SATEC SATEC PM130 PLUS Min/Max Log Modbus RTU template

SATEC PM130 PLUS Min/Max Log

Panel meter log of minimum and maximum voltage, current, power and demand values with time stamps.

The SATEC PM130 PLUS is a three-phase panel meter that keeps a log of minimum and maximum values in switchboards and substations. This Modbus RTU template reads the logged extremes of voltage, current, power, power factor and frequency, and the maximum demands per tariff, each with its time stamp, into ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
144, read only
Brand
SATEC
Key readings
Minimum and maximum voltage · Minimum and maximum current · Minimum and maximum power · Maximum demand · Maximum demand per tariff · Time of each extreme
Compatible models
PM130P PLUS · PM130E PLUS · PM130EH PLUS
Last updated

Registers (144)

144 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Minimum V1/V12 VoltageVRead35840FC03uint32
Minimum V1/V12 Voltage TimesRead35842FC03uint32
Minimum V2/V23 VoltageVRead35844FC03uint32
Minimum V2/V23 Voltage TimesRead35846FC03uint32
Minimum V3/V31 VoltageVRead35848FC03uint32
Minimum V3/V31 Voltage TimesRead
Minimum I1 CurrentARead
Minimum I1 Current TimesRead
Minimum I2 CurrentARead
Minimum I2 Current TimesRead
Minimum I3 CurrentARead
Minimum I3 Current TimesRead
Maximum V1/V12 VoltageVRead
Maximum V1/V12 Voltage TimesRead
Maximum V2/V23 VoltageVRead
Maximum V2/V23 Voltage TimesRead
Maximum V3/V31 VoltageVRead
Maximum V3/V31 Voltage TimesRead
Maximum I1 CurrentARead
Maximum I1 Current TimesRead
Maximum I2 CurrentARead
Maximum I2 Current TimesRead
Maximum I3 CurrentARead
Maximum I3 Current TimesRead
Minimum Total kWkWRead
Minimum Total kW TimesRead
Minimum Total kvarkvarRead
Minimum Total kvar TimesRead
Minimum Total kVAkVARead
Minimum Total kVA TimesRead
Minimum Total Power FactorRead
Minimum Total Power Factor TimesRead
Maximum Total kWkWRead
Maximum Total kW TimesRead
Maximum Total kvarkvarRead
Maximum Total kvar TimesRead
Maximum Total kVAkVARead
Maximum Total kVA TimesRead
Maximum Total Power FactorRead
Maximum Total Power Factor TimesRead
Minimum Neutral CurrentARead
Minimum Neutral Current TimesRead
Minimum FrequencyHzRead
Minimum Frequency TimesRead
Maximum Neutral CurrentARead
Maximum Neutral Current TimesRead
Maximum FrequencyHzRead
Maximum Frequency TimesRead
Summary Register 1 Maximum DemandRead
Summary Register 1 Maximum Demand TimesRead
Summary Register 2 Maximum DemandRead
Summary Register 2 Maximum Demand TimesRead
Summary Register 3 Maximum DemandRead
Summary Register 3 Maximum Demand TimesRead
Summary Register 4 Maximum DemandRead
Summary Register 4 Maximum Demand TimesRead
V1/V12 Maximum Volt DemandVRead
V1/V12 Maximum Volt Demand TimesRead
V2/V23 Maximum Volt DemandVRead
V2/V23 Maximum Volt Demand TimesRead
V3/V31 Maximum Volt DemandVRead
V3/V31 Maximum Volt Demand TimesRead
I1 Maximum Ampere DemandARead
I1 Maximum Ampere Demand TimesRead
I2 Maximum Ampere DemandARead
I2 Maximum Ampere Demand TimesRead
I3 Maximum Ampere DemandARead
I3 Maximum Ampere Demand TimesRead
Maximum kW Import Sliding Window DemandkWRead
Maximum kW Import Sliding Window Demand TimesRead
Maximum kvar Import Sliding Window DemandkvarRead
Maximum kvar Import Sliding Window Demand TimesRead
Maximum kVA Sliding Window DemandkVARead
Maximum kVA Sliding Window Demand TimesRead
Maximum kW Export Sliding Window DemandkWRead
Maximum kW Export Sliding Window Demand TimesRead
Maximum kvar Export Sliding Window DemandkvarRead
Maximum kvar Export Sliding Window Demand TimesRead
In Maximum Ampere DemandARead
In Maximum Ampere Demand TimesRead
TOU Register 1 Tariff 1 Maximum DemandRead
TOU Register 1 Tariff 1 Maximum Demand TimesRead
TOU Register 1 Tariff 2 Maximum DemandRead
TOU Register 1 Tariff 2 Maximum Demand TimesRead
TOU Register 1 Tariff 3 Maximum DemandRead
TOU Register 1 Tariff 3 Maximum Demand TimesRead
TOU Register 1 Tariff 4 Maximum DemandRead
TOU Register 1 Tariff 4 Maximum Demand TimesRead
TOU Register 1 Tariff 5 Maximum DemandRead
TOU Register 1 Tariff 5 Maximum Demand TimesRead
TOU Register 1 Tariff 6 Maximum DemandRead
TOU Register 1 Tariff 6 Maximum Demand TimesRead
TOU Register 1 Tariff 7 Maximum DemandRead
