdoor Air TempRead
Alarm Status High Outdoor Air TempRead
Alarm Status Malfunction Adiabatic CoolingRead
Alarm Status Communication Error Expansion Unit 5Read
Alarm Status Communication Error Expansion Unit 6Read
Exchanger PressureRead
UAI1 Exp.Unit 3 ValueRead
UAI2 Exp.Unit 3 ValueRead
Pressure A Exp.Unit 3 ValueRead
Pressure B Exp.Unit 3 ValueRead
UAI1 Exp.Unit 4 ValueRead
UAI2 Exp.Unit 4 ValueRead
Pressure A Exp.Unit 4 ValueRead
Pressure B Exp.Unit 4 ValueRead
UAI1 Exp.Unit 5 ValueRead
UAI2 Exp.Unit 5 ValueRead
Pressure A Exp.Unit 5 ValueRead
Pressure B Exp.Unit 5 ValueRead
UAI1 Exp.Unit 6 ValueRead
UAI2 Exp.Unit 6 ValueRead
Pressure A Exp.Unit 6 ValueRead
Pressure B Exp.Unit 6 ValueRead
Exchanger Air FlowRead
Set if Timechannel Full Speed is ActiveRead
Set if Timechannel Reduced Speed is ActiveRead
Set if Timer Output 1 is ActiveRead
Set if Timer Output 2 is ActiveRead
Set if Timer Output 3 is ActiveRead
Set if Timer Output 4 is ActiveRead
Set if Timer Output 5 is ActiveRead
Set if Extended Operation Full SpeedRead
Set if Extended Operation Half SpeedRead
Set if Ongoing Support HeatingRead
Set if Ongoing Support CoolingRead
Set if Ongoing Support CO2Read
Set if Ongoing De-icingRead
DI1 ValueRead
DI2 ValueRead
DI3 ValueRead
DI4 ValueRead
DI5 ValueRead
DI6 ValueRead
DI7 ValueRead
DI8 ValueRead
UDI1 ValueRead
UDI2 ValueRead
UDI3 ValueRead
UDI4 ValueRead
DO1 ValueRead
DO2 ValueRead
DO3 ValueRead
DO4 ValueRead
DO5 ValueRead
DO6 ValueRead
DO7 ValueRead
Alarm Supply Air Fan MalfunctionRead
Alarm Extract Air Fan MalfunctionRead
Alarm P1 Heater MalfunctionRead
Alarm P1 Cooler MalfunctionRead
Alarm P1 Exchanger MalfunctionRead
Alarm Filter Guard 1Read
Alarm Flow GuardRead
Alarm External Frost GuardRead
Alarm Deicing Pressure GuardRead
Alarm Fire AlarmRead
Alarm External SwitchRead
Alarm External AlarmRead
Alarm Supply Air Control ErrorRead
Alarm Humidity Control ErrorRead
Alarm High Supply Air TempRead
Alarm Low Supply Air TempRead
Alarm Supply Air Fan Max LimitRead
Alarm Supply Air Fan Min LimitRead
Alarm High Room TempRead
Alarm Low Room TempRead
Alarm High Extract Air TempRead
Alarm Low Extract Air TempRead
Alarm Electric Heating is OverheatedRead
Alarm Frost RiskRead
Alarm Low Frost Guard TempRead
Alarm Low EfficiencyRead
Alarm Sensor Error Outdoor TempRead
Alarm Analogue DeicingRead
Alarm Rotation Guard ExchangerRead
Alarm Fire Damper MalfunctionRead
Alarm Supply Air Fan Control ErrorRead
Alarm Extract Air Fan Control ErrorRead
Alarm Supply Air Fan External OperationRead
Alarm Extract Air Fan External OperationRead
Alarm Ventilation Manual ModeRead
Alarm Manual Supply Air ControlRead
Alarm Manual Supply Air Fan ModeRead
Alarm Manual Supply Air Fan Freq. ControlRead
Alarm Manual Extract Air Fan ModeRead
Alarm Manual Extract Air Fan Freq. ControlRead
Alarm Manual Heater ControlRead
Alarm Manual Exchanger ControlRead
Alarm Manual Cooler ControlRead
Alarm Manual P1 HeaterRead
Alarm Manual P1 ExchangerRead
Alarm Manual P1 CoolerRead
Alarm Manual Fire DamperRead
Alarm Internal Battery ErrorRead
Start Signal Full Speed Supply Air FanRead
Start Signal Full Speed Extract Air FanRead
Start Signal Half Speed Supply Air FanRead
Start Signal Half Speed Extract Air FanRead
Start Signal Heat PumpRead
Start Signal ExchangerRead
Start Signal Cool PumpRead
Start Signal Frequencer Supply Air FanRead
Start Signal Frequencer Extract Air FanRead
Alarm Sensor Error Supply Air TempRead
Alarm Sensor Error Extract Air TempRead
Alarm Sensor Error Room Temp. 1Read
Alarm Sensor Error Room Temp. 2Read
Alarm Sensor Error Extract Air Temp Pt53Read
Alarm Sensor Error Extra SensorRead
Alarm Sensor Error SAF PressureRead
Alarm Sensor Error EAF PressureRead
Alarm Sensor Error Deicing TempRead
Alarm Sensor Error Frost Protection TempRead
Alarm Sensor Error CO2Read
Alarm Sensor Error Humidity RoomRead
Alarm Sensor Error Humidity DuctRead
Alarm Sensor Error Extra Unit TempRead
Alarm Sensor Error External Control SAFRead
Alarm Sensor Error External Control EAFRead
Alarm Sensor Error SAF Pressure 2Read
