manufacturer_and_model_number Device manufacturer name and model identifier string. | 1 | FC03 | string | | R |
serial_number Unique factory serial number string for this unit. | 17 | FC03 | string | | R |
grid_voltage_l1 AC grid voltage on phase L1, in volts. | 101 | FC03 | int16 | V | R |
grid_voltage_l2 AC grid voltage on phase L2, in volts. | 102 | FC03 | int16 | V | R |
grid_voltage_l3 AC grid voltage on phase L3, in volts. | 103 | FC03 | int16 | V | R |
grid_current_l1 AC grid current on phase L1, in amperes. | 104 | FC03 | int16 | A | R |
grid_current_l2 AC grid current on phase L2, in amperes. | 105 | FC03 | int16 | A | R |
grid_current_l3 AC grid current on phase L3, in amperes. | 106 | FC03 | int16 | A | R |
frequency AC grid frequency, in hertz. | 107 | FC03 | int16 | Hz | R |
active_power_l1 Active power on phase L1, in watts. | 110 | FC03 | int16 | W | R |
active_power_l2 Active power on phase L2, in watts. | 111 | FC03 | int16 | W | R |
active_power_l3 Active power on phase L3, in watts. | 112 | FC03 | int16 | W | R |
reactive_power_l1 Reactive power on phase L1. | 113 | FC03 | int16 | W | R |
reactive_power_l2 Reactive power on phase L2. | 114 | FC03 | int16 | W | R |
reactive_power_l3 Reactive power on phase L3. | 115 | FC03 | int16 | W | R |
apperent_power_l1 Apparent power on phase L1. | 116 | FC03 | int16 | W | R |
apperent_power_l2 Apparent power on phase L2. | 117 | FC03 | int16 | W | R |
apperent_power_l3 Apparent power on phase L3. | 118 | FC03 | int16 | W | R |
cos_phi_l1 Power factor (cos phi) on phase L1. | 119 | FC03 | int16 | | R |
cos_phi_l2 Power factor (cos phi) on phase L2. | 120 | FC03 | int16 | | R |
cos_phi_l3 Power factor (cos phi) on phase L3. | 121 | FC03 | int16 | | R |
active_power Total three-phase active power, in watts. | 122 | FC03 | int16 | W | R |
reactive_power Total three-phase reactive power, in var. | 123 | FC03 | int16 | var | R |
apparent_power Total three-phase apparent power, in VA. | 124 | FC03 | int16 | VA | R |
cos_phi Overall three-phase power factor (cos phi). | 125 | FC03 | int16 | | R |
temperature_of_ac_heat_sink AC-side power stage heat sink temperature. | 132 | FC03 | int16 | °C | R |
dc_voltage_positive Positive DC bus voltage. | 133 | FC03 | int16 | V | R |
dc_voltage_negative Negative DC bus voltage. | 134 | FC03 | int16 | V | R |
set_active_power_a Active power setpoint readback, in watts. | 135 | FC03 | int16 | W | R |
set_reactive_power_a Reactive power setpoint readback. | 136 | FC03 | int16 | W | R |
set_off_grid_voltage_a Off-grid output voltage setpoint readback, in volts. | 137 | FC03 | int16 | V | R |
set_off_grid_frequency_a Off-grid output frequency setpoint readback, in hertz. | 138 | FC03 | int16 | Hz | R |
dc_power DC-side power, in watts. | 141 | FC03 | int16 | W | R |
dc_voltage DC-side voltage, in volts. | 142 | FC03 | int16 | V | R |
dc_current DC-side current, in amperes. | 143 | FC03 | int16 | A | R |
dc_charge_energy Cumulative DC charge energy, in watt-hours. | 144 | FC03 | uint32 | Wh | R |
dc_discharge_energy Cumulative DC discharge energy, in watt-hours. | 146 | FC03 | uint32 | Wh | R |
temperature_of_dc_dc_heat_sink DC-DC converter heat sink temperature. | 148 | FC03 | int16 | °C | R |
dc_relay_rear_end_voltage Voltage at the rear end of the DC relay, in volts. | 224 | FC03 | int16 | V | R |
charge_max_current_read Maximum charge current limit, readback. | 225 | FC03 | uint16 | A | R |
discharge_max_current_read Maximum discharge current limit, readback. | 226 | FC03 | uint16 | A | R |
