Remeha GTW-08
Modbus RTU interface for Remeha boilers and heat pumps with up to 12 heating zones.
The Remeha GTW-08 is a Modbus interface that connects Remeha boilers and heat pumps with an L-Bus controller to a building management system. This Modbus RTU template reads temperatures, water pressure, status, errors and counters of the appliance, cascade, buffer tank and up to 12 zones, and lets you write heat demand, zone modes and setpoints from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 1434, read and write
- Brand
- Remeha
- Key readings
- Flow temperature · Return temperature · Outdoor temperature · Water pressure · Appliance status · Error code · Zone room temperature · DHW tank temperature
- Available commands
- Heat demand setpoint · Zone mode · Room temperature setpoint · DHW setpoint · Heating curve · CH and DHW enable
- Compatible models
- GTW-08 · Remeha boilers and heat pumps with L-Bus controller (CU-GH, CU-OH, EHC) and a GTW-08 interface
- Last updated
Registers (1434)
1434 read, 946 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Flow Temperature | °C | Read | |||
| Return Temperature | °C | Read | |||
| Outside Temperature | °C | Read | |||
| Water Pressure | bar | Read | |||
| Flue Gas Temperature | °C | Read | |||
| Heat Pump Flow Temperature | °C | Read | |||
| Heat Pump Return Temperature | °C | Read | |||
| Flow Rate | l/min | Read | |||
| Appliance Status | Read | ||||
| Appliance Sub Status | Read | ||||
| Relative Power | % | Read | |||
| Actual Power | kW | Read | |||
| Power Setpoint Percent Of Max | Read | ||||
| Ionisation Current | Read | ||||
| CH Setpoint | °C | Read | |||
| DHW Internal Setpoint | °C | Read | |||
| Cooling Flow Setpoint | °C | Read | |||
| DHW Flow Temperature Setpoint | °C | Read | |||
| Season Mode | Read | ||||
| Calculated COP | Read | ||||
| COP Switch Threshold | Read | ||||
| System Actual Power | % | Read | |||
| System Flow Temperature | °C | Read | |||
| System Return Temperature | °C | Read | |||
| Producer Status Bits | Read | ||||
| Producer Special Request Bits | Read | ||||
| Appliance Error Code | Read | ||||
| Appliance Error Priority | Read | ||||
| Appliance Status 1 Bits | Read | ||||
| Appliance Status 2 Bits | Read | ||||
| Heat Demand Power Setpoint | % | Read and write | |||
| Heat Demand Temperature Setpoint | °C | Read and write | |||
| Algorithm Type | Read and write | ||||
| Heat Demand Type | Read and write | ||||
| Internal Heat Demand Power | % | Read | |||
| Internal Heat Demand Temperature | °C | Read | |||
| Internal Heat Demand Type | Read | ||||
| CH Enabled | Read and write | ||||
| DHW Enabled | Read and write | ||||
| Cooling Mode | Read and write | ||||
| Cooling Forced | Read and write | ||||
| Force Summer Mode | Read and write | ||||
| Summer Winter Switch Temperature | °C | Read and write | |||
| Summer Winter Neutral Band | °C | Read and write | |||
| Frost Protection Outside Temperature | °C | Read and write | |||
| Mode Change End Time | Read and write | ||||
| Burner Starts | Read | ||||
| Burner Hours | h | Read | |||
| Backup 1 Starts | Read | ||||
| Backup 1 Hours | h | Read | |||
| Backup 2 Starts | Read | ||||
| Backup 2 Hours | h | Read | |||
| Operating Hours Total | h | Read | |||
| CH Energy Consumption | kWh | Read | |||
| DHW Energy Consumption | kWh | Read | |||
| Cooling Energy Consumption | kWh | Read | |||
| Total Energy Consumption | kWh | Read and write | |||
| Backup Energy Consumption | kWh | Read and write | |||
| Total Thermal Energy Delivered | kWh | Read and write | |||
| CH Thermal Energy Delivered | kWh | Read and write | |||
| DHW Thermal Energy Delivered | kWh | Read and write | |||
| Cooling Thermal Energy Delivered | kWh | Read and write | |||
| Backup Thermal Energy Delivered | kWh | Read and write | |||
| Pump Speed | % | Read and write | |||
| Main Control Burner Starts | Read | ||||
| Main Control Burner Hours | h | Read | |||
| Main Control Service Starts | Read | ||||
| Main Control Backup 1 Starts | Read | ||||
| Main Control Backup 1 Hours | h | Read | |||
| Main Control Backup 2 Starts | Read | ||||
| Main Control Backup 2 Hours | h | Read | |||
| Main Control Operating Hours | h | Read | |||
| Main Control Service Burning Hours | h | Read | |||
| Service Required | Read | ||||
| Service Notification | Read | ||||
| Service Burning Hours | h | Read | |||
| Service Operating Hours | h | Read | |||
| Service Starts | Read | ||||
| Appliance On Error | Read | ||||
| Board 1 Error Code | Read | ||||
| Board 1 Error Priority | Read | ||||
| Board 2 Error Code | Read | ||||
| Board 2 Error Priority | Read | ||||
| Board 3 Error Code | Read | ||||
| Board 3 Error Priority | Read | ||||
| Board 4 Error Code | Read | ||||
| Board 4 Error Priority | Read | ||||
| Board 5 Error Code | Read | ||||
| Board 5 Error Priority | Read | ||||
| Board 6 Error Code | Read | ||||
| Board 6 Error Priority | Read | ||||
| Board 7 Error Code | Read | ||||
| Board 7 Error Priority | Read | ||||
| Board 8 Error Code | Read | ||||
| Board 8 Error Priority | Read | ||||
| Board 9 Error Code | Read | ||||
| Board 9 Error Priority | Read | ||||
| Board 10 Error Code | Read | ||||
| Board 10 Error Priority | Read | ||||
| Number Of Boards | Read | ||||
| Board 1 Device Type | Read | ||||
| Board 1 Software Version | Read | ||||
| Board 1 Config Table Version | Read | ||||
| Board 1 Hardware Version | Read | ||||
| Board 1 Article Number | Read | ||||
| Board 2 Device Type | Read | ||||
| Board 2 Software Version | Read | ||||
| Board 2 Config Table Version | Read | ||||
| Board 2 Hardware Version | Read | ||||
| Board 2 Article Number | Read | ||||
| Board 3 Device Type | Read | ||||
| Board 3 Software Version | Read | ||||
| Board 3 Config Table Version | Read | ||||
| Board 3 Hardware Version | Read | ||||
| Board 3 Article Number | Read | ||||
| Board 4 Device Type | Read | ||||
| Board 4 Software Version | Read | ||||
| Board 4 Config Table Version | Read | ||||
| Board 4 Hardware Version | Read | ||||
| Board 4 Article Number | Read | ||||
| Board 5 Device Type | Read | ||||
| Board 5 Software Version | Read | ||||
| Board 5 Config Table Version | Read | ||||
| Board 5 Hardware Version | Read | ||||
| Board 5 Article Number | Read | ||||
| Board 6 Device Type | Read | ||||
| Board 6 Software Version | Read | ||||
| Board 6 Config Table Version | Read | ||||
| Board 6 Hardware Version | Read | ||||
| Board 6 Article Number | Read | ||||
| Board 7 Device Type | Read | ||||
| Board 7 Software Version | Read | ||||
| Board 7 Config Table Version | Read | ||||
| Board 7 Hardware Version | Read | ||||
| Board 7 Article Number | Read | ||||
| Board 8 Device Type | Read | ||||
| Board 8 Software Version | Read | ||||
| Board 8 Config Table Version | Read | ||||
| Board 8 Hardware Version | Read | ||||
| Board 8 Article Number | Read | ||||
| Board 9 Device Type | Read | ||||
| Board 9 Software Version | Read | ||||
| Board 9 Config Table Version | Read | ||||
| Board 9 Hardware Version | Read | ||||
| Board 9 Article Number | Read | ||||
| Board 10 Device Type | Read | ||||
| Board 10 Software Version | Read | ||||
| Board 10 Config Table Version | Read | ||||
| Board 10 Hardware Version | Read | ||||
| Board 10 Article Number | Read | ||||
| Number Of Zones | Read | ||||
| Number Of Zones Disabled | Read | ||||
| Number Of CH Zones | Read | ||||
| Number Of CH Cooling Zones | Read | ||||
| Number Of DHW Zones | Read | ||||
| Number Of Process Heat Zones | Read | ||||
| Number Of Swimming Pool Zones | Read | ||||
| Number Of Other Zones | Read | ||||
| Buffer Tank Active | Read | ||||
| Cascade Active | Read | ||||
| Reset Discovery Table | Read and write | ||||
| Manufacturer Code | Read | ||||
| Gateway Device Type | Read | ||||
| Fallback Heat Demand Mode | Read and write | ||||
| Fallback Heat Demand Config | Read and write | ||||
| Fallback Heat Demand Period | min | Read and write | |||
| Fallback Power Setpoint | % | Read and write | |||
| Fallback Temperature Setpoint | °C | Read and write | |||
| Fallback Heat Demand Type | Read and write | ||||
| Analog Input Function | Read and write | ||||
| Analog Input Value | V | Read and write | |||
| Cascade Flow Temperature | °C | Read | |||
| Cascade Return Temperature | °C | Read | |||
| Cascade LLH Flow Temperature | °C | Read | |||
| Cascade LLH Return Temperature | °C | Read | |||
| Cascade Appliance Number | Read and write | ||||
| Cascade Mode | Read and write | ||||
| Cascade Type | Read and write | ||||
| Cascade Lead Appliance | Read and write | ||||
| Cascade Inter Stage Time | Read and write | ||||
| Cascade Parallel Heating Outside Temp | °C | Read and write | |||
| Cascade Parallel Cooling Outside Temp | °C | Read and write | |||
| Cascade Power Rise Time | Read and write | ||||
| Cascade Management Type | Read and write | ||||
| Cascade Permutation Type | Read and write | ||||
| Cascade Power Control Strategy | Read and write | ||||
| Cascade Preferred CH Producer | Read and write | ||||
| Cascade Non Preferred CH Producer | Read and write | ||||
| Cascade Late On Value | % | Read and write | |||
| Cascade Late Off Value | % | Read and write | |||
| Cascade Early On Value | % | Read and write | |||
| Cascade Early Off Value | % | Read and write | |||
| Cascade Primary Pump Type | Read and write | ||||