Alarm Sensor Error Outdoor HumidityRead
Alarm Sensor Error Intake TempRead
Alarm Sensor Error Extra SAF PressureRead
Alarm Sensor Error Extra EAF PressureRead
Alarm Sensor Error Filter Guard 1Read
Alarm Sensor Error Filter Guard 2Read
Alarm Sensor Error Exchanger PressureRead
Alarm Alarm Frequency Converter SAFRead
Alarm Alarm Frequency Converter EAFRead
Alarm Communication Error Frequency SAFRead
Alarm Communication Error Frequency EAFRead
Alarm Communication Error Expansion Unit 1Read
Alarm Communication Error Expansion Unit 2Read
Alarm Warning Frequency Converter SAFRead
Alarm Warning Frequency Converter EAFRead
Alarm Output in Manual ModeRead
Alarm Time for ServiceRead
Alarm Y4 Extra Sequence Control ManualRead
Alarm Restart Blocked After Power-onRead
Alarm Y5 Extra Sequence Control ManualRead
Alarm Filter Guard 2Read
Alarm High Temp Extra Sensor 1Read
Alarm Low Temp Extra Sensor 1Read
Alarm High Temp Extra Sensor 2Read
Alarm Low Temp Extra Sensor 2Read
Alarm High Temp Extra Sensor 3Read
Alarm Low Temp Extra Sensor 3Read
Alarm High Temp Extra Sensor 4Read
Alarm Low Temp Extra Sensor 4Read
Alarm High Temp Extra Sensor 5Read
Alarm Low Temp Extra Sensor 5Read
DI1 Expansion Unit 1 ValueRead
DI2 Expansion Unit 1 ValueRead
DI3 Expansion Unit 1 ValueRead
DI4 Expansion Unit 1 ValueRead
DI5 Expansion Unit 1 ValueRead
DI6 Expansion Unit 1 ValueRead
DI7 Expansion Unit 1 ValueRead
DI8 Expansion Unit 1 ValueRead
UDI1 Expansion Unit 1 ValueRead
UDI2 Expansion Unit 1 ValueRead
UD3 Expansion Unit 1 ValueRead
UD4 Expansion Unit 1 ValueRead
DO1 Expansion Unit 1 ValueRead
DO2 Expansion Unit 1 ValueRead
DO3 Expansion Unit 1 ValueRead
DO4 Expansion Unit 1 ValueRead
DO5 Expansion Unit 1 ValueRead
DO6 Expansion Unit 1 ValueRead
DO7 Expansion Unit 1 ValueRead
DI1 Expansion Unit 2 ValueRead
DI2 Expansion Unit 2 ValueRead
DI3 Expansion Unit 2 ValueRead
DI4 Expansion Unit 2 ValueRead
DI5 Expansion Unit 2 ValueRead
DI6 Expansion Unit 2 ValueRead
DI7 Expansion Unit 2 ValueRead
DI8 Expansion Unit 2 ValueRead
UDI1 Expansion Unit 2 ValueRead
UDI2 Expansion Unit 2 ValueRead
UDI3 Expansion Unit 2 ValueRead
UDI4 Expansion Unit 2 ValueRead
DO1 Expansion Unit 2 ValueRead
DO2 Expansion Unit 2 ValueRead
DO3 Expansion Unit 2 ValueRead
DO4 Expansion Unit 2 ValueRead
DO5 Expansion Unit 2 ValueRead
DO6 Expansion Unit 2 ValueRead
DO7 Expansion Unit 2 ValueRead
Recirculation Run ActiveRead
Sum AlarmRead
A-alarmRead
B-alarmRead
Alarm Extra Alarm 1Read
Alarm Extra Alarm 2Read
Alarm Extra Alarm 3Read
Alarm Extra Alarm 4Read
Alarm Extra Alarm 5Read
Alarm Extra Alarm 6Read
Alarm Extra Alarm 7Read
Alarm Extra Alarm 8Read
Alarm Extra Alarm 9Read
Alarm Extra Alarm 10Read
Alarm Extra Unit in Manual ModeRead
Alarm Malfunction Motor Control 1Read
Alarm Malfunction Motor Control 2Read
Alarm Motor Control 1 External OperationRead
Alarm Motor Control 2 External OperationRead
Alarm Motor Control 1 in Manual ModeRead
Alarm Motor Control 2 in Manual ModeRead
Alarm Communication Error Expansion Unit 3Read
Alarm Communication Error Expansion Unit 4Read
Alarm Low Outdoor Air TempRead
Alarm High Outdoor Air TempRead
Alarm Malfunction Adiabatic CoolingRead
Alarm Communication Error Expansion Unit 5Read
Alarm Communication Error Expansion Unit 6Read
UDI1 Expansion Unit 3 ValueRead
UDI2 Expansion Unit 3 ValueRead
UDI1 Expansion Unit 4 ValueRead
UDI2 Expansion Unit 4 ValueRead
UDI1 Expansion Unit 5 ValueRead
UDI2 Expansion Unit 5 ValueRead
UDI1 Expansion Unit 6 ValueRead
UDI2 Expansion Unit 6 ValueRead
Setpoint Supply Air Temperature°CRead and write
Outdoor Temp for First Curve Point for Outdoor°CRead and write
Outdoor Temp for Second Curve Point for Outdoor°CRead and write
Outdoor Temp for Third Curve Point for Outdoor°CRead and write
Outdoor Temp for Fourth Curve Point for Outdoor°CRead and write
Outdoor Temp for Fifth Curve Point for Outdoor°CRead and write
Outdoor Temp for Sixth Curve Point for Outdoor°CRead and write
Outdoor Temp for Seventh Curve Point for Outdoor°CRead and write
Outdoor Temp for Eighth Curve Point for Outdoor°CRead and write