ip_address_block_1_a First octet of the device IP address. | 300 | FC03 | uint16 | | R |
ip_address_block_2_a Second octet of the device IP address. | 301 | FC03 | uint16 | | R |
ip_address_block_3_a Third octet of the device IP address. | 302 | FC03 | uint16 | | R |
ip_address_block_4_a Fourth octet of the device IP address. | 303 | FC03 | uint16 | | R |
netmask_block_1_a First octet of the network subnet mask. | 304 | FC03 | uint16 | | R |
netmask_block_2_a Second octet of the network subnet mask. | 305 | FC03 | uint16 | | R |
netmask_block_3_a Third octet of the network subnet mask. | 306 | FC03 | uint16 | | R |
netmask_block_4_a Fourth octet of the network subnet mask. | 307 | FC03 | uint16 | | R |
gateway_ip_block_1_a First octet of the network gateway IP address. | 308 | FC03 | uint16 | | R |
gateway_ip_block_2_a Second octet of the network gateway IP address. | 309 | FC03 | uint16 | | R |
gateway_ip_block_3_a Third octet of the network gateway IP address. | 310 | FC03 | uint16 | | R |
gateway_ip_block_4_a Fourth octet of the network gateway IP address. | 311 | FC03 | uint16 | | R |
mac_a Device MAC address string. | 312 | FC03 | string | | R |
modbus_unit_id_a Configured Modbus unit ID of this device. | 316 | FC03 | uint16 | | R |
baudrate_a RS-485 communication baud rate setting. | 320 | FC03 | uint16 | | R |
interface_type_a Active communication interface type selection. | 325 | FC03 | uint16 | | R |
communication_protocol_selection_a Active communication protocol selection (e.g. Modbus RTU/TCP). | 326 | FC03 | uint16 | | R |
ems_timeout_a EMS communication timeout setting. | 327 | FC03 | uint16 | s | R |
epo_enable_a Emergency power-off (EPO) function enable flag. | 328 | FC03 | uint16 | | R |
bms_timeout_a BMS communication timeout setting. | 329 | FC03 | uint16 | s | R |
bms_protocol_selection_a BMS communication protocol selection. | 330 | FC03 | uint16 | | R |
set_grid_mode_a Grid mode configuration (on-grid or off-grid). | 331 | FC03 | uint16 | | R |
buzzer_enable_a Audible buzzer alarm enable flag. | 332 | FC03 | uint16 | | R |
restore_factory_setting_a Factory settings restore command register. | 333 | FC03 | uint16 | | R |
start_inverter_a Inverter start command register readback. | 650 | FC03 | uint16 | | R |
stop_inverter_a Inverter stop command register readback. | 651 | FC03 | uint16 | | R |
clear_failure_a Fault clear command register readback. | 652 | FC03 | uint16 | | R |
set_on_grid_mode_a On-grid mode command register readback. | 653 | FC03 | uint16 | | R |
set_off_grid_mode_a Off-grid mode command register readback. | 654 | FC03 | uint16 | | R |
set_standby_command_a Standby command register readback. | 655 | FC03 | uint16 | | R |
set_soft_start_a AC soft-start command register readback. | 656 | FC03 | uint16 | | R |
reset_instruction_a Device reset instruction register readback. | 657 | FC03 | uint16 | | R |
grid_stop_a Grid disconnect command register readback. | 658 | FC03 | uint16 | | R |
voltage_level Configured nominal AC voltage level. | 748 | FC03 | uint16 | V | R |
frequency_level Configured nominal grid frequency level. | 749 | FC03 | uint16 | Hz | R |
inverter_wiring_topology Inverter wiring topology configuration (e.g. 3P3W or 3P4W). | 750 | FC03 | uint16 | | R |
switching_device_access_setting_a Switching device access permission setting. | 752 | FC03 | uint16 | | R |
module_power_level Rated power level of the inverter module. | 753 | FC03 | uint16 | W | R |
dc_voltage_level Configured DC voltage level. | 754 | FC03 | uint16 | V | R |