| Cascade Secondary Pump Type | Read and write | ||||
| Producer Activation Order | Read and write | ||||
| Identified Producer Number | Read and write | ||||
| Identified Producer State | Read and write | ||||
| Cascade Producer Switch Interval | h | Read and write | |||
| Producer Min Power | Read and write | ||||
| Producer Max Power | Read and write | ||||
| Active Producers | Read | ||||
| Temporary Producer Order | Read | ||||
| Producer Main Status | Read | ||||
| Producer Serial Number | Read | ||||
| Cascade First Start Producer | Read | ||||
| Cascade Producers Present | Read | ||||
| Cascade Stages Available | Read | ||||
| Cascade Stages Required | Read | ||||
| Cascade Power Request | % | Read | |||
| Cascade Power Request Temperature | °C | Read | |||
| Cascade Power Request Type | Read | ||||
| Cascade Calculated Power | % | Read | |||
| Cascade Calculated Temperature | °C | Read | |||
| Cascade Calculated Demand Type | Read | ||||
| Cascade Requested Power | kW | Read | |||
| Cascade Requested Power Percent | % | Read | |||
| Cascade Primary Pump Status | Read | ||||
| Cascade Secondary Pump Status | Read | ||||
| Cascade State | Read | ||||
| Cascade CH Hours | h | Read | |||
| Cascade DHW Hours | h | Read | |||
| Cascade Central Pump Status | Read | ||||
| Producer Pump PWM | % | Read | |||
| Consumer Pump PWM | % | Read | |||
| Cascade Member 1 Power | Read | ||||
| Cascade Member 1 Flow Temperature | °C | Read | |||
| Cascade Member 1 Status Bits | Read | ||||
| Cascade Member 1 Special Request | Read | ||||
| Cascade Member 3 Power | Read | ||||
| Cascade Member 3 Flow Temperature | °C | Read | |||
| Cascade Member 3 Status Bits | Read | ||||
| Cascade Member 3 Special Request | Read | ||||
| Cascade Member 4 Power | Read | ||||
| Cascade Member 4 Flow Temperature | °C | Read | |||
| Cascade Member 4 Status Bits | Read | ||||
| Cascade Member 4 Special Request | Read | ||||
| Cascade Member 5 Power | Read | ||||
| Cascade Member 5 Flow Temperature | °C | Read | |||
| Cascade Member 5 Status Bits | Read | ||||
| Cascade Member 5 Special Request | Read | ||||
| Cascade Member 6 Power | Read | ||||
| Cascade Member 6 Flow Temperature | °C | Read | |||
| Cascade Member 6 Status Bits | Read | ||||
| Cascade Member 6 Special Request | Read | ||||
| Cascade Member 7 Power | Read | ||||
| Cascade Member 7 Flow Temperature | °C | Read | |||
| Cascade Member 7 Status Bits | Read | ||||
| Cascade Member 7 Special Request | Read | ||||
| Cascade Member 8 Power | Read | ||||
| Cascade Member 8 Flow Temperature | °C | Read | |||
| Cascade Member 8 Status Bits | Read | ||||
| Cascade Member 8 Special Request | Read | ||||
| Cascade Member 9 Power | Read | ||||
| Cascade Member 9 Flow Temperature | °C | Read | |||
| Cascade Member 9 Status Bits | Read | ||||
| Cascade Member 9 Special Request | Read | ||||
| Cascade Member 10 Power | Read | ||||
| Cascade Member 10 Flow Temperature | °C | Read | |||
| Cascade Member 10 Status Bits | Read | ||||
| Cascade Member 10 Special Request | Read | ||||
| Buffer Temperature Bottom | °C | Read | |||
| Buffer Temperature Top | °C | Read | |||
| Buffer Pump State | Read | ||||
| Buffer Mode | Read | ||||
| Buffer Demand Power | Read | ||||
| Buffer Demand Temperature | °C | Read | |||
| Buffer Demand Type | Read | ||||
| Buffer Hysteresis Start | Read and write | ||||
| Buffer Hysteresis Stop | Read and write | ||||
| Buffer Pump Post Run | Read and write | ||||
| Buffer Control Strategy | Read and write | ||||
| Buffer Heating Setpoint | °C | Read and write | |||
| Buffer Cooling Setpoint | °C | Read and write | |||
| Buffer Slope | Read and write | ||||
| Buffer Offset | Read and write | ||||
| Buffer Time Program Monday | Read and write | ||||
| Buffer Time Program Tuesday | Read and write | ||||
| Buffer Time Program Wednesday | Read and write | ||||
| Buffer Time Program Thursday | Read and write | ||||
| Buffer Time Program Friday | Read and write | ||||
| Buffer Time Program Saturday | Read and write | ||||
| Buffer Time Program Sunday | Read and write | ||||
| Zone 1 Flow Temperature | °C | Read | |||
| Zone 1 Flow Setpoint | °C | Read | |||
| Zone 1 Room Setpoint | °C | Read | |||
| Zone 1 Outside Temperature | °C | Read | |||
| Zone 1 Room Temperature | °C | Read | |||
| Zone 1 Room Temperature Measured | Read and write | ||||
| Zone 1 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 1 DHW Tank Temperature Top | °C | Read | |||
| Zone 1 Heat Demand Active | Read | ||||
| Zone 1 Current Activity | Read | ||||
| Zone 1 Current Mode | Read | ||||
| Zone 1 Heating Mode | Read | ||||
| Zone 1 Pump Running | Read | ||||
| Zone 1 Mixing Valve Closing | Read | ||||
| Zone 1 Mixing Valve Opening | Read | ||||
| Zone 1 Pool Secondary Pump | Read | ||||
| Zone 1 Electric Backup Output | Read | ||||
| Zone 1 Pump Hours | h | Read | |||
| Zone 1 Pump Starts | Read | ||||
| Zone 1 Type | Read | ||||
| Zone 1 Function | Read | ||||
| Zone 1 Short Name | Read | ||||
| Zone 1 Board Device Type | Read | ||||
| Zone 1 Board Instance | Read | ||||
| Zone 1 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 1 Mode | Read and write | ||||
| Zone 1 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 1 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 1 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 1 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 1 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 1 Room Reduced Setpoint | °C | Read and write | |||
| Zone 1 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 1 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 1 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 1 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 1 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 1 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 1 Room Holiday Setpoint | °C | Read and write | |||
| Zone 1 Room Temporary Setpoint | °C | Read and write | |||
| Zone 1 Room Manual Setpoint | °C | Read and write | |||
| Zone 1 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 1 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 1 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 1 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 1 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 1 Process Heat Setpoint | °C | Read and write | |||
| Zone 1 Heating Control Strategy | Read and write | ||||
| Zone 1 Max Flow Setpoint | °C | Read and write | |||
| Zone 1 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 1 Heating Curve Slope | Read and write | ||||
| Zone 1 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 1 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 1 Max Preheat Time | Read and write | ||||
| Zone 1 Mixing Valve Shift | Read and write | ||||
| Zone 1 Mixing Valve Bandwidth | Read and write | ||||
| Zone 1 DHW Hysteresis | Read and write | ||||
| Zone 1 DHW Calorifier Offset | Read and write | ||||
| Zone 1 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 1 Process Heat Hysteresis On | Read and write | ||||
| Zone 1 Process Heat Hysteresis Off | Read and write | ||||
| Zone 1 Process Heat Setpoint Raise | Read and write | ||||
| Zone 1 DHW Start Hysteresis | Read and write | ||||
| Zone 1 Pump Post Run | Read and write | ||||
| Zone 1 Selected Time Program | Read and write | ||||
| Zone 1 Program 1 Monday | Read and write | ||||
| Zone 1 Program 1 Tuesday | Read and write | ||||
| Zone 1 Program 1 Wednesday | Read and write | ||||
| Zone 1 Program 1 Thursday | Read and write | ||||
| Zone 1 Program 1 Friday | Read and write | ||||
| Zone 1 Program 1 Saturday | Read and write | ||||
| Zone 1 Program 1 Sunday | Read and write | ||||
| Zone 1 Program 2 Monday | Read and write | ||||
| Zone 1 Program 2 Tuesday | Read and write | ||||
| Zone 1 Program 2 Wednesday | Read and write | ||||
| Zone 1 Program 2 Thursday | Read and write | ||||
| Zone 1 Program 2 Friday | Read and write | ||||
| Zone 1 Program 2 Saturday | Read and write | ||||
| Zone 1 Program 2 Sunday | Read and write | ||||
| Zone 1 Program 3 Monday | Read and write | ||||
| Zone 1 Program 3 Tuesday | Read and write | ||||
| Zone 1 Program 3 Wednesday | Read and write | ||||
| Zone 1 Program 3 Thursday | Read and write | ||||
| Zone 1 Program 3 Friday | Read and write | ||||
| Zone 1 Program 3 Saturday | Read and write | ||||
| Zone 1 Program 3 Sunday | Read and write | ||||
| Zone 1 Program 4 Monday | Read and write | ||||
| Zone 1 Program 4 Tuesday | Read and write | ||||
| Zone 1 Program 4 Wednesday | Read and write | ||||
| Zone 1 Program 4 Thursday | Read and write | ||||
| Zone 1 Program 4 Friday | Read and write | ||||
| Zone 1 Program 4 Saturday | Read and write | ||||
| Zone 1 Program 4 Sunday | Read and write | ||||
| Zone 1 Holiday Start | Read and write | ||||
| Zone 1 Holiday End | Read and write | ||||
| Zone 1 Mode Change End | Read and write | ||||
| Zone 2 Flow Temperature | °C | Read | |||
| Zone 2 Flow Setpoint | °C | Read | |||
| Zone 2 Room Setpoint | °C | Read | |||
| Zone 2 Outside Temperature | °C | Read | |||
| Zone 2 Room Temperature | °C | Read | |||
| Zone 2 Room Temperature Measured | Read and write | ||||
| Zone 2 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 2 DHW Tank Temperature Top | °C | Read | |||