Setpoint for First Curve Point for Outdoor Compensated°CRead and write
Setpoint for Second Curve Point for Outdoor Compensated°CRead and write
Setpoint for Third Curve Point for Outdoor Compensated°CRead and write
Setpoint for Fourth Curve Point for Outdoor Compensated°CRead and write
Setpoint for Fifth Curve Point for Outdoor Compensated°CRead and write
Setpoint for Sixth Curve Point for Outdoor Compensated°CRead and write
Setpoint for Seventh Curve Point for Outdoor°CRead and write
Setpoint for Eight Curve Point for Outdoor Compensated°CRead and write
Setpoint Extract Air Temp if Extract Air Temp Control°CRead and write
Room Setpoint if Room Temp Control Function°CRead and write
Room Temp for Start the Unit if Intermittent Heating°CRead and write
Room Temp for Stop the Unit if Intermittent Heating°CRead and write
Room Temp for Start the Unit if Intermittent Cooling°CRead and write
Room Temp for Stop the Unit if Intermittent Cooling°CRead and write
Setpoint Full Speed Supply Air Fan PressurePaRead and write
Setpoint Reduced Speed Supply Air Fan PressurePaRead and write
Setpoint Full Speed Extract Air Fan PressurePaRead and write
Setpoint Reduced Speed Extract Air Fan PressurePaRead and write
Setpoint Full Speed Supply Air Fan Flowm³/hRead and write
Setpoint Reduced Speed Supply Air Fan Flowm³/hRead and write
Setpoint Full Speed Extract Air Fan Flowm³/hRead and write
Setpoint Reduced Speed Extract Air Fan Flowm³/hRead and write
Setpoint CO2ppmRead and write
Setpoint Frost Protection if the Ventilation Unit is Stopped°CRead and write
P-Gain Frost Protection when Running°CRead and write
Setpoint De-icing Temp°CRead and write
Hysteresis for Stop of De-icing°CRead and write
Setpoint Humidity Room%RHRead and write
Max Limit Humidity Duct%RHRead and write
Hysteresis to Start Humidity Control After Stop Max%RHRead and write
Start Time Period 1 Mon. Normal SpeedRead and write
Stop Time Period 1 Mon. Normal SpeedRead and write
Start Time Period 2 Mon. Normal SpeedRead and write
Stop Time Period 2 Mon. Normal SpeedRead and write
Start Time Period 1 Tue. Normal SpeedRead and write
Stop Time Period 1 Tue. Normal SpeedRead and write
Start Time Period 2 Tue. Normal SpeedRead and write
Stop Time Period 2 Tue. Normal SpeedRead and write
Start Time Period 1 Wed. Normal SpeedRead and write
Stop Time Period 1 Wed. Normal SpeedRead and write
Start Time Period 2 Wed. Normal SpeedRead and write
Stop Time Period 2 Wed. Normal SpeedRead and write
Start Time Period 1 Thu. Normal SpeedRead and write
Stop Time Period 1 Thu. Normal SpeedRead and write
Start Time Period 2 Thu. Normal SpeedRead and write
Stop Time Period 2 Thu. Normal SpeedRead and write
Start Time Period 1 Fri. Normal SpeedRead and write
Stop Time Period 1 Fri. Normal SpeedRead and write
Start Time Period 2 Fri. Normal SpeedRead and write
Stop Time Period 2 Fri. Normal SpeedRead and write
Start Time Period 1 Sat. Normal SpeedRead and write
Stop Time Period 1 Sat. Normal SpeedRead and write
Start Time Period 2 Sat. Normal SpeedRead and write
Stop Time Period 2 Sat. Normal SpeedRead and write
Start Time Period 1 Sun. Normal SpeedRead and write
Stop Time Period 1 Sun. Normal SpeedRead and write
Start Time Period 2 Sun. Normal SpeedRead and write
Stop Time Period 2 Sun. Normal SpeedRead and write
Start Time Period 1 Holiday Normal SpeedRead and write
Stop Time Period 1 Holiday Normal SpeedRead and write
Start Time Period 2 Holiday Normal SpeedRead and write
Stop Time Period 2 Holiday Normal SpeedRead and write
Start Time Period 1 Mon. Reduced SpeedRead and write
Stop Time Period 1 Mon. Reduced SpeedRead and write
Start Time Period 2 Mon. Reduced SpeedRead and write
Stop Time Period 2 Mon. Reduced SpeedRead and write
Start Time Period 1 Tue. Reduced SpeedRead and write
Stop Time Period 1 Tue. Reduced SpeedRead and write
Start Time Period 2 Tue. Reduced SpeedRead and write
Stop Time Period 2 Tue. Reduced SpeedRead and write
Start Time Period 1 Wed. Reduced SpeedRead and write
Stop Time Period 1 Wed. Reduced SpeedRead and write