cpu_type_a CPU type identifier for this inverter module. | 755 | FC03 | uint16 | | R |
off_grid_and_parallel_enable_a Off-grid and parallel operation enable flag. | 756 | FC03 | uint16 | | R |
set_dc_soft_start_external_control_a DC soft-start external control enable flag. | 757 | FC03 | uint16 | | R |
grid_over_voltage_protection_amplitude_a Grid overvoltage protection trip threshold. | 768 | FC03 | int16 | V | R |
ac_over_voltage_trip_time_1_a AC overvoltage trip delay time, level 1. | 769 | FC03 | int16 | s | R |
ac_over_voltage_trip_level_2_a AC overvoltage trip threshold, level 2. | 770 | FC03 | int16 | V | R |
ac_over_voltage_trip_time_2_a AC overvoltage trip delay time, level 2. | 771 | FC03 | int16 | s | R |
ac_under_voltage_trip_level_1_a AC undervoltage trip threshold, level 1. | 772 | FC03 | int16 | V | R |
ac_under_voltage_trip_time_1_a AC undervoltage trip delay time, level 1. | 773 | FC03 | int16 | s | R |
ac_under_voltage_trip_level_2_a AC undervoltage trip threshold, level 2. | 774 | FC03 | int16 | V | R |
ac_under_voltage_trip_time_2_a AC undervoltage trip delay time, level 2. | 775 | FC03 | int16 | s | R |
ac_under_voltage_trip_level_3_a AC undervoltage trip threshold, level 3. | 776 | FC03 | int16 | V | R |
ac_under_voltage_trip_time_3_a AC undervoltage trip delay time, level 3. | 777 | FC03 | int16 | s | R |
ac_over_frequency_trip_level_1_a AC over-frequency trip threshold, level 1. | 778 | FC03 | int16 | Hz | R |
ac_over_frequency_trip_time_1_a AC over-frequency trip delay time, level 1. | 779 | FC03 | int16 | s | R |
ac_over_frequency_trip_level_2_a AC over-frequency trip threshold, level 2. | 780 | FC03 | int16 | Hz | R |
ac_over_frequency_trip_time_2_a AC over-frequency trip delay time, level 2. | 781 | FC03 | int16 | s | R |
ac_under_frequency_trip_level_1_a AC under-frequency trip threshold, level 1. | 782 | FC03 | int16 | Hz | R |
ac_under_frequency_trip_time_1_a AC under-frequency trip delay time, level 1. | 783 | FC03 | int16 | s | R |
ac_under_frequency_trip_level_2_a AC under-frequency trip threshold, level 2. | 784 | FC03 | int16 | Hz | R |
ac_under_frequency_trip_time_2_a AC under-frequency trip delay time, level 2. | 785 | FC03 | int16 | s | R |
reconnect_time_a Grid reconnection delay time after a trip event. | 786 | FC03 | int16 | s | R |
anti_islanding_a Anti-islanding protection enable flag. | 790 | FC03 | uint16 | | R |
frequency_voltage_ride_through_a Frequency and voltage ride-through enable flag. | 791 | FC03 | uint16 | | R |
reactive_power_control_mode_a Reactive power control mode selection. | 792 | FC03 | uint16 | | R |
power_rising_mode_a Power ramp-up mode selection. | 793 | FC03 | uint16 | | R |
active_power_control_mode_a Active power control mode selection. | 794 | FC03 | uint16 | | R |
grid_voltage_asymmetric_detecton_a Grid voltage asymmetry detection enable flag. | 795 | FC03 | uint16 | | R |
continuous_overvoltage_detection_a Continuous overvoltage detection enable flag. | 796 | FC03 | uint16 | | R |
grid_existence_detection_on_a Grid presence detection enable flag. | 797 | FC03 | uint16 | | R |
neutral_floating_detection_a Neutral floating detection enable flag. | 798 | FC03 | uint16 | | R |
off_grid_blackstart_mode_a Off-grid black-start mode enable flag. | 799 | FC03 | uint16 | | R |
grid_code_selection_a Grid code standard selection. | 800 | FC03 | uint16 | | R |
grid_connected_active_capacity_limitation_function_a Grid-connected active power limitation enable flag. | 801 | FC03 | uint16 | | R |