| Zone 2 Heat Demand Active | Read | ||||
| Zone 2 Current Activity | Read | ||||
| Zone 2 Current Mode | Read | ||||
| Zone 2 Heating Mode | Read | ||||
| Zone 2 Pump Running | Read | ||||
| Zone 2 Mixing Valve Closing | Read | ||||
| Zone 2 Mixing Valve Opening | Read | ||||
| Zone 2 Pool Secondary Pump | Read | ||||
| Zone 2 Electric Backup Output | Read | ||||
| Zone 2 Pump Hours | h | Read | |||
| Zone 2 Pump Starts | Read | ||||
| Zone 2 Type | Read | ||||
| Zone 2 Function | Read | ||||
| Zone 2 Short Name | Read | ||||
| Zone 2 Board Device Type | Read | ||||
| Zone 2 Board Instance | Read | ||||
| Zone 2 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 2 Mode | Read and write | ||||
| Zone 2 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 2 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 2 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 2 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 2 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 2 Room Reduced Setpoint | °C | Read and write | |||
| Zone 2 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 2 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 2 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 2 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 2 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 2 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 2 Room Holiday Setpoint | °C | Read and write | |||
| Zone 2 Room Temporary Setpoint | °C | Read and write | |||
| Zone 2 Room Manual Setpoint | °C | Read and write | |||
| Zone 2 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 2 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 2 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 2 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 2 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 2 Process Heat Setpoint | °C | Read and write | |||
| Zone 2 Heating Control Strategy | Read and write | ||||
| Zone 2 Max Flow Setpoint | °C | Read and write | |||
| Zone 2 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 2 Heating Curve Slope | Read and write | ||||
| Zone 2 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 2 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 2 Max Preheat Time | Read and write | ||||
| Zone 2 Mixing Valve Shift | Read and write | ||||
| Zone 2 Mixing Valve Bandwidth | Read and write | ||||
| Zone 2 DHW Hysteresis | Read and write | ||||
| Zone 2 DHW Calorifier Offset | Read and write | ||||
| Zone 2 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 2 Process Heat Hysteresis On | Read and write | ||||
| Zone 2 Process Heat Hysteresis Off | Read and write | ||||
| Zone 2 Process Heat Setpoint Raise | Read and write | ||||
| Zone 2 DHW Start Hysteresis | Read and write | ||||
| Zone 2 Pump Post Run | Read and write | ||||
| Zone 2 Selected Time Program | Read and write | ||||
| Zone 2 Program 1 Monday | Read and write | ||||
| Zone 2 Program 1 Tuesday | Read and write | ||||
| Zone 2 Program 1 Wednesday | Read and write | ||||
| Zone 2 Program 1 Thursday | Read and write | ||||
| Zone 2 Program 1 Friday | Read and write | ||||
| Zone 2 Program 1 Saturday | Read and write | ||||
| Zone 2 Program 1 Sunday | Read and write | ||||
| Zone 2 Program 2 Monday | Read and write | ||||
| Zone 2 Program 2 Tuesday | Read and write | ||||
| Zone 2 Program 2 Wednesday | Read and write | ||||
| Zone 2 Program 2 Thursday | Read and write | ||||
| Zone 2 Program 2 Friday | Read and write | ||||
| Zone 2 Program 2 Saturday | Read and write | ||||
| Zone 2 Program 2 Sunday | Read and write | ||||
| Zone 2 Program 3 Monday | Read and write | ||||
| Zone 2 Program 3 Tuesday | Read and write | ||||
| Zone 2 Program 3 Wednesday | Read and write | ||||
| Zone 2 Program 3 Thursday | Read and write | ||||
| Zone 2 Program 3 Friday | Read and write | ||||
| Zone 2 Program 3 Saturday | Read and write | ||||
| Zone 2 Program 3 Sunday | Read and write | ||||
| Zone 2 Program 4 Monday | Read and write | ||||
| Zone 2 Program 4 Tuesday | Read and write | ||||
| Zone 2 Program 4 Wednesday | Read and write | ||||
| Zone 2 Program 4 Thursday | Read and write | ||||
| Zone 2 Program 4 Friday | Read and write | ||||
| Zone 2 Program 4 Saturday | Read and write | ||||
| Zone 2 Program 4 Sunday | Read and write | ||||
| Zone 2 Holiday Start | Read and write | ||||
| Zone 2 Holiday End | Read and write | ||||
| Zone 2 Mode Change End | Read and write | ||||
| Zone 3 Flow Temperature | °C | Read | |||
| Zone 3 Flow Setpoint | °C | Read | |||
| Zone 3 Room Setpoint | °C | Read | |||
| Zone 3 Outside Temperature | °C | Read | |||
| Zone 3 Room Temperature | °C | Read | |||
| Zone 3 Room Temperature Measured | Read and write | ||||
| Zone 3 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 3 DHW Tank Temperature Top | °C | Read | |||
| Zone 3 Heat Demand Active | Read | ||||
| Zone 3 Current Activity | Read | ||||
| Zone 3 Current Mode | Read | ||||
| Zone 3 Heating Mode | Read | ||||
| Zone 3 Pump Running | Read | ||||
| Zone 3 Mixing Valve Closing | Read | ||||
| Zone 3 Mixing Valve Opening | Read | ||||
| Zone 3 Pool Secondary Pump | Read | ||||
| Zone 3 Electric Backup Output | Read | ||||
| Zone 3 Pump Hours | h | Read | |||
| Zone 3 Pump Starts | Read | ||||
| Zone 3 Type | Read | ||||
| Zone 3 Function | Read | ||||
| Zone 3 Short Name | Read | ||||
| Zone 3 Board Device Type | Read | ||||
| Zone 3 Board Instance | Read | ||||
| Zone 3 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 3 Mode | Read and write | ||||
| Zone 3 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 3 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 3 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 3 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 3 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 3 Room Reduced Setpoint | °C | Read and write | |||
| Zone 3 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 3 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 3 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 3 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 3 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 3 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 3 Room Holiday Setpoint | °C | Read and write | |||
| Zone 3 Room Temporary Setpoint | °C | Read and write | |||
| Zone 3 Room Manual Setpoint | °C | Read and write | |||
| Zone 3 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 3 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 3 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 3 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 3 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 3 Process Heat Setpoint | °C | Read and write | |||
| Zone 3 Heating Control Strategy | Read and write | ||||
| Zone 3 Max Flow Setpoint | °C | Read and write | |||
| Zone 3 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 3 Heating Curve Slope | Read and write | ||||
| Zone 3 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 3 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 3 Max Preheat Time | Read and write | ||||
| Zone 3 Mixing Valve Shift | Read and write | ||||
| Zone 3 Mixing Valve Bandwidth | Read and write | ||||
| Zone 3 DHW Hysteresis | Read and write | ||||
| Zone 3 DHW Calorifier Offset | Read and write | ||||
| Zone 3 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 3 Process Heat Hysteresis On | Read and write | ||||
| Zone 3 Process Heat Hysteresis Off | Read and write | ||||
| Zone 3 Process Heat Setpoint Raise | Read and write | ||||
| Zone 3 DHW Start Hysteresis | Read and write | ||||
| Zone 3 Pump Post Run | Read and write | ||||
| Zone 3 Selected Time Program | Read and write | ||||
| Zone 3 Program 1 Monday | Read and write | ||||
| Zone 3 Program 1 Tuesday | Read and write | ||||
| Zone 3 Program 1 Wednesday | Read and write | ||||
| Zone 3 Program 1 Thursday | Read and write | ||||
| Zone 3 Program 1 Friday | Read and write | ||||
| Zone 3 Program 1 Saturday | Read and write | ||||
| Zone 3 Program 1 Sunday | Read and write | ||||
| Zone 3 Program 2 Monday | Read and write | ||||
| Zone 3 Program 2 Tuesday | Read and write | ||||
| Zone 3 Program 2 Wednesday | Read and write | ||||
| Zone 3 Program 2 Thursday | Read and write | ||||
| Zone 3 Program 2 Friday | Read and write | ||||
| Zone 3 Program 2 Saturday | Read and write | ||||
| Zone 3 Program 2 Sunday | Read and write | ||||
| Zone 3 Program 3 Monday | Read and write | ||||
| Zone 3 Program 3 Tuesday | Read and write | ||||
| Zone 3 Program 3 Wednesday | Read and write | ||||
| Zone 3 Program 3 Thursday | Read and write | ||||
| Zone 3 Program 3 Friday | Read and write | ||||
| Zone 3 Program 3 Saturday | Read and write | ||||
| Zone 3 Program 3 Sunday | Read and write | ||||
| Zone 3 Program 4 Monday | Read and write | ||||
| Zone 3 Program 4 Tuesday | Read and write | ||||
| Zone 3 Program 4 Wednesday | Read and write | ||||
| Zone 3 Program 4 Thursday | Read and write | ||||
| Zone 3 Program 4 Friday | Read and write | ||||
| Zone 3 Program 4 Saturday | Read and write | ||||
| Zone 3 Program 4 Sunday | Read and write | ||||
| Zone 3 Holiday Start | Read and write | ||||
| Zone 3 Holiday End | Read and write | ||||
| Zone 3 Mode Change End | Read and write | ||||
| Zone 4 Flow Temperature | °C | Read | |||