Start Time Period 2 Wed. Reduced SpeedRead and write
Stop Time Period 2 Wed. Reduced SpeedRead and write
Start Time Period 1 Thu. Reduced SpeedRead and write
Stop Time Period 1 Thu. Reduced SpeedRead and write
Start Time Period 2 Thu. Reduced SpeedRead and write
Stop Time Period 2 Thu. Reduced SpeedRead and write
Start Time Period 1 Fri. Reduced SpeedRead and write
Stop Time Period 1 Fri. Reduced SpeedRead and write
Start Time Period 2 Fri. Reduced SpeedRead and write
Stop Time Period 2 Fri. Reduced SpeedRead and write
Start Time Period 1 Sat. Reduced SpeedRead and write
Stop Time Period 1 Sat. Reduced SpeedRead and write
Start Time Period 2 Sat. Reduced SpeedRead and write
Stop Time Period 2 Sat. Reduced SpeedRead and write
Start Time Period 1 Sun. Reduced SpeedRead and write
Stop Time Period 1 Sun. Reduced SpeedRead and write
Start Time Period 2 Sun. Reduced SpeedRead and write
Stop Time Period 2 Sun. Reduced SpeedRead and write
Start Time Period 1 Holiday Reduced SpeedRead and write
Stop Time Period 1 Holiday Reduced SpeedRead and write
Start Time Period 2 Holiday Reduced SpeedRead and write
Stop Time Period 2 Holiday Reduced SpeedRead and write
Start Time Period 1 Mon. Timer Output 1Read and write
Stop Time Period 1 Mon. Timer Output 1Read and write
Start Time Period 2 Mon. Timer Output 1Read and write
Stop Time Period 2 Mon. Timer Output 1Read and write
Start Time Period 1 Tue. Timer Output 1Read and write
Stop Time Period 1 Tue. Timer Output 1Read and write
Start Time Period 2 Tue. Timer Output 1Read and write
Stop Time Period 2 Tue. Timer Output 1Read and write
Start Time Period 1 Wed. Timer Output 1Read and write
Stop Time Period 1 Wed. Timer Output 1Read and write
Start Time Period 2 Wed. Timer Output 1Read and write
Stop Time Period 2 Wed. Timer Output 1Read and write
Start Time Period 1 Thu. Timer Output 1Read and write
Stop Time Period 1 Thu. Timer Output 1Read and write
Start Time Period 2 Thu. Timer Output 1Read and write
Stop Time Period 2 Thu. Timer Output 1Read and write
Start Time Period 1 Fri. Timer Output 1Read and write
Stop Time Period 1 Fri. Timer Output 1Read and write
Start Time Period 2 Fri. Timer Output 1Read and write
Stop Time Period 2 Fri. Timer Output 1Read and write
Start Time Period 1 Sat. Timer Output 1Read and write
Stop Time Period 1 Sat. Timer Output 1Read and write
Start Time Period 2 Sat. Timer Output 1Read and write
Stop Time Period 2 Sat. Timer Output 1Read and write
Start Time Period 1 Sun. Timer Output 1Read and write
Stop Time Period 1 Sun. Timer Output 1Read and write
Start Time Period 2 Sun. Timer Output 1Read and write
Stop Time Period 2 Sun. Timer Output 1Read and write
Start Time Period 1 Holiday Timer Output 1Read and write
Stop Time Period 1 Holiday Timer Output 1Read and write
Start Time Period 2 Holiday Timer Output 1Read and write
Stop Time Period 2 Holiday Timer Output 1Read and write
Start Time Period 1 Mon. Timer Output 2Read and write
Stop Time Period 1 Mon. Timer Output 2Read and write
Start Time Period 2 Mon. Timer Output 2Read and write
Stop Time Period 2 Mon. Timer Output 2Read and write
Start Time Period 1 Tue. Timer Output 2Read and write
Stop Time Period 1 Tue. Timer Output 2Read and write
Start Time Period 2 Tue. Timer Output 2Read and write
Stop Time Period 2 Tue. Timer Output 2Read and write
Start Time Period 1 Wed. Timer Output 2Read and write
Stop Time Period 1 Wed. Timer Output 2Read and write
Start Time Period 2 Wed. Timer Output 2Read and write
Stop Time Period 2 Wed. Timer Output 2Read and write
Start Time Period 1 Thu. Timer Output 2Read and write
Stop Time Period 1 Thu. Timer Output 2Read and write
Start Time Period 2 Thu. Timer Output 2Read and write
Stop Time Period 2 Thu. Timer Output 2Read and write
Start Time Period 1 Fri. Timer Output 2Read and write
Stop Time Period 1 Fri. Timer Output 2Read and write
Start Time Period 2 Fri. Timer Output 2Read and write
Stop Time Period 2 Fri. Timer Output 2Read and write
Start Time Period 1 Sat. Timer Output 2Read and write