TOU Register 1 Tariff 7 Maximum Demand TimesRead
TOU Register 1 Tariff 8 Maximum DemandRead
TOU Register 1 Tariff 8 Maximum Demand TimesRead
TOU Register 2 Tariff 1 Maximum DemandRead
TOU Register 2 Tariff 1 Maximum Demand TimesRead
TOU Register 2 Tariff 2 Maximum DemandRead
TOU Register 2 Tariff 2 Maximum Demand TimesRead
TOU Register 2 Tariff 3 Maximum DemandRead
TOU Register 2 Tariff 3 Maximum Demand TimesRead
TOU Register 2 Tariff 4 Maximum DemandRead
TOU Register 2 Tariff 4 Maximum Demand TimesRead
TOU Register 2 Tariff 5 Maximum DemandRead
TOU Register 2 Tariff 5 Maximum Demand TimesRead
TOU Register 2 Tariff 6 Maximum DemandRead
TOU Register 2 Tariff 6 Maximum Demand TimesRead
TOU Register 2 Tariff 7 Maximum DemandRead
TOU Register 2 Tariff 7 Maximum Demand TimesRead
TOU Register 2 Tariff 8 Maximum DemandRead
TOU Register 2 Tariff 8 Maximum Demand TimesRead
TOU Register 3 Tariff 1 Maximum DemandRead
TOU Register 3 Tariff 1 Maximum Demand TimesRead
TOU Register 3 Tariff 2 Maximum DemandRead
TOU Register 3 Tariff 2 Maximum Demand TimesRead
TOU Register 3 Tariff 3 Maximum DemandRead
TOU Register 3 Tariff 3 Maximum Demand TimesRead
TOU Register 3 Tariff 4 Maximum DemandRead
TOU Register 3 Tariff 4 Maximum Demand TimesRead
TOU Register 3 Tariff 5 Maximum DemandRead
TOU Register 3 Tariff 5 Maximum Demand TimesRead
TOU Register 3 Tariff 6 Maximum DemandRead
TOU Register 3 Tariff 6 Maximum Demand TimesRead
TOU Register 3 Tariff 7 Maximum DemandRead
TOU Register 3 Tariff 7 Maximum Demand TimesRead
TOU Register 3 Tariff 8 Maximum DemandRead
TOU Register 3 Tariff 8 Maximum Demand TimesRead
TOU Register 4 Tariff 1 Maximum DemandRead
TOU Register 4 Tariff 1 Maximum Demand TimesRead
TOU Register 4 Tariff 2 Maximum DemandRead
TOU Register 4 Tariff 2 Maximum Demand TimesRead
TOU Register 4 Tariff 3 Maximum DemandRead
TOU Register 4 Tariff 3 Maximum Demand TimesRead
TOU Register 4 Tariff 4 Maximum DemandRead
TOU Register 4 Tariff 4 Maximum Demand TimesRead
TOU Register 4 Tariff 5 Maximum DemandRead
TOU Register 4 Tariff 5 Maximum Demand TimesRead
TOU Register 4 Tariff 6 Maximum DemandRead
TOU Register 4 Tariff 6 Maximum Demand TimesRead
TOU Register 4 Tariff 7 Maximum DemandRead
TOU Register 4 Tariff 7 Maximum Demand TimesRead
TOU Register 4 Tariff 8 Maximum DemandRead
TOU Register 4 Tariff 8 Maximum Demand TimesRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show the highest current per phase and when it occurred on a ModbusCloud dashboard.
  • Send an alarm when the maximum kW demand of the month passes the contracted capacity.
  • Keep the minimum voltage per phase in history to find dips on a feeder.
  • Compare maximum demand per tariff between months for an energy report.
  • Check the time of the last maximum demand before you discuss a peak with the customer.

Installation

  1. Wire the RS485 port of the PM130 PLUS to the ModbusCloud Gateway, A to A and B to B, with termination at the end of the bus.

  2. Check the Modbus address, baud rate and parity of the meter in its communication setup.

  3. In ModbusCloud add a Modbus device on the Gateway with the same address as the main PM130 PLUS template, and import this template.

  4. Check that the maximum values and time stamps arrive; a time of 0 means the value has not been logged yet.

Things to watch for

Why are the maximum demand values zero?

Power and tariff demands are only measured by PM130E and PM130EH meters. On a PM130P these registers stay at zero. On E models check that the demand period has passed at least once since the log was cleared.

How do I read the time stamps?

Each time stamp is the number of seconds since 1 January 1970 as kept by the meter clock. Set the meter clock correctly, otherwise the moments in the log are shifted.

The values are a factor 10 or 100 off. What is wrong?

The meter has a low and a high resolution option. This template assumes the default low resolution: 1 V, 1 A and 1 kW. With high resolution and PT ratio 1 the meter returns 0.1 V, 0.01 A and 1 W, so change the scale of those registers.

Can I clear the min/max log from ModbusCloud?

Not with this template, which only reads. The clear command is in the PM130 PLUS control and status template.