| Zone 4 Flow Setpoint | °C | Read | |||
| Zone 4 Room Setpoint | °C | Read | |||
| Zone 4 Outside Temperature | °C | Read | |||
| Zone 4 Room Temperature | °C | Read | |||
| Zone 4 Room Temperature Measured | Read and write | ||||
| Zone 4 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 4 DHW Tank Temperature Top | °C | Read | |||
| Zone 4 Heat Demand Active | Read | ||||
| Zone 4 Current Activity | Read | ||||
| Zone 4 Current Mode | Read | ||||
| Zone 4 Heating Mode | Read | ||||
| Zone 4 Pump Running | Read | ||||
| Zone 4 Mixing Valve Closing | Read | ||||
| Zone 4 Mixing Valve Opening | Read | ||||
| Zone 4 Pool Secondary Pump | Read | ||||
| Zone 4 Electric Backup Output | Read | ||||
| Zone 4 Pump Hours | h | Read | |||
| Zone 4 Pump Starts | Read | ||||
| Zone 4 Type | Read | ||||
| Zone 4 Function | Read | ||||
| Zone 4 Short Name | Read | ||||
| Zone 4 Board Device Type | Read | ||||
| Zone 4 Board Instance | Read | ||||
| Zone 4 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 4 Mode | Read and write | ||||
| Zone 4 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 4 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 4 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 4 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 4 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 4 Room Reduced Setpoint | °C | Read and write | |||
| Zone 4 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 4 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 4 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 4 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 4 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 4 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 4 Room Holiday Setpoint | °C | Read and write | |||
| Zone 4 Room Temporary Setpoint | °C | Read and write | |||
| Zone 4 Room Manual Setpoint | °C | Read and write | |||
| Zone 4 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 4 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 4 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 4 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 4 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 4 Process Heat Setpoint | °C | Read and write | |||
| Zone 4 Heating Control Strategy | Read and write | ||||
| Zone 4 Max Flow Setpoint | °C | Read and write | |||
| Zone 4 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 4 Heating Curve Slope | Read and write | ||||
| Zone 4 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 4 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 4 Max Preheat Time | Read and write | ||||
| Zone 4 Mixing Valve Shift | Read and write | ||||
| Zone 4 Mixing Valve Bandwidth | Read and write | ||||
| Zone 4 DHW Hysteresis | Read and write | ||||
| Zone 4 DHW Calorifier Offset | Read and write | ||||
| Zone 4 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 4 Process Heat Hysteresis On | Read and write | ||||
| Zone 4 Process Heat Hysteresis Off | Read and write | ||||
| Zone 4 Process Heat Setpoint Raise | Read and write | ||||
| Zone 4 DHW Start Hysteresis | Read and write | ||||
| Zone 4 Pump Post Run | Read and write | ||||
| Zone 4 Selected Time Program | Read and write | ||||
| Zone 4 Program 1 Monday | Read and write | ||||
| Zone 4 Program 1 Tuesday | Read and write | ||||
| Zone 4 Program 1 Wednesday | Read and write | ||||
| Zone 4 Program 1 Thursday | Read and write | ||||
| Zone 4 Program 1 Friday | Read and write | ||||
| Zone 4 Program 1 Saturday | Read and write | ||||
| Zone 4 Program 1 Sunday | Read and write | ||||
| Zone 4 Program 2 Monday | Read and write | ||||
| Zone 4 Program 2 Tuesday | Read and write | ||||
| Zone 4 Program 2 Wednesday | Read and write | ||||
| Zone 4 Program 2 Thursday | Read and write | ||||
| Zone 4 Program 2 Friday | Read and write | ||||
| Zone 4 Program 2 Saturday | Read and write | ||||
| Zone 4 Program 2 Sunday | Read and write | ||||
| Zone 4 Program 3 Monday | Read and write | ||||
| Zone 4 Program 3 Tuesday | Read and write | ||||
| Zone 4 Program 3 Wednesday | Read and write | ||||
| Zone 4 Program 3 Thursday | Read and write | ||||
| Zone 4 Program 3 Friday | Read and write | ||||
| Zone 4 Program 3 Saturday | Read and write | ||||
| Zone 4 Program 3 Sunday | Read and write | ||||
| Zone 4 Program 4 Monday | Read and write | ||||
| Zone 4 Program 4 Tuesday | Read and write | ||||
| Zone 4 Program 4 Wednesday | Read and write | ||||
| Zone 4 Program 4 Thursday | Read and write | ||||
| Zone 4 Program 4 Friday | Read and write | ||||
| Zone 4 Program 4 Saturday | Read and write | ||||
| Zone 4 Program 4 Sunday | Read and write | ||||
| Zone 4 Holiday Start | Read and write | ||||
| Zone 4 Holiday End | Read and write | ||||
| Zone 4 Mode Change End | Read and write | ||||
| Zone 5 Flow Temperature | °C | Read | |||
| Zone 5 Flow Setpoint | °C | Read | |||
| Zone 5 Room Setpoint | °C | Read | |||
| Zone 5 Outside Temperature | °C | Read | |||
| Zone 5 Room Temperature | °C | Read | |||
| Zone 5 Room Temperature Measured | Read and write | ||||
| Zone 5 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 5 DHW Tank Temperature Top | °C | Read | |||
| Zone 5 Heat Demand Active | Read | ||||
| Zone 5 Current Activity | Read | ||||
| Zone 5 Current Mode | Read | ||||
| Zone 5 Heating Mode | Read | ||||
| Zone 5 Pump Running | Read | ||||
| Zone 5 Mixing Valve Closing | Read | ||||
| Zone 5 Mixing Valve Opening | Read | ||||
| Zone 5 Pool Secondary Pump | Read | ||||
| Zone 5 Electric Backup Output | Read | ||||
| Zone 5 Pump Hours | h | Read | |||
| Zone 5 Pump Starts | Read | ||||
| Zone 5 Type | Read | ||||
| Zone 5 Function | Read | ||||
| Zone 5 Short Name | Read | ||||
| Zone 5 Board Device Type | Read | ||||
| Zone 5 Board Instance | Read | ||||
| Zone 5 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 5 Mode | Read and write | ||||
| Zone 5 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 5 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 5 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 5 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 5 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 5 Room Reduced Setpoint | °C | Read and write | |||
| Zone 5 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 5 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 5 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 5 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 5 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 5 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 5 Room Holiday Setpoint | °C | Read and write | |||
| Zone 5 Room Temporary Setpoint | °C | Read and write | |||
| Zone 5 Room Manual Setpoint | °C | Read and write | |||
| Zone 5 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 5 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 5 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 5 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 5 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 5 Process Heat Setpoint | °C | Read and write | |||
| Zone 5 Heating Control Strategy | Read and write | ||||
| Zone 5 Max Flow Setpoint | °C | Read and write | |||
| Zone 5 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 5 Heating Curve Slope | Read and write | ||||
| Zone 5 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 5 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 5 Max Preheat Time | Read and write | ||||
| Zone 5 Mixing Valve Shift | Read and write | ||||
| Zone 5 Mixing Valve Bandwidth | Read and write | ||||
| Zone 5 DHW Hysteresis | Read and write | ||||
| Zone 5 DHW Calorifier Offset | Read and write | ||||
| Zone 5 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 5 Process Heat Hysteresis On | Read and write | ||||
| Zone 5 Process Heat Hysteresis Off | Read and write | ||||
| Zone 5 Process Heat Setpoint Raise | Read and write | ||||
| Zone 5 DHW Start Hysteresis | Read and write | ||||
| Zone 5 Pump Post Run | Read and write | ||||
| Zone 5 Selected Time Program | Read and write | ||||
| Zone 5 Program 1 Monday | Read and write | ||||
| Zone 5 Program 1 Tuesday | Read and write | ||||
| Zone 5 Program 1 Wednesday | Read and write | ||||
| Zone 5 Program 1 Thursday | Read and write | ||||
| Zone 5 Program 1 Friday | Read and write | ||||
| Zone 5 Program 1 Saturday | Read and write | ||||
| Zone 5 Program 1 Sunday | Read and write | ||||
| Zone 5 Program 2 Monday | Read and write | ||||
| Zone 5 Program 2 Tuesday | Read and write | ||||
| Zone 5 Program 2 Wednesday | Read and write | ||||
| Zone 5 Program 2 Thursday | Read and write | ||||
| Zone 5 Program 2 Friday | Read and write | ||||
| Zone 5 Program 2 Saturday | Read and write | ||||
| Zone 5 Program 2 Sunday | Read and write | ||||
| Zone 5 Program 3 Monday | Read and write | ||||
| Zone 5 Program 3 Tuesday | Read and write | ||||
| Zone 5 Program 3 Wednesday | Read and write | ||||
| Zone 5 Program 3 Thursday | Read and write | ||||
| Zone 5 Program 3 Friday | Read and write | ||||
| Zone 5 Program 3 Saturday | Read and write | ||||
| Zone 5 Program 3 Sunday | Read and write | ||||
| Zone 5 Program 4 Monday | Read and write | ||||
| Zone 5 Program 4 Tuesday | Read and write | ||||
| Zone 5 Program 4 Wednesday | Read and write | ||||
| Zone 5 Program 4 Thursday | Read and write | ||||