Stop Time Period 1 Sat. Timer Output 2Read and write
Start Time Period 2 Sat. Timer Output 2Read and write
Stop Time Period 2 Sat. Timer Output 2Read and write
Start Time Period 1 Sun. Timer Output 2Read and write
Stop Time Period 1 Sun. Timer Output 2Read and write
Start Time Period 2 Sun. Timer Output 2Read and write
Stop Time Period 2 Sun. Timer Output 2Read and write
Start Time Period 1 Holiday Timer Output 2Read and write
Stop Time Period 1 Holiday Timer Output 2Read and write
Start Time Period 2 Holiday Timer Output 2Read and write
Stop Time Period 2 Holiday Timer Output 2Read and write
Start Time Period 1 Mon. Timer Output 3Read and write
Stop Time Period 1 Mon. Timer Output 3Read and write
Start Time Period 2 Mon. Timer Output 3Read and write
Stop Time Period 2 Mon. Timer Output 3Read and write
Start Time Period 1 Tue. Timer Output 3Read and write
Stop Time Period 1 Tue. Timer Output 3Read and write
Start Time Period 2 Tue. Timer Output 3Read and write
Stop Time Period 2 Tue. Timer Output 3Read and write
Start Time Period 1 Wed. Timer Output 3Read and write
Stop Time Period 1 Wed. Timer Output 3Read and write
Start Time Period 2 Wed. Timer Output 3Read and write
Stop Time Period 2 Wed. Timer Output 3Read and write
Start Time Period 1 Thu. Timer Output 3Read and write
Stop Time Period 1 Thu. Timer Output 3Read and write
Start Time Period 2 Thu. Timer Output 3Read and write
Stop Time Period 2 Thu. Timer Output 3Read and write
Start Time Period 1 Fri. Timer Output 3Read and write
Stop Time Period 1 Fri. Timer Output 3Read and write
Start Time Period 2 Fri. Timer Output 3Read and write
Stop Time Period 2 Fri. Timer Output 3Read and write
Start Time Period 1 Sat. Timer Output 3Read and write
Stop Time Period 1 Sat. Timer Output 3Read and write
Start Time Period 2 Sat. Timer Output 3Read and write
Stop Time Period 2 Sat. Timer Output 3Read and write
Start Time Period 1 Sun. Timer Output 3Read and write
Stop Time Period 1 Sun. Timer Output 3Read and write
Start Time Period 2 Sun. Timer Output 3Read and write
Stop Time Period 2 Sun. Timer Output 3Read and write
Start Time Period 1 Holiday Timer Output 3Read and write
Stop Time Period 1 Holiday Timer Output 3Read and write
Start Time Period 2 Holiday Timer Output 3Read and write
Stop Time Period 2 Holiday Timer Output 3Read and write
Start Time Period 1 Mon. Timer Output 4Read and write
Stop Time Period 1 Mon. Timer Output 4Read and write
Start Time Period 2 Mon. Timer Output 4Read and write
Stop Time Period 2 Mon. Timer Output 4Read and write
Start Time Period 1 Tue. Timer Output 4Read and write
Stop Time Period 1 Tue. Timer Output 4Read and write
Start Time Period 2 Tue. Timer Output 4Read and write
Stop Time Period 2 Tue. Timer Output 4Read and write
Start Time Period 1 Wed. Timer Output 4Read and write
Stop Time Period 1 Wed. Timer Output 4Read and write
Start Time Period 2 Wed. Timer Output 4Read and write
Stop Time Period 2 Wed. Timer Output 4Read and write
Start Time Period 1 Thu. Timer Output 4Read and write
Stop Time Period 1 Thu. Timer Output 4Read and write
Start Time Period 2 Thu. Timer Output 4Read and write
Stop Time Period 2 Thu. Timer Output 4Read and write
Start Time Period 1 Fri. Timer Output 4Read and write
Stop Time Period 1 Fri. Timer Output 4Read and write
Start Time Period 2 Fri. Timer Output 4Read and write
Stop Time Period 2 Fri. Timer Output 4Read and write
Start Time Period 1 Sat. Timer Output 4Read and write
Stop Time Period 1 Sat. Timer Output 4Read and write
Start Time Period 2 Sat. Timer Output 4Read and write
Stop Time Period 2 Sat. Timer Output 4Read and write
Start Time Period 1 Sun. Timer Output 4Read and write
Stop Time Period 1 Sun. Timer Output 4Read and write
Start Time Period 2 Sun. Timer Output 4Read and write
Stop Time Period 2 Sun. Timer Output 4Read and write
Start Time Period 1 Holiday Timer Output 4Read and write
Stop Time Period 1 Holiday Timer Output 4Read and write
Start Time Period 2 Holiday Timer Output 4Read and write
Stop Time Period 2 Holiday Timer Output 4Read and write