grid_active_power_capacity_setting_a Active power capacity limit setting for grid connection. | 802 | FC03 | uint16 | W | R |
single_phase_mode_selection_a Single-phase or three-phase mode selection. | 803 | FC03 | uint16 | | R |
over_voltage_drop_active_a Active power reduction on overvoltage enable flag. | 804 | FC03 | uint16 | | R |
start_up_mode_a Inverter startup mode selection. | 805 | FC03 | uint16 | | R |
local_id_setting_a Local unit ID assignment for parallel operation. | 807 | FC03 | int16 | | R |
float_charge_voltage_a Battery float charge voltage setpoint, in volts. | 808 | FC03 | int16 | V | R |
topping_charge_voltage_a Battery topping (bulk) charge voltage setpoint, in volts. | 809 | FC03 | int16 | V | R |
current_from_topping_charging_to_float_charging_a Transition current threshold from topping to float charge. | 810 | FC03 | int16 | A | R |
charge_max_current_a Maximum battery charge current limit, in amperes. | 811 | FC03 | int16 | A | R |
discharge_max_current_a Maximum battery discharge current limit, in amperes. | 812 | FC03 | int16 | A | R |
discharge_min_voltage_a Minimum allowable battery discharge voltage, in volts. | 813 | FC03 | int16 | V | R |
charge_max_voltage_a Maximum allowable battery charge voltage, in volts. | 814 | FC03 | int16 | V | R |
battery_voltage_protection_limit_a Battery voltage protection threshold setting. | 815 | FC03 | uint16 | V | R |
leakage_current_dc_component_detector_a DC leakage current detector enable flag. | 825 | FC03 | uint16 | | R |
resume_and_limit_frequency_a Frequency threshold for power limitation and resumption, in hertz. | 846 | FC03 | int16 | Hz | R |
restore_lower_frequency_of_grid_connection_a Lower frequency threshold for grid reconnection. | 847 | FC03 | int16 | Hz | R |
voltage_reactive_reference_a Reference voltage for volt-var control. | 848 | FC03 | uint16 | V | R |
voltage_and_reactive_power_adjustment_point_v1_a Volt-var curve voltage breakpoint V1. | 849 | FC03 | uint16 | V | R |
voltage_and_reactive_power_adjustment_point_v2_a Volt-var curve voltage breakpoint V2. | 850 | FC03 | int16 | V | R |
voltage_and_reactive_power_adjustment_point_v3_a Volt-var curve voltage breakpoint V3. | 851 | FC03 | int16 | V | R |
voltage_and_reactive_power_adjustment_point_v4_a Volt-var curve voltage breakpoint V4. | 852 | FC03 | int16 | V | R |
max_capacitive_reactive_regulation_q1_a Maximum capacitive reactive power limit Q1. | 853 | FC03 | int16 | var | R |
initial_capacitive_reactive_regulation_q2_a Initial capacitive reactive power value Q2. | 854 | FC03 | int16 | var | R |
initial_inductive_reactive_regulation_q3_a Initial inductive reactive power value Q3. | 855 | FC03 | int16 | var | R |
max_inductive_reactive_regulation_q4_a Maximum inductive reactive power limit Q4. | 856 | FC03 | int16 | var | R |
voltage_and_reactive_response_time_a Response time for volt-var adjustment. | 857 | FC03 | int16 | s | R |
reactive_first_order_response_time_a First-order filter response time for reactive power control. | 858 | FC03 | int16 | s | R |
initial_voltage_v_start_a Volt-watt curve start voltage threshold. | 862 | FC03 | int16 | V | R |
end_voltage_v_stop_a Volt-watt curve stop voltage threshold. | 863 | FC03 | int16 | V | R |
initial_power_p_start_a Volt-watt curve start power level. | 864 | FC03 | int16 | W | R |
end_power_p_stop_a Volt-watt curve stop power level. | 865 | FC03 | int16 | W | R |
return_to_service_delay_a Delay before returning to service after a trip. | 866 | FC03 | int16 | s | R |
volt_watt_response_time_a Response time for volt-watt control. | 867 | FC03 | int16 | s | R |