| Zone 5 Program 4 Friday | Read and write | ||||
| Zone 5 Program 4 Saturday | Read and write | ||||
| Zone 5 Program 4 Sunday | Read and write | ||||
| Zone 5 Holiday Start | Read and write | ||||
| Zone 5 Holiday End | Read and write | ||||
| Zone 5 Mode Change End | Read and write | ||||
| Zone 6 Flow Temperature | °C | Read | |||
| Zone 6 Flow Setpoint | °C | Read | |||
| Zone 6 Room Setpoint | °C | Read | |||
| Zone 6 Outside Temperature | °C | Read | |||
| Zone 6 Room Temperature | °C | Read | |||
| Zone 6 Room Temperature Measured | Read and write | ||||
| Zone 6 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 6 DHW Tank Temperature Top | °C | Read | |||
| Zone 6 Heat Demand Active | Read | ||||
| Zone 6 Current Activity | Read | ||||
| Zone 6 Current Mode | Read | ||||
| Zone 6 Heating Mode | Read | ||||
| Zone 6 Pump Running | Read | ||||
| Zone 6 Mixing Valve Closing | Read | ||||
| Zone 6 Mixing Valve Opening | Read | ||||
| Zone 6 Pool Secondary Pump | Read | ||||
| Zone 6 Electric Backup Output | Read | ||||
| Zone 6 Pump Hours | h | Read | |||
| Zone 6 Pump Starts | Read | ||||
| Zone 6 Type | Read | ||||
| Zone 6 Function | Read | ||||
| Zone 6 Short Name | Read | ||||
| Zone 6 Board Device Type | Read | ||||
| Zone 6 Board Instance | Read | ||||
| Zone 6 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 6 Mode | Read and write | ||||
| Zone 6 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 6 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 6 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 6 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 6 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 6 Room Reduced Setpoint | °C | Read and write | |||
| Zone 6 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 6 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 6 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 6 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 6 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 6 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 6 Room Holiday Setpoint | °C | Read and write | |||
| Zone 6 Room Temporary Setpoint | °C | Read and write | |||
| Zone 6 Room Manual Setpoint | °C | Read and write | |||
| Zone 6 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 6 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 6 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 6 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 6 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 6 Process Heat Setpoint | °C | Read and write | |||
| Zone 6 Heating Control Strategy | Read and write | ||||
| Zone 6 Max Flow Setpoint | °C | Read and write | |||
| Zone 6 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 6 Heating Curve Slope | Read and write | ||||
| Zone 6 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 6 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 6 Max Preheat Time | Read and write | ||||
| Zone 6 Mixing Valve Shift | Read and write | ||||
| Zone 6 Mixing Valve Bandwidth | Read and write | ||||
| Zone 6 DHW Hysteresis | Read and write | ||||
| Zone 6 DHW Calorifier Offset | Read and write | ||||
| Zone 6 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 6 Process Heat Hysteresis On | Read and write | ||||
| Zone 6 Process Heat Hysteresis Off | Read and write | ||||
| Zone 6 Process Heat Setpoint Raise | Read and write | ||||
| Zone 6 DHW Start Hysteresis | Read and write | ||||
| Zone 6 Pump Post Run | Read and write | ||||
| Zone 6 Selected Time Program | Read and write | ||||
| Zone 6 Program 1 Monday | Read and write | ||||
| Zone 6 Program 1 Tuesday | Read and write | ||||
| Zone 6 Program 1 Wednesday | Read and write | ||||
| Zone 6 Program 1 Thursday | Read and write | ||||
| Zone 6 Program 1 Friday | Read and write | ||||
| Zone 6 Program 1 Saturday | Read and write | ||||
| Zone 6 Program 1 Sunday | Read and write | ||||
| Zone 6 Program 2 Monday | Read and write | ||||
| Zone 6 Program 2 Tuesday | Read and write | ||||
| Zone 6 Program 2 Wednesday | Read and write | ||||
| Zone 6 Program 2 Thursday | Read and write | ||||
| Zone 6 Program 2 Friday | Read and write | ||||
| Zone 6 Program 2 Saturday | Read and write | ||||
| Zone 6 Program 2 Sunday | Read and write | ||||
| Zone 6 Program 3 Monday | Read and write | ||||
| Zone 6 Program 3 Tuesday | Read and write | ||||
| Zone 6 Program 3 Wednesday | Read and write | ||||
| Zone 6 Program 3 Thursday | Read and write | ||||
| Zone 6 Program 3 Friday | Read and write | ||||
| Zone 6 Program 3 Saturday | Read and write | ||||
| Zone 6 Program 3 Sunday | Read and write | ||||
| Zone 6 Program 4 Monday | Read and write | ||||
| Zone 6 Program 4 Tuesday | Read and write | ||||
| Zone 6 Program 4 Wednesday | Read and write | ||||
| Zone 6 Program 4 Thursday | Read and write | ||||
| Zone 6 Program 4 Friday | Read and write | ||||
| Zone 6 Program 4 Saturday | Read and write | ||||
| Zone 6 Program 4 Sunday | Read and write | ||||
| Zone 6 Holiday Start | Read and write | ||||
| Zone 6 Holiday End | Read and write | ||||
| Zone 6 Mode Change End | Read and write | ||||
| Zone 7 Flow Temperature | °C | Read | |||
| Zone 7 Flow Setpoint | °C | Read | |||
| Zone 7 Room Setpoint | °C | Read | |||
| Zone 7 Outside Temperature | °C | Read | |||
| Zone 7 Room Temperature | °C | Read | |||
| Zone 7 Room Temperature Measured | Read and write | ||||
| Zone 7 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 7 DHW Tank Temperature Top | °C | Read | |||
| Zone 7 Heat Demand Active | Read | ||||
| Zone 7 Current Activity | Read | ||||
| Zone 7 Current Mode | Read | ||||
| Zone 7 Heating Mode | Read | ||||
| Zone 7 Pump Running | Read | ||||
| Zone 7 Mixing Valve Closing | Read | ||||
| Zone 7 Mixing Valve Opening | Read | ||||
| Zone 7 Pool Secondary Pump | Read | ||||
| Zone 7 Electric Backup Output | Read | ||||
| Zone 7 Pump Hours | h | Read | |||
| Zone 7 Pump Starts | Read | ||||
| Zone 7 Type | Read | ||||
| Zone 7 Function | Read | ||||
| Zone 7 Short Name | Read | ||||
| Zone 7 Board Device Type | Read | ||||
| Zone 7 Board Instance | Read | ||||
| Zone 7 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 7 Mode | Read and write | ||||
| Zone 7 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 7 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 7 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 7 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 7 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 7 Room Reduced Setpoint | °C | Read and write | |||
| Zone 7 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 7 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 7 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 7 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 7 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 7 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 7 Room Holiday Setpoint | °C | Read and write | |||
| Zone 7 Room Temporary Setpoint | °C | Read and write | |||
| Zone 7 Room Manual Setpoint | °C | Read and write | |||
| Zone 7 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 7 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 7 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 7 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 7 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 7 Process Heat Setpoint | °C | Read and write | |||
| Zone 7 Heating Control Strategy | Read and write | ||||
| Zone 7 Max Flow Setpoint | °C | Read and write | |||
| Zone 7 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 7 Heating Curve Slope | Read and write | ||||
| Zone 7 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 7 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 7 Max Preheat Time | Read and write | ||||
| Zone 7 Mixing Valve Shift | Read and write | ||||
| Zone 7 Mixing Valve Bandwidth | Read and write | ||||
| Zone 7 DHW Hysteresis | Read and write | ||||
| Zone 7 DHW Calorifier Offset | Read and write | ||||
| Zone 7 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 7 Process Heat Hysteresis On | Read and write | ||||
| Zone 7 Process Heat Hysteresis Off | Read and write | ||||
| Zone 7 Process Heat Setpoint Raise | Read and write | ||||
| Zone 7 DHW Start Hysteresis | Read and write | ||||
| Zone 7 Pump Post Run | Read and write | ||||
| Zone 7 Selected Time Program | Read and write | ||||
| Zone 7 Program 1 Monday | Read and write | ||||
| Zone 7 Program 1 Tuesday | Read and write | ||||
| Zone 7 Program 1 Wednesday | Read and write | ||||
| Zone 7 Program 1 Thursday | Read and write | ||||
| Zone 7 Program 1 Friday | Read and write | ||||
| Zone 7 Program 1 Saturday | Read and write | ||||
| Zone 7 Program 1 Sunday | Read and write | ||||
| Zone 7 Program 2 Monday | Read and write | ||||
| Zone 7 Program 2 Tuesday | Read and write | ||||
| Zone 7 Program 2 Wednesday | Read and write | ||||
| Zone 7 Program 2 Thursday | Read and write | ||||
| Zone 7 Program 2 Friday | Read and write | ||||
| Zone 7 Program 2 Saturday | Read and write | ||||
| Zone 7 Program 2 Sunday | Read and write | ||||
| Zone 7 Program 3 Monday | Read and write | ||||
| Zone 7 Program 3 Tuesday | Read and write | ||||
| Zone 7 Program 3 Wednesday | Read and write | ||||
| Zone 7 Program 3 Thursday | Read and write | ||||
| Zone 7 Program 3 Friday | Read and write | ||||