Start Time Period 1 Mon. Timer Output 5Read and write
Stop Time Period 1 Mon. Timer Output 5Read and write
Start Time Period 2 Mon. Timer Output 5Read and write
Stop Time Period 2 Mon. Timer Output 5Read and write
Start Time Period 1 Tue. Timer Output 5Read and write
Stop Time Period 1 Tue. Timer Output 5Read and write
Start Time Period 2 Tue. Timer Output 5Read and write
Stop Time Period 2 Tue. Timer Output 5Read and write
Start Time Period 1 Wed. Timer Output 5Read and write
Stop Time Period 1 Wed. Timer Output 5Read and write
Start Time Period 2 Wed. Timer Output 5Read and write
Stop Time Period 2 Wed. Timer Output 5Read and write
Start Time Period 1 Thu. Timer Output 5Read and write
Stop Time Period 1 Thu. Timer Output 5Read and write
Start Time Period 2 Thu. Timer Output 5Read and write
Stop Time Period 2 Thu. Timer Output 5Read and write
Start Time Period 1 Fri. Timer Output 5Read and write
Stop Time Period 1 Fri. Timer Output 5Read and write
Start Time Period 2 Fri. Timer Output 5Read and write
Stop Time Period 2 Fri. Timer Output 5Read and write
Start Time Period 1 Sat. Timer Output 5Read and write
Stop Time Period 1 Sat. Timer Output 5Read and write
Start Time Period 2 Sat. Timer Output 5Read and write
Stop Time Period 2 Sat. Timer Output 5Read and write
Start Time Period 1 Sun. Timer Output 5Read and write
Stop Time Period 1 Sun. Timer Output 5Read and write
Start Time Period 2 Sun. Timer Output 5Read and write
Stop Time Period 2 Sun. Timer Output 5Read and write
Start Time Period 1 Holiday Timer Output 5Read and write
Stop Time Period 1 Holiday Timer Output 5Read and write
Start Time Period 2 Holiday Timer Output 5Read and write
Stop Time Period 2 Holiday Timer Output 5Read and write
Start Date Holiday Period 1Read and write
End Date Holiday Period 1Read and write
Start Date Holiday Period 2Read and write
End Date Holiday Period 2Read and write
Start Date Holiday Period 3Read and write
End Date Holiday Period 3Read and write
Start Date Holiday Period 4Read and write
End Date Holiday Period 4Read and write
Start Date Holiday Period 5Read and write
End Date Holiday Period 5Read and write
Start Date Holiday Period 6Read and write
End Date Holiday Period 6Read and write
Start Date Holiday Period 7Read and write
End Date Holiday Period 7Read and write
Start Date Holiday Period 8Read and write
End Date Holiday Period 8Read and write
Start Date Holiday Period 9Read and write
End Date Holiday Period 9Read and write
Start Date Holiday Period 10Read and write
End Date Holiday Period 10Read and write
Start Date Holiday Period 11Read and write
End Date Holiday Period 11Read and write
Start Date Holiday Period 12Read and write
End Date Holiday Period 12Read and write
Start Date Holiday Period 13Read and write
End Date Holiday Period 13Read and write
Start Date Holiday Period 14Read and write
End Date Holiday Period 14Read and write
Start Date Holiday Period 15Read and write
End Date Holiday Period 15Read and write
Start Date Holiday Period 16Read and write
End Date Holiday Period 16Read and write
Start Date Holiday Period 17Read and write
End Date Holiday Period 17Read and write
Start Date Holiday Period 18Read and write
End Date Holiday Period 18Read and write
Start Date Holiday Period 19Read and write
End Date Holiday Period 19Read and write
Start Date Holiday Period 20Read and write
End Date Holiday Period 20Read and write
Start Date Holiday Period 21Read and write
End Date Holiday Period 21Read and write
Start Date Holiday Period 22Read and write
End Date Holiday Period 22Read and write
Start Date Holiday Period 23Read and write
End Date Holiday Period 23Read and write
Start Date Holiday Period 24Read and write
End Date Holiday Period 24Read and write
P-band Supply Air Control°CRead and write
I-time Supply Air ControlsRead and write
P-band Extract Air Control°CRead and write
I-time Extract Air ControlsRead and write
P-band Room Air Control°CRead and write
I-time Room Air ControlsRead and write
P-band Switchdown Mode°CRead and write
I-time Switchdown ModesRead and write