start_of_frequeny_drop_a Frequency threshold where power droop begins. | 868 | FC03 | int16 | Hz | R |
slope_of_frequency_drop_a Droop slope for frequency-watt control. | 869 | FC03 | int16 | | R |
frequency_watt_f_stop_discharge_a Frequency threshold to stop discharge in freq-watt mode. | 870 | FC03 | int16 | Hz | R |
frequency_watt_f_stop_charge_a Frequency threshold to stop charging in freq-watt mode. | 871 | FC03 | int16 | Hz | R |
volt_watt_v_start_charge_a Voltage threshold to start charging in volt-watt mode. | 872 | FC03 | int16 | V | R |
soft_start_ramp_rate_a Power ramp rate during soft start. | 876 | FC03 | int16 | | R |
power_ramp_rate_a Normal power ramp rate setting. | 877 | FC03 | int16 | | R |
power_factor_setting_a Fixed power factor setpoint. | 878 | FC03 | int16 | | R |
power_factor_p1_a Power factor curve power breakpoint P1. | 879 | FC03 | int16 | W | R |
power_factor_p2_a Power factor curve power breakpoint P2. | 880 | FC03 | int16 | W | R |
power_factor_p3_a Power factor curve power breakpoint P3. | 881 | FC03 | int16 | W | R |
power_factor_p4_a Power factor curve power breakpoint P4. | 882 | FC03 | int16 | W | R |
power_factor_curve_mode_p1_a Power factor curve mode value at breakpoint P1. | 883 | FC03 | int16 | | R |
power_factor_curve_mode_p2_a Power factor curve mode value at breakpoint P2. | 884 | FC03 | int16 | | R |
power_factor_curve_mode_p3_a Power factor curve mode value at breakpoint P3. | 885 | FC03 | int16 | | R |
power_factor_curve_mode_p4_a Power factor curve mode value at breakpoint P4. | 886 | FC03 | int16 | | R |
continuos_over_voltage_trip_threshold_a Continuous overvoltage trip amplitude threshold. | 887 | FC03 | int16 | V | R |
frequency_variation_rate_trip_threshold_a Rate-of-change-of-frequency (ROCOF) trip threshold. | 888 | FC03 | int16 | | R |
phase_angle_abrupt_trip_threshold_a Abrupt phase angle change trip threshold. | 889 | FC03 | int16 | | R |
grid_reconnection_voltage_upper_limit_a Upper voltage limit for grid reconnection. | 890 | FC03 | int16 | V | R |
grid_reconnection_voltage_lower_limit_a Lower voltage limit for grid reconnection. | 891 | FC03 | int16 | V | R |
grid_reconnection_frequency_upper_limit_a Upper frequency limit for grid reconnection. | 892 | FC03 | int16 | Hz | R |
grid_reconnection_frequency_lower_limit_a Lower frequency limit for grid reconnection. | 893 | FC03 | int16 | Hz | R |
low_frequency_ramp_rate_a Power ramp rate under low-frequency conditions. | 894 | FC03 | int16 | | R |
meter_active_power_a Active power reading from the external meter, in watts. | 934 | FC03 | int16 | W | R |
grid_voltage_calibration_l1_a Grid voltage calibration factor for phase L1. | 948 | FC03 | uint16 | | R |
grid_voltage_calibration_l2_a Grid voltage calibration factor for phase L2. | 949 | FC03 | uint16 | | R |
grid_voltage_calibration_l3_a Grid voltage calibration factor for phase L3. | 950 | FC03 | uint16 | | R |
inverter_voltage_calibration_l1_a Inverter output voltage calibration factor, phase L1. | 951 | FC03 | uint16 | | R |
inverter_voltage_calibration_l2_a Inverter output voltage calibration factor, phase L2. | 952 | FC03 | uint16 | | R |
inverter_voltage_calibration_l3_a Inverter output voltage calibration factor, phase L3. | 953 | FC03 | uint16 | | R |
inductor_current_calibration_l1_parameters_1_a Inductor current calibration parameter 1, phase L1. | 954 | FC03 | uint16 | | R |
inductor_current_calibration_l2_parameters_1_a Inductor current calibration parameter 1, phase L2. | 955 | FC03 | uint16 | | R |