| Zone 7 Program 3 Saturday | Read and write | ||||
| Zone 7 Program 3 Sunday | Read and write | ||||
| Zone 7 Program 4 Monday | Read and write | ||||
| Zone 7 Program 4 Tuesday | Read and write | ||||
| Zone 7 Program 4 Wednesday | Read and write | ||||
| Zone 7 Program 4 Thursday | Read and write | ||||
| Zone 7 Program 4 Friday | Read and write | ||||
| Zone 7 Program 4 Saturday | Read and write | ||||
| Zone 7 Program 4 Sunday | Read and write | ||||
| Zone 7 Holiday Start | Read and write | ||||
| Zone 7 Holiday End | Read and write | ||||
| Zone 7 Mode Change End | Read and write | ||||
| Zone 8 Flow Temperature | °C | Read | |||
| Zone 8 Flow Setpoint | °C | Read | |||
| Zone 8 Room Setpoint | °C | Read | |||
| Zone 8 Outside Temperature | °C | Read | |||
| Zone 8 Room Temperature | °C | Read | |||
| Zone 8 Room Temperature Measured | Read and write | ||||
| Zone 8 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 8 DHW Tank Temperature Top | °C | Read | |||
| Zone 8 Heat Demand Active | Read | ||||
| Zone 8 Current Activity | Read | ||||
| Zone 8 Current Mode | Read | ||||
| Zone 8 Heating Mode | Read | ||||
| Zone 8 Pump Running | Read | ||||
| Zone 8 Mixing Valve Closing | Read | ||||
| Zone 8 Mixing Valve Opening | Read | ||||
| Zone 8 Pool Secondary Pump | Read | ||||
| Zone 8 Electric Backup Output | Read | ||||
| Zone 8 Pump Hours | h | Read | |||
| Zone 8 Pump Starts | Read | ||||
| Zone 8 Type | Read | ||||
| Zone 8 Function | Read | ||||
| Zone 8 Short Name | Read | ||||
| Zone 8 Board Device Type | Read | ||||
| Zone 8 Board Instance | Read | ||||
| Zone 8 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 8 Mode | Read and write | ||||
| Zone 8 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 8 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 8 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 8 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 8 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 8 Room Reduced Setpoint | °C | Read and write | |||
| Zone 8 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 8 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 8 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 8 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 8 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 8 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 8 Room Holiday Setpoint | °C | Read and write | |||
| Zone 8 Room Temporary Setpoint | °C | Read and write | |||
| Zone 8 Room Manual Setpoint | °C | Read and write | |||
| Zone 8 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 8 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 8 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 8 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 8 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 8 Process Heat Setpoint | °C | Read and write | |||
| Zone 8 Heating Control Strategy | Read and write | ||||
| Zone 8 Max Flow Setpoint | °C | Read and write | |||
| Zone 8 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 8 Heating Curve Slope | Read and write | ||||
| Zone 8 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 8 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 8 Max Preheat Time | Read and write | ||||
| Zone 8 Mixing Valve Shift | Read and write | ||||
| Zone 8 Mixing Valve Bandwidth | Read and write | ||||
| Zone 8 DHW Hysteresis | Read and write | ||||
| Zone 8 DHW Calorifier Offset | Read and write | ||||
| Zone 8 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 8 Process Heat Hysteresis On | Read and write | ||||
| Zone 8 Process Heat Hysteresis Off | Read and write | ||||
| Zone 8 Process Heat Setpoint Raise | Read and write | ||||
| Zone 8 DHW Start Hysteresis | Read and write | ||||
| Zone 8 Pump Post Run | Read and write | ||||
| Zone 8 Selected Time Program | Read and write | ||||
| Zone 8 Program 1 Monday | Read and write | ||||
| Zone 8 Program 1 Tuesday | Read and write | ||||
| Zone 8 Program 1 Wednesday | Read and write | ||||
| Zone 8 Program 1 Thursday | Read and write | ||||
| Zone 8 Program 1 Friday | Read and write | ||||
| Zone 8 Program 1 Saturday | Read and write | ||||
| Zone 8 Program 1 Sunday | Read and write | ||||
| Zone 8 Program 2 Monday | Read and write | ||||
| Zone 8 Program 2 Tuesday | Read and write | ||||
| Zone 8 Program 2 Wednesday | Read and write | ||||
| Zone 8 Program 2 Thursday | Read and write | ||||
| Zone 8 Program 2 Friday | Read and write | ||||
| Zone 8 Program 2 Saturday | Read and write | ||||
| Zone 8 Program 2 Sunday | Read and write | ||||
| Zone 8 Program 3 Monday | Read and write | ||||
| Zone 8 Program 3 Tuesday | Read and write | ||||
| Zone 8 Program 3 Wednesday | Read and write | ||||
| Zone 8 Program 3 Thursday | Read and write | ||||
| Zone 8 Program 3 Friday | Read and write | ||||
| Zone 8 Program 3 Saturday | Read and write | ||||
| Zone 8 Program 3 Sunday | Read and write | ||||
| Zone 8 Program 4 Monday | Read and write | ||||
| Zone 8 Program 4 Tuesday | Read and write | ||||
| Zone 8 Program 4 Wednesday | Read and write | ||||
| Zone 8 Program 4 Thursday | Read and write | ||||
| Zone 8 Program 4 Friday | Read and write | ||||
| Zone 8 Program 4 Saturday | Read and write | ||||
| Zone 8 Program 4 Sunday | Read and write | ||||
| Zone 8 Holiday Start | Read and write | ||||
| Zone 8 Holiday End | Read and write | ||||
| Zone 8 Mode Change End | Read and write | ||||
| Zone 9 Flow Temperature | °C | Read | |||
| Zone 9 Flow Setpoint | °C | Read | |||
| Zone 9 Room Setpoint | °C | Read | |||
| Zone 9 Outside Temperature | °C | Read | |||
| Zone 9 Room Temperature | °C | Read | |||
| Zone 9 Room Temperature Measured | Read and write | ||||
| Zone 9 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 9 DHW Tank Temperature Top | °C | Read | |||
| Zone 9 Heat Demand Active | Read | ||||
| Zone 9 Current Activity | Read | ||||
| Zone 9 Current Mode | Read | ||||
| Zone 9 Heating Mode | Read | ||||
| Zone 9 Pump Running | Read | ||||
| Zone 9 Mixing Valve Closing | Read | ||||
| Zone 9 Mixing Valve Opening | Read | ||||
| Zone 9 Pool Secondary Pump | Read | ||||
| Zone 9 Electric Backup Output | Read | ||||
| Zone 9 Pump Hours | h | Read | |||
| Zone 9 Pump Starts | Read | ||||
| Zone 9 Type | Read | ||||
| Zone 9 Function | Read | ||||
| Zone 9 Short Name | Read | ||||
| Zone 9 Board Device Type | Read | ||||
| Zone 9 Board Instance | Read | ||||
| Zone 9 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 9 Mode | Read and write | ||||
| Zone 9 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 9 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 9 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 9 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 9 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 9 Room Reduced Setpoint | °C | Read and write | |||
| Zone 9 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 9 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 9 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 9 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 9 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 9 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 9 Room Holiday Setpoint | °C | Read and write | |||
| Zone 9 Room Temporary Setpoint | °C | Read and write | |||
| Zone 9 Room Manual Setpoint | °C | Read and write | |||
| Zone 9 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 9 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 9 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 9 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 9 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 9 Process Heat Setpoint | °C | Read and write | |||
| Zone 9 Heating Control Strategy | Read and write | ||||
| Zone 9 Max Flow Setpoint | °C | Read and write | |||
| Zone 9 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 9 Heating Curve Slope | Read and write | ||||
| Zone 9 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 9 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 9 Max Preheat Time | Read and write | ||||
| Zone 9 Mixing Valve Shift | Read and write | ||||
| Zone 9 Mixing Valve Bandwidth | Read and write | ||||
| Zone 9 DHW Hysteresis | Read and write | ||||
| Zone 9 DHW Calorifier Offset | Read and write | ||||
| Zone 9 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 9 Process Heat Hysteresis On | Read and write | ||||
| Zone 9 Process Heat Hysteresis Off | Read and write | ||||
| Zone 9 Process Heat Setpoint Raise | Read and write | ||||
| Zone 9 DHW Start Hysteresis | Read and write | ||||
| Zone 9 Pump Post Run | Read and write | ||||
| Zone 9 Selected Time Program | Read and write | ||||
| Zone 9 Program 1 Monday | Read and write | ||||
| Zone 9 Program 1 Tuesday | Read and write | ||||
| Zone 9 Program 1 Wednesday | Read and write | ||||
| Zone 9 Program 1 Thursday | Read and write | ||||
| Zone 9 Program 1 Friday | Read and write | ||||
| Zone 9 Program 1 Saturday | Read and write | ||||
| Zone 9 Program 1 Sunday | Read and write | ||||
| Zone 9 Program 2 Monday | Read and write | ||||
| Zone 9 Program 2 Tuesday | Read and write | ||||
| Zone 9 Program 2 Wednesday | Read and write | ||||
| Zone 9 Program 2 Thursday | Read and write | ||||
| Zone 9 Program 2 Friday | Read and write | ||||
