SEW-Eurodrive SEW-Eurodrive MOVITRAC LTE-B Modbus RTU template

SEW-Eurodrive MOVITRAC LTE-B

Compact frequency inverter with speed control, status and drive parameters.

The SEW-Eurodrive MOVITRAC LTE-B is a compact frequency inverter that controls the speed of three phase motors in conveyors, fans and pumps. This Modbus RTU template reads status, actual speed, current, DC link voltage, temperature and all drive parameters, and lets you write the control word, speed setpoint and ramp time from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 115200 baud
Registers
62, read and write
Key readings
Status word · Actual speed · Actual current · DC link voltage · Heat sink temperature · Operating hours
Available commands
Control word · Speed setpoint · Ramp time
Compatible models
MOVITRAC LTE-B
Last updated

Registers (62)

62 read, 3 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Status WordRead
Actual Speed%Read
Actual Current%Read
Setpoint Speed DisplayHzRead
DC Link VoltageVRead
Heat Sink Temperature°CRead
Analog Input 1%Read
Analog Input 1 ScaledRead
Digital Input StatusRead
Operating HourshRead
Operating Hours Min SecsRead
Run Time Since Stop HourshRead
Run Time Since Stop Min SecsRead
Control WordRead and write
Setpoint Speed%Read and write
Ramp TimemsRead and write
Inverter IDRead
Power ClassRead
Voltage ClassRead
IO Software VersionRead
Motor Control Software VersionRead
Inverter TypeRead
Maximum SpeedHzRead
Minimum SpeedHzRead
Acceleration Ramp TimesRead
Deceleration Ramp TimeRead
Stop Mode SelectionRead
Energy Saving FunctionRead
Nominal Motor VoltageRead
Nominal Motor CurrentRead
Rated Motor FrequencyRead
Nominal Motor SpeedRead
Voltage BoostRead
Control Signal SourceRead
Error LogRead
Advanced Menu AccessRead
Digital Input FunctionRead
Analog Input FormatRead
PWM Switching FrequencyRead
Relay Output FunctionRead
Relay Threshold LevelRead
Fixed Setpoint Speed 1Read
Fixed Setpoint Speed 2Read
Fixed Setpoint Speed 3Read
Fixed Setpoint Speed 4Read
Deceleration Ramp 2Read
Analog Output FunctionRead
Speed Skip BandRead
Speed Skip CenterRead
V/f Adjustment VoltageRead
V/f Adjustment FrequencyRead
Terminal Mode RestartRead
Keypad Mode RestartRead
DC Hold TimeRead
Flying StartRead
Brake ChopperRead
Analog Input ScalingRead
Fieldbus SettingsRead
Access CodeRead
Parameter LockRead
Analog Input OffsetRead
Speed Scaling FactorRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show actual speed, current and status of each drive on one dashboard for a conveyor or ventilation system.
  • Get an alert when the error bit in the status word is set or the heat sink temperature rises above your limit.
  • Track operating hours per drive to plan maintenance on motors and fans.
  • Change the speed setpoint of a fan or pump remotely without going to the panel.
  • Compare DC link voltage over a year of history to spot supply problems.

Installation

  1. Connect the RJ45 communication socket of the inverter to the RS485 port of the ModbusCloud Gateway, A to A and B to B, with termination at both ends of the bus.

  2. Set P-14 to 101 for the advanced menu, then set P-12 to 5 (control word and speed) or 6 (also ramp time).

  3. Set the Modbus address and baud rate in P-36; the default speed is 115200 baud, 8 data bits, no parity, 1 stop bit.

  4. In ModbusCloud, add a Modbus device with the same address and settings and import this template.

  5. Check that status word, DC link voltage and heat sink temperature come in before you write a setpoint.

Things to watch for

The inverter does not answer on the bus. What should I check?

Check address, baud rate and timeout in P-36 and that ModbusCloud uses the same speed with 8 data bits, no parity and 1 stop bit. The default is 115200 baud; long cables work better at a lower speed. Check the wiring in the RJ45 socket and the termination at both ends of the bus.

Writing the control word or speed has no effect. Why?

The inverter only takes commands over Modbus when P-12 is 5 or 6. With 5 the ramp comes from P-03 and P-04; with 6 the ramp time register is used. A control word of 6 enables the drive; 0 on bit 0 inhibits it. The speed setpoint is a percentage of maximum speed, 16393 means 100 percent.

The drive stops when the connection drops. Is that intended?

That depends on the timeout setting in P-36. With 0 the drive keeps the last data; a t setting trips with an error after the set time, an r setting ramps the motor down. Choose the behavior that is safe for the installation before you control the drive remotely.

How do I read the error code of the inverter?

Read the status word. When bit 5 is set, the high byte holds the error, for example 0x07 overvoltage on the DC bus, 0x08 motor overload or 0x0B overtemperature. Write a rising edge on bit 6 of the control word to reset the error once the cause is solved.