inductor_current_calibration_l3_parameters_1_a Inductor current calibration parameter 1, phase L3. | 956 | FC03 | uint16 | | R |
inductor_current_calibration_l1_parameters_2_a Inductor current calibration parameter 2, phase L1. | 957 | FC03 | uint16 | | R |
inductor_current_calibration_l2_parameters_2_a Inductor current calibration parameter 2, phase L2. | 958 | FC03 | uint16 | | R |
inductor_current_calibration_l3_parameters_2_a Inductor current calibration parameter 2, phase L3. | 959 | FC03 | uint16 | | R |
output_current_calibration_l1_a Output current calibration factor for phase L1. | 960 | FC03 | uint16 | | R |
output_current_calibration_l2_a Output current calibration factor for phase L2. | 961 | FC03 | uint16 | | R |
output_current_calibration_l3_a Output current calibration factor for phase L3. | 962 | FC03 | uint16 | | R |
positive_bus_voltage_calibration_a Positive DC bus voltage calibration factor. | 963 | FC03 | uint16 | | R |
negative_bus_voltage_calibration_a Negative DC bus voltage calibration factor. | 964 | FC03 | uint16 | | R |
dc_voltage_calibration_a DC voltage measurement calibration factor. | 965 | FC03 | uint16 | | R |
dc_current_calibration_a DC current measurement calibration factor. | 966 | FC03 | uint16 | | R |
dc_inductor_current_calibration_a DC inductor current calibration factor. | 967 | FC03 | uint16 | | R |
set_active_power_b Active power setpoint write; positive charges battery, negative discharges. | 135 | FC16 | int16 | W | W |
set_reactive_power_b Reactive power setpoint write, in volt-amperes reactive. | 136 | FC16 | int16 | W | W |
set_off_grid_voltage_b Off-grid output voltage setpoint write, in volts. | 137 | FC16 | int16 | V | W |
set_off_grid_frequency_b Off-grid output frequency setpoint write, in hertz. | 138 | FC16 | int16 | Hz | W |
ip_address_block_1_b Write first octet of the device IP address. | 300 | FC16 | uint16 | | W |
ip_address_block_2_b Write second octet of the device IP address. | 301 | FC16 | uint16 | | W |
ip_address_block_3_b Write third octet of the device IP address. | 302 | FC16 | uint16 | | W |
ip_address_block_4_b Write fourth octet of the device IP address. | 303 | FC16 | uint16 | | W |
netmask_block_1_b Write first octet of the subnet mask. | 304 | FC16 | uint16 | | W |
netmask_block_2_b Write second octet of the subnet mask. | 305 | FC16 | uint16 | | W |
netmask_block_3_b Write third octet of the subnet mask. | 306 | FC16 | uint16 | | W |
netmask_block_4_b Write fourth octet of the subnet mask. | 307 | FC16 | uint16 | | W |
gateway_ip_block_1_b Write first octet of the gateway IP address. | 308 | FC16 | uint16 | | W |
gateway_ip_block_2_b Write second octet of the gateway IP address. | 309 | FC16 | uint16 | | W |
gateway_ip_block_3_b Write third octet of the gateway IP address. | 310 | FC16 | uint16 | | W |
gateway_ip_block_4_b Write fourth octet of the gateway IP address. | 311 | FC16 | uint16 | | W |
mac_b Write device MAC address. | 312 | FC16 | uint16 | | W |
modbus_unit_id_b Write Modbus unit ID for this device. | 316 | FC16 | uint16 | | W |
baudrate_b Write RS-485 baud rate setting. | 320 | FC16 | uint16 | | W |
interface_type_b Write active communication interface type. | 325 | FC16 | uint16 | | W |
communication_protocol_selection_b Write communication protocol selection. | 326 | FC16 | uint16 | | W |
ems_timeout_b Write EMS communication timeout value. | 327 | FC16 | uint16 | s | W |
epo_enable_b Write emergency power-off (EPO) enable flag. | 328 | FC16 | uint16 | | W |