| Zone 9 Program 2 Saturday | Read and write | ||||
| Zone 9 Program 2 Sunday | Read and write | ||||
| Zone 9 Program 3 Monday | Read and write | ||||
| Zone 9 Program 3 Tuesday | Read and write | ||||
| Zone 9 Program 3 Wednesday | Read and write | ||||
| Zone 9 Program 3 Thursday | Read and write | ||||
| Zone 9 Program 3 Friday | Read and write | ||||
| Zone 9 Program 3 Saturday | Read and write | ||||
| Zone 9 Program 3 Sunday | Read and write | ||||
| Zone 9 Program 4 Monday | Read and write | ||||
| Zone 9 Program 4 Tuesday | Read and write | ||||
| Zone 9 Program 4 Wednesday | Read and write | ||||
| Zone 9 Program 4 Thursday | Read and write | ||||
| Zone 9 Program 4 Friday | Read and write | ||||
| Zone 9 Program 4 Saturday | Read and write | ||||
| Zone 9 Program 4 Sunday | Read and write | ||||
| Zone 9 Holiday Start | Read and write | ||||
| Zone 9 Holiday End | Read and write | ||||
| Zone 9 Mode Change End | Read and write | ||||
| Zone 10 Flow Temperature | °C | Read | |||
| Zone 10 Flow Setpoint | °C | Read | |||
| Zone 10 Room Setpoint | °C | Read | |||
| Zone 10 Outside Temperature | °C | Read | |||
| Zone 10 Room Temperature | °C | Read | |||
| Zone 10 Room Temperature Measured | Read and write | ||||
| Zone 10 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 10 DHW Tank Temperature Top | °C | Read | |||
| Zone 10 Heat Demand Active | Read | ||||
| Zone 10 Current Activity | Read | ||||
| Zone 10 Current Mode | Read | ||||
| Zone 10 Heating Mode | Read | ||||
| Zone 10 Pump Running | Read | ||||
| Zone 10 Mixing Valve Closing | Read | ||||
| Zone 10 Mixing Valve Opening | Read | ||||
| Zone 10 Pool Secondary Pump | Read | ||||
| Zone 10 Electric Backup Output | Read | ||||
| Zone 10 Pump Hours | h | Read | |||
| Zone 10 Pump Starts | Read | ||||
| Zone 10 Type | Read | ||||
| Zone 10 Function | Read | ||||
| Zone 10 Short Name | Read | ||||
| Zone 10 Board Device Type | Read | ||||
| Zone 10 Board Instance | Read | ||||
| Zone 10 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 10 Mode | Read and write | ||||
| Zone 10 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 10 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 10 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 10 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 10 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 10 Room Reduced Setpoint | °C | Read and write | |||
| Zone 10 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 10 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 10 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 10 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 10 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 10 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 10 Room Holiday Setpoint | °C | Read and write | |||
| Zone 10 Room Temporary Setpoint | °C | Read and write | |||
| Zone 10 Room Manual Setpoint | °C | Read and write | |||
| Zone 10 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 10 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 10 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 10 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 10 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 10 Process Heat Setpoint | °C | Read and write | |||
| Zone 10 Heating Control Strategy | Read and write | ||||
| Zone 10 Max Flow Setpoint | °C | Read and write | |||
| Zone 10 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 10 Heating Curve Slope | Read and write | ||||
| Zone 10 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 10 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 10 Max Preheat Time | Read and write | ||||
| Zone 10 Mixing Valve Shift | Read and write | ||||
| Zone 10 Mixing Valve Bandwidth | Read and write | ||||
| Zone 10 DHW Hysteresis | Read and write | ||||
| Zone 10 DHW Calorifier Offset | Read and write | ||||
| Zone 10 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 10 Process Heat Hysteresis On | Read and write | ||||
| Zone 10 Process Heat Hysteresis Off | Read and write | ||||
| Zone 10 Process Heat Setpoint Raise | Read and write | ||||
| Zone 10 DHW Start Hysteresis | Read and write | ||||
| Zone 10 Pump Post Run | Read and write | ||||
| Zone 10 Selected Time Program | Read and write | ||||
| Zone 10 Program 1 Monday | Read and write | ||||
| Zone 10 Program 1 Tuesday | Read and write | ||||
| Zone 10 Program 1 Wednesday | Read and write | ||||
| Zone 10 Program 1 Thursday | Read and write | ||||
| Zone 10 Program 1 Friday | Read and write | ||||
| Zone 10 Program 1 Saturday | Read and write | ||||
| Zone 10 Program 1 Sunday | Read and write | ||||
| Zone 10 Program 2 Monday | Read and write | ||||
| Zone 10 Program 2 Tuesday | Read and write | ||||
| Zone 10 Program 2 Wednesday | Read and write | ||||
| Zone 10 Program 2 Thursday | Read and write | ||||
| Zone 10 Program 2 Friday | Read and write | ||||
| Zone 10 Program 2 Saturday | Read and write | ||||
| Zone 10 Program 2 Sunday | Read and write | ||||
| Zone 10 Program 3 Monday | Read and write | ||||
| Zone 10 Program 3 Tuesday | Read and write | ||||
| Zone 10 Program 3 Wednesday | Read and write | ||||
| Zone 10 Program 3 Thursday | Read and write | ||||
| Zone 10 Program 3 Friday | Read and write | ||||
| Zone 10 Program 3 Saturday | Read and write | ||||
| Zone 10 Program 3 Sunday | Read and write | ||||
| Zone 10 Program 4 Monday | Read and write | ||||
| Zone 10 Program 4 Tuesday | Read and write | ||||
| Zone 10 Program 4 Wednesday | Read and write | ||||
| Zone 10 Program 4 Thursday | Read and write | ||||
| Zone 10 Program 4 Friday | Read and write | ||||
| Zone 10 Program 4 Saturday | Read and write | ||||
| Zone 10 Program 4 Sunday | Read and write | ||||
| Zone 10 Holiday Start | Read and write | ||||
| Zone 10 Holiday End | Read and write | ||||
| Zone 10 Mode Change End | Read and write | ||||
| Zone 11 Flow Temperature | °C | Read | |||
| Zone 11 Flow Setpoint | °C | Read | |||
| Zone 11 Room Setpoint | °C | Read | |||
| Zone 11 Outside Temperature | °C | Read | |||
| Zone 11 Room Temperature | °C | Read | |||
| Zone 11 Room Temperature Measured | Read and write | ||||
| Zone 11 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 11 DHW Tank Temperature Top | °C | Read | |||
| Zone 11 Heat Demand Active | Read | ||||
| Zone 11 Current Activity | Read | ||||
| Zone 11 Current Mode | Read | ||||
| Zone 11 Heating Mode | Read | ||||
| Zone 11 Pump Running | Read | ||||
| Zone 11 Mixing Valve Closing | Read | ||||
| Zone 11 Mixing Valve Opening | Read | ||||
| Zone 11 Pool Secondary Pump | Read | ||||
| Zone 11 Electric Backup Output | Read | ||||
| Zone 11 Pump Hours | h | Read | |||
| Zone 11 Pump Starts | Read | ||||
| Zone 11 Type | Read | ||||
| Zone 11 Function | Read | ||||
| Zone 11 Short Name | Read | ||||
| Zone 11 Board Device Type | Read | ||||
| Zone 11 Board Instance | Read | ||||
| Zone 11 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 11 Mode | Read and write | ||||
| Zone 11 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 11 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 11 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 11 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 11 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 11 Room Reduced Setpoint | °C | Read and write | |||
| Zone 11 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 11 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 11 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 11 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 11 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 11 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 11 Room Holiday Setpoint | °C | Read and write | |||
| Zone 11 Room Temporary Setpoint | °C | Read and write | |||
| Zone 11 Room Manual Setpoint | °C | Read and write | |||
| Zone 11 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 11 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 11 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 11 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 11 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 11 Process Heat Setpoint | °C | Read and write | |||
| Zone 11 Heating Control Strategy | Read and write | ||||
| Zone 11 Max Flow Setpoint | °C | Read and write | |||
| Zone 11 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 11 Heating Curve Slope | Read and write | ||||
| Zone 11 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 11 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 11 Max Preheat Time | Read and write | ||||
| Zone 11 Mixing Valve Shift | Read and write | ||||
| Zone 11 Mixing Valve Bandwidth | Read and write | ||||
| Zone 11 DHW Hysteresis | Read and write | ||||
| Zone 11 DHW Calorifier Offset | Read and write | ||||
| Zone 11 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 11 Process Heat Hysteresis On | Read and write | ||||
| Zone 11 Process Heat Hysteresis Off | Read and write | ||||
| Zone 11 Process Heat Setpoint Raise | Read and write | ||||
| Zone 11 DHW Start Hysteresis | Read and write | ||||
| Zone 11 Pump Post Run | Read and write | ||||
| Zone 11 Selected Time Program | Read and write | ||||
| Zone 11 Program 1 Monday | Read and write | ||||
| Zone 11 Program 1 Tuesday | Read and write | ||||