P-band De-icing°CRead and write
I-time De-icingsRead and write
P-band Pressure Control SAFPaRead and write
I-time Pressure Control SAFsRead and write
P-band Pressure Control EAFPaRead and write
I-time Pressure Control EAFsRead and write
P-band Flow Control SAFm³/hRead and write
I-time Flow Control SAFsRead and write
P-band Flow Control EAFm³/hRead and write
I-time Flow Control EAFsRead and write
P-band Humidity Control RH%Read and write
I-time Humidity ControlsRead and write
Max Control Deviation Supply Air Temp°CRead and write
High Alarm Limit Supply Air Temp°CRead and write
Low Alarm Limit Supply Air Temp°CRead and write
High Alarm Limit Extract Air Temp°CRead and write
Low Alarm Limit Extract Air Temp°CRead and write
High Alarm Limit Room Air Temp°CRead and write
Low Alarm Limit Room Air Temp°CRead and write
Alarm Limit Frost Protection°CRead and write
Max Control Deviation Pressure SAFPaRead and write
Max Control Deviation Pressure EAFPaRead and write
Low Efficiency%Read and write
Alarm Delay Control Deviation Supply Air TempminRead and write
Alarm Delay High Supply Air TempsRead and write
Alarm Delay Low Supply Air TempsRead and write
Alarm Delay High Extract Air TempminRead and write
Alarm Delay Low Extract Air TempminRead and write
Alarm Delay High Room Air TempminRead and write
Alarm Delay Low Alarm Room Air TempminRead and write
Alarm Delay Frost ProtectionsRead and write
Alarm Delay Max Control Deviation Pressure SAFminRead and write
Alarm Delay Max Control Deviation Pressure EAFminRead and write
Alarm Delay Low EfficiencyminRead and write
Alarm Delay Malfunction SAFsRead and write
Alarm Delay Malfunction EAFsRead and write
Alarm Delay Malfunction P1-HeatingsRead and write
Alarm Delay Malfunction P1-CoolingsRead and write
Alarm Delay Malfunction P1-ExchangersRead and write
Alarm Delay Filter MonitoringsRead and write
Alarm Delay Flow SwitchsRead and write
Alarm Delay External Frost GuardsRead and write
Alarm Delay Frost Protection Digital InputsRead and write
Alarm Delay Fire AlarmsRead and write
Alarm Delay External AlarmsRead and write
Alarm Delay Electric HeatersRead and write
Alarm Delay Sensor ErrorsRead and write
Alarm Delay Rotation Guard ExchangersRead and write
Running Mode Air UnitRead and write
Supply Temp Controller ModeRead and write
Supply Temp Controller Output if Manual on Mode%Read and write
Running Mode SAFRead and write
Running Mode EAFRead and write
Running Mode Frequence Controlled SAFRead and write
Freguencer Controller Output SAF if Manual Mode%Read and write
Running Mode Frequence Controlled EAFRead and write
Freguencer Controller Output EAF if Manual Mode%Read and write
Running Mode HeatingRead and write
Heating Controller Output if Manual ModeRead and write
Running Mode ExchangerRead and write
Exchanger Controller Output if Manual ModeRead and write
Running Mode CoolingRead and write
Cooling Controller Output if Manual ModeRead and write
Running Mode Humidification/DehumidificationRead and write
Humidification/Dehumidification Controller OutputRead and write
Running Mode P1-HeatingRead and write
Running Mode P1-ExchangerRead and write
Running Mode P1-CoolingRead and write
Running Mode Fire DamperRead and write
Running Mode Fresh Air DamperRead and write
Running Mode Recirculation DamperRead and write
Running Mode Extract Air DamperRead and write
Outdoor Temperature Setting°CRead
Manual/Auto Full Speed Time ChannelRead and write
Manual/Auto Half Speed Time ChannelRead and write
Manual/Auto Timer Output 1Read and write
Manual/Auto Timer Output 2Read and write
Manual/Auto Timer Output 3Read and write
Manual/Auto Timer Output 4Read and write
Manual/Auto Timer Output 5Read and write
External Alarm Acknowledge by Setting This SignalRead and write
External Alarm Blocking by Setting This SignalRead and write
External Alarm Unblocking by Setting This SignalRead and write
If Lower Outdoor Temp the Heating Pump is Not Stopped°CRead and write
Max Limit of Supply Setpoint when Cascade Control°CRead and write
Min Limit of Supply Setpoint when Cascade Control°CRead and write