bms_timeout_b Write BMS communication timeout value. | 329 | FC16 | uint16 | s | W |
bms_protocol_selection_b Write BMS communication protocol selection. | 330 | FC16 | uint16 | | W |
set_grid_mode_b Write grid mode configuration. | 331 | FC16 | uint16 | | W |
buzzer_enable_b Write audible buzzer alarm enable flag. | 332 | FC16 | uint16 | | W |
restore_factory_setting_b Write command to restore factory defaults. | 333 | FC16 | uint16 | | W |
start_inverter_b Write command to start the inverter. | 650 | FC16 | uint16 | | W |
stop_inverter_b Write command to stop the inverter. | 651 | FC16 | uint16 | | W |
clear_failure_b Write command to clear active fault flags. | 652 | FC16 | uint16 | | W |
set_on_grid_mode_b Write command to switch to on-grid mode. | 653 | FC16 | uint16 | | W |
set_off_grid_mode_b Write command to switch to off-grid mode. | 654 | FC16 | uint16 | | W |
set_standby_command_b Write command to place inverter in standby. | 655 | FC16 | uint16 | | W |
set_soft_start_b Write command to initiate AC soft start. | 656 | FC16 | uint16 | | W |
reset_instruction_b Write command to reset the inverter. | 657 | FC16 | uint16 | | W |
grid_stop_b Write command to disconnect from the grid. | 658 | FC16 | uint16 | | W |
switching_device_access_setting_b Write switching device access permission. | 752 | FC16 | uint16 | | W |
cpu_type_b Write CPU type identifier. | 755 | FC16 | uint16 | | W |
off_grid_and_parallel_enable_b Write off-grid and parallel operation enable flag. | 756 | FC16 | uint16 | | W |
set_dc_soft_start_external_control_b Write DC soft-start external control enable. | 757 | FC16 | uint16 | | W |
grid_over_voltage_protection_amplitude_b Write grid overvoltage protection trip threshold. | 768 | FC16 | int16 | V | W |
ac_over_voltage_trip_time_1_b Write AC overvoltage trip delay, level 1. | 769 | FC16 | int16 | s | W |
ac_over_voltage_trip_level_2_b Write AC overvoltage trip threshold, level 2. | 770 | FC16 | int16 | V | W |
ac_over_voltage_trip_time_2_b Write AC overvoltage trip delay, level 2. | 771 | FC16 | int16 | s | W |
ac_under_voltage_trip_level_1_b Write AC undervoltage trip threshold, level 1. | 772 | FC16 | int16 | V | W |
ac_under_voltage_trip_time_1_b Write AC undervoltage trip delay, level 1. | 773 | FC16 | int16 | s | W |
ac_under_voltage_trip_level_2_b Write AC undervoltage trip threshold, level 2. | 774 | FC16 | int16 | V | W |
ac_under_voltage_trip_time_2_b Write AC undervoltage trip delay, level 2. | 775 | FC16 | int16 | s | W |
ac_under_voltage_trip_level_3_b Write AC undervoltage trip threshold, level 3. | 776 | FC16 | int16 | V | W |
ac_under_voltage_trip_time_3_b Write AC undervoltage trip delay, level 3. | 777 | FC16 | int16 | s | W |
ac_over_frequency_trip_level_1_b Write AC over-frequency trip threshold, level 1. | 778 | FC16 | int16 | Hz | W |
ac_over_frequency_trip_time_1_b Write AC over-frequency trip delay, level 1. | 779 | FC16 | int16 | s | W |
ac_over_frequency_trip_level_2_b Write AC over-frequency trip threshold, level 2. | 780 | FC16 | int16 | Hz | W |
ac_over_frequency_trip_time_2_b Write AC over-frequency trip delay, level 2. | 781 | FC16 | int16 | s | W |
ac_under_frequency_trip_level_1_b Write AC under-frequency trip threshold, level 1. | 782 | FC16 | int16 | Hz | W |
ac_under_frequency_trip_time_1_b Write AC under-frequency trip delay, level 1. | 783 | FC16 | int16 | s | W |
ac_under_frequency_trip_level_2_b Write AC under-frequency trip threshold, level 2. | 784 | FC16 | int16 | Hz | W |
ac_under_frequency_trip_time_2_b Write AC under-frequency trip delay, level 2. | 785 | FC16 | int16 | s | W |