| Zone 11 Program 1 Wednesday | Read and write | ||||
| Zone 11 Program 1 Thursday | Read and write | ||||
| Zone 11 Program 1 Friday | Read and write | ||||
| Zone 11 Program 1 Saturday | Read and write | ||||
| Zone 11 Program 1 Sunday | Read and write | ||||
| Zone 11 Program 2 Monday | Read and write | ||||
| Zone 11 Program 2 Tuesday | Read and write | ||||
| Zone 11 Program 2 Wednesday | Read and write | ||||
| Zone 11 Program 2 Thursday | Read and write | ||||
| Zone 11 Program 2 Friday | Read and write | ||||
| Zone 11 Program 2 Saturday | Read and write | ||||
| Zone 11 Program 2 Sunday | Read and write | ||||
| Zone 11 Program 3 Monday | Read and write | ||||
| Zone 11 Program 3 Tuesday | Read and write | ||||
| Zone 11 Program 3 Wednesday | Read and write | ||||
| Zone 11 Program 3 Thursday | Read and write | ||||
| Zone 11 Program 3 Friday | Read and write | ||||
| Zone 11 Program 3 Saturday | Read and write | ||||
| Zone 11 Program 3 Sunday | Read and write | ||||
| Zone 11 Program 4 Monday | Read and write | ||||
| Zone 11 Program 4 Tuesday | Read and write | ||||
| Zone 11 Program 4 Wednesday | Read and write | ||||
| Zone 11 Program 4 Thursday | Read and write | ||||
| Zone 11 Program 4 Friday | Read and write | ||||
| Zone 11 Program 4 Saturday | Read and write | ||||
| Zone 11 Program 4 Sunday | Read and write | ||||
| Zone 11 Holiday Start | Read and write | ||||
| Zone 11 Holiday End | Read and write | ||||
| Zone 11 Mode Change End | Read and write | ||||
| Zone 12 Flow Temperature | °C | Read | |||
| Zone 12 Flow Setpoint | °C | Read | |||
| Zone 12 Room Setpoint | °C | Read | |||
| Zone 12 Outside Temperature | °C | Read | |||
| Zone 12 Room Temperature | °C | Read | |||
| Zone 12 Room Temperature Measured | Read and write | ||||
| Zone 12 DHW Tank Temperature Bottom | °C | Read | |||
| Zone 12 DHW Tank Temperature Top | °C | Read | |||
| Zone 12 Heat Demand Active | Read | ||||
| Zone 12 Current Activity | Read | ||||
| Zone 12 Current Mode | Read | ||||
| Zone 12 Heating Mode | Read | ||||
| Zone 12 Pump Running | Read | ||||
| Zone 12 Mixing Valve Closing | Read | ||||
| Zone 12 Mixing Valve Opening | Read | ||||
| Zone 12 Pool Secondary Pump | Read | ||||
| Zone 12 Electric Backup Output | Read | ||||
| Zone 12 Pump Hours | h | Read | |||
| Zone 12 Pump Starts | Read | ||||
| Zone 12 Type | Read | ||||
| Zone 12 Function | Read | ||||
| Zone 12 Short Name | Read | ||||
| Zone 12 Board Device Type | Read | ||||
| Zone 12 Board Instance | Read | ||||
| Zone 12 Fixed Flow Setpoint | °C | Read and write | |||
| Zone 12 Mode | Read and write | ||||
| Zone 12 Room Activity Setpoint 1 | °C | Read and write | |||
| Zone 12 Room Activity Setpoint 2 | °C | Read and write | |||
| Zone 12 Room Activity Setpoint 3 | °C | Read and write | |||
| Zone 12 Room Activity Setpoint 4 | °C | Read and write | |||
| Zone 12 Room Activity Setpoint 5 | °C | Read and write | |||
| Zone 12 Room Reduced Setpoint | °C | Read and write | |||
| Zone 12 Room Cooling Setpoint 1 | °C | Read and write | |||
| Zone 12 Room Cooling Setpoint 2 | °C | Read and write | |||
| Zone 12 Room Cooling Setpoint 3 | °C | Read and write | |||
| Zone 12 Room Cooling Setpoint 4 | °C | Read and write | |||
| Zone 12 Room Cooling Setpoint 5 | °C | Read and write | |||
| Zone 12 Room Cooling Reduced Setpoint | °C | Read and write | |||
| Zone 12 Room Holiday Setpoint | °C | Read and write | |||
| Zone 12 Room Temporary Setpoint | °C | Read and write | |||
| Zone 12 Room Manual Setpoint | °C | Read and write | |||
| Zone 12 DHW Comfort Setpoint | °C | Read and write | |||
| Zone 12 DHW Reduced Setpoint | °C | Read and write | |||
| Zone 12 DHW Holiday Setpoint | °C | Read and write | |||
| Zone 12 DHW Anti Legionella Setpoint | °C | Read and write | |||
| Zone 12 Swimming Pool Setpoint | °C | Read and write | |||
| Zone 12 Process Heat Setpoint | °C | Read and write | |||
| Zone 12 Heating Control Strategy | Read and write | ||||
| Zone 12 Max Flow Setpoint | °C | Read and write | |||
| Zone 12 Cooling Flow Setpoint | °C | Read and write | |||
| Zone 12 Heating Curve Slope | Read and write | ||||
| Zone 12 Heating Curve Footpoint Comfort | °C | Read and write | |||
| Zone 12 Heating Curve Footpoint Reduced | °C | Read and write | |||
| Zone 12 Max Preheat Time | Read and write | ||||
| Zone 12 Mixing Valve Shift | Read and write | ||||
| Zone 12 Mixing Valve Bandwidth | Read and write | ||||
| Zone 12 DHW Hysteresis | Read and write | ||||
| Zone 12 DHW Calorifier Offset | Read and write | ||||
| Zone 12 DHW Calorifier Setpoint Raise | Read and write | ||||
| Zone 12 Process Heat Hysteresis On | Read and write | ||||
| Zone 12 Process Heat Hysteresis Off | Read and write | ||||
| Zone 12 Process Heat Setpoint Raise | Read and write | ||||
| Zone 12 DHW Start Hysteresis | Read and write | ||||
| Zone 12 Pump Post Run | Read and write | ||||
| Zone 12 Selected Time Program | Read and write | ||||
| Zone 12 Program 1 Monday | Read and write | ||||
| Zone 12 Program 1 Tuesday | Read and write | ||||
| Zone 12 Program 1 Wednesday | Read and write | ||||
| Zone 12 Program 1 Thursday | Read and write | ||||
| Zone 12 Program 1 Friday | Read and write | ||||
| Zone 12 Program 1 Saturday | Read and write | ||||
| Zone 12 Program 1 Sunday | Read and write | ||||
| Zone 12 Program 2 Monday | Read and write | ||||
| Zone 12 Program 2 Tuesday | Read and write | ||||
| Zone 12 Program 2 Wednesday | Read and write | ||||
| Zone 12 Program 2 Thursday | Read and write | ||||
| Zone 12 Program 2 Friday | Read and write | ||||
| Zone 12 Program 2 Saturday | Read and write | ||||
| Zone 12 Program 2 Sunday | Read and write | ||||
| Zone 12 Program 3 Monday | Read and write | ||||
| Zone 12 Program 3 Tuesday | Read and write | ||||
| Zone 12 Program 3 Wednesday | Read and write | ||||
| Zone 12 Program 3 Thursday | Read and write | ||||
| Zone 12 Program 3 Friday | Read and write | ||||
| Zone 12 Program 3 Saturday | Read and write | ||||
| Zone 12 Program 3 Sunday | Read and write | ||||
| Zone 12 Program 4 Monday | Read and write | ||||
| Zone 12 Program 4 Tuesday | Read and write | ||||
| Zone 12 Program 4 Wednesday | Read and write | ||||
| Zone 12 Program 4 Thursday | Read and write | ||||
| Zone 12 Program 4 Friday | Read and write | ||||
| Zone 12 Program 4 Saturday | Read and write | ||||
| Zone 12 Program 4 Sunday | Read and write | ||||
| Zone 12 Holiday Start | Read and write | ||||
| Zone 12 Holiday End | Read and write | ||||
| Zone 12 Mode Change End | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show flow, return and outdoor temperature and water pressure of a Remeha boiler on one ModbusCloud dashboard.
- Get an email when the appliance error code changes or the water pressure drops below a threshold you set.
- Track burner starts, burner hours and energy for heating and hot water in the 365-day history.
- Change the room or DHW setpoint of a zone remotely from the portal.
- Compare flow temperature and status of each appliance in a cascade to see which one is running.
- Check the service notification and hours since the last service before a maintenance visit.
Installation
Mount the GTW-08 on the L-Bus of the appliance as described in the Remeha installation manual.
Set the Modbus address with the rotary dial (0 gives 100) and baud rate and parity with DIP switches 1 to 4.
Connect RS485 A and B of the GTW-08 to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.
In ModbusCloud, add a Modbus device with the same address, speed and parity, and import this template.
Check that Flow Temperature and Water Pressure show plausible values and that Number Of Zones matches the installation.
Things to watch for
The GTW-08 does not answer. What should I check?
Check the address on the rotary dial (position 0 is address 100, not 0), the baud rate and parity on DIP switches 1 to 4, and swap A and B. Add a termination resistor at both ends of the bus. A blinking orange LED on the GTW-08 means there is a problem.
Why do zone registers return nothing or an error?
Not every zone exists on every appliance. Read Number Of Zones and the zone Type and Function first; a zone with type 0 is not present. Each zone uses the same layout 512 registers further. If the appliance was changed after installing the GTW-08, write 90 to Reset Discovery Table so it scans the boards again.
Why are some temperatures 100 times too high or too low?
Water and outdoor temperatures use 0.01 °C, room temperatures 0.1 °C. Some parameters such as hystereses and offsets have no stated resolution and are shown unscaled. Compare one value with the display of the appliance and adjust the scale in the portal if needed.
How do I control the boiler through Modbus?
Write Algorithm Type first: 0 power and temperature, 1 power, 2 temperature. At 3 the appliance ignores the heat demand registers. Then write Heat Demand Type (7 heating, 8 cooling) and the power or temperature setpoint. Writing registers is off per Gateway until it is enabled on request; write only setpoints you understand.
Can several appliances share one GTW-08?
One GTW-08 serves one appliance and its L-Bus boards. In a cascade the master reports the cascade registers and the flow temperature and status of each member. Several GTW-08 on one RS485 bus each need their own address.