Clock Second 0-59Read
Clock Minute 0-59Read
Clock Hour 0-23Read
Clock Day of Week 1-7Read
Clock Week Number 1-53Read
Clock Day of Month 1-31Read
Clock Month 1-12Read
Clock Year 0-99Read
Pressure Compensation at Breakpoint 1Read and write
Outdoor Temp Breakpoint 1Read and write
Pressure Compensation at Breakpoint 2Read and write
Outdoor Temp Breakpoint 2Read and write
Max Allowed Difference Between Setpoint and Humidity%RHRead and write
Start Limit in % to Start Digital Output Signal%RHRead and write
Stop Limit in % to Stop Digital Output Signal%RHRead and write
Running Mode Humidity Start SignalRead and write
Start Delay ExchangersRead and write
If Lower Outdoor Temperature All Steps for DX-cooling°CRead and write
Output Signal Full Speed SAF if Frequency Control Manually%Read and write
Output Signal Half Speed SAF if Frequency Control Manually%Read and write
Output Signal Full Speed EAF if Frequency Control Manually%Read and write
Output Signal Half Speed EAF if Frequency Control Manually%Read and write
If Frequens Output Signal SAF is Lower Cool Step 1%Read and write
If Frequens Output Signal SAF is Lower Cool Step 2%Read and write
If Frequens Output Signal SAF is Lower Cool Step 3%Read and write
If Lower Outdoor Temperature Cool Step 1 is Blocked°CRead and write
If Lower Outdoor Temperature Cool Step 2 is Blocked°CRead and write
If Lower Outdoor Temperature Cool Step 3 is Blocked°CRead and write
Start/Stop Function Extra UnitRead and write
Setpoint Extra Unit°CRead and write
Control Mode Extra UnitRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show supply, extract and outdoor temperature together with fan pressure on one dashboard per air handling unit.
  • Send an e-mail when an alarm status register leaves Normal, for example a filter guard or fan malfunction.
  • Keep a year of supply temperature and air flow history to check comfort complaints and heat recovery efficiency.
  • Change the supply air setpoint or the time schedule from ModbusCloud without a visit on site.
  • Compare CO2 and fan speed over the day to see whether demand controlled ventilation works as intended.

Installation

  1. Connect RS485 port 1 of the Corrigo (terminals A and B) to the RS485 port of the ModbusCloud Gateway. Terminate both ends of the bus.

  2. In the Corrigo menu under Configuration, Communication, set Modbus slave on port 1 to active and note the address and speed (default 1, 9600 baud, no parity, 2 stop bits).

  3. In ModbusCloud, add a Modbus device with the same address and serial settings and import this template.

  4. Check that supply air temperature and run mode show plausible values. If nothing answers, swap A and B and check the port settings.

Things to watch for

The Corrigo does not answer at all. What should I check?

Modbus is off from the factory: set Modbus slave on port 1 to active in the Corrigo menu. Then compare address, speed, parity and stop bits with the settings in ModbusCloud (default 1, 9600, none, 2). Check A and B, and make sure no other device uses port 1, such as an expansion unit or frequency converters.

Why does the supply temperature read 215 instead of 21.5?

The Corrigo sends values with decimals multiplied by 10, schedule times by 100 and air flows unscaled. The template already applies these factors. If you read registers with another tool, divide by 10 yourself.

I write a manual output value but nothing changes.

A manual value only takes effect when the matching running mode is set to manual. Write the running mode register first, for example Running Mode Heating to Manual, then the manual output value. Set the running mode back to Auto when you are done.

What should I keep in mind when writing settings?

Every setting you write goes straight into the controller and changes how the air handling unit runs, including alarm limits and schedules. Read the current value first, write one register at a time and check the result on the Corrigo display. Running modes left on manual stop automatic control.