reconnect_time_b Write grid reconnection delay time. | 786 | FC16 | int16 | s | W |
anti_islanding_b Write anti-islanding protection enable flag. | 790 | FC16 | uint16 | | W |
frequency_voltage_ride_through_b Write frequency and voltage ride-through enable flag. | 791 | FC16 | uint16 | | W |
reactive_power_control_mode_b Write reactive power control mode selection. | 792 | FC16 | uint16 | | W |
power_rising_mode_b Write power ramp-up mode selection. | 793 | FC16 | uint16 | | W |
active_power_control_mode_b Write active power control mode selection. | 794 | FC16 | uint16 | | W |
grid_voltage_asymmetric_detecton_b Write grid voltage asymmetry detection enable flag. | 795 | FC16 | uint16 | | W |
continuous_overvoltage_detection_b Write continuous overvoltage detection enable flag. | 796 | FC16 | uint16 | | W |
grid_existence_detection_on_b Write grid presence detection enable flag. | 797 | FC16 | uint16 | | W |
neutral_floating_detection_b Write neutral floating detection enable flag. | 798 | FC16 | uint16 | | W |
off_grid_blackstart_mode_b Write off-grid black-start mode enable flag. | 799 | FC16 | uint16 | | W |
grid_code_selection_b Write grid code standard selection. | 800 | FC16 | uint16 | | W |
grid_connected_active_capacity_limitation_function_b Write grid-connected active power limitation enable flag. | 801 | FC16 | uint16 | | W |
grid_active_power_capacity_setting_b Write active power capacity limit for grid connection. | 802 | FC16 | uint16 | W | W |
single_phase_mode_selection_b Write single-phase or three-phase mode selection. | 803 | FC16 | uint16 | | W |
over_voltage_drop_active_b Write active power reduction on overvoltage enable flag. | 804 | FC16 | uint16 | | W |
start_up_mode_b Write inverter startup mode selection. | 805 | FC16 | uint16 | | W |
local_id_setting_b Write local unit ID for parallel operation. | 807 | FC16 | int16 | | W |
float_charge_voltage_b Write battery float charge voltage setpoint, in volts. | 808 | FC16 | int16 | V | W |
topping_charge_voltage_b Write battery topping charge voltage setpoint, in volts. | 809 | FC16 | int16 | V | W |
current_from_topping_charging_to_float_charging_b Write transition current threshold, topping to float charge. | 810 | FC16 | int16 | A | W |
charge_max_current_b Write maximum battery charge current limit, in amperes. | 811 | FC16 | int16 | A | W |
discharge_max_current_b Write maximum battery discharge current limit, in amperes. | 812 | FC16 | int16 | A | W |
discharge_min_voltage_b Write minimum allowable battery discharge voltage, in volts. | 813 | FC16 | int16 | V | W |
charge_max_voltage_b Write maximum allowable battery charge voltage, in volts. | 814 | FC16 | int16 | V | W |
battery_voltage_protection_limit_b Write battery voltage protection threshold. | 815 | FC16 | uint16 | V | W |
leakage_current_dc_component_detector_b Write DC leakage current detector enable flag. | 825 | FC16 | uint16 | | W |
resume_and_limit_frequency_b Write frequency threshold for power limitation and resumption, in hertz. | 846 | FC16 | int16 | Hz | W |
restore_lower_frequency_of_grid_connection_b Write lower frequency threshold for grid reconnection. | 847 | FC16 | int16 | Hz | W |
voltage_reactive_reference_b Write reference voltage for volt-var control. | 848 | FC16 | int16 | V | W |
voltage_and_reactive_power_adjustment_point_v1_b Write volt-var curve voltage breakpoint V1. | 849 | FC16 | int16 | V | W |
voltage_and_reactive_power_adjustment_point_v2_b Write volt-var curve voltage breakpoint V2. | 850 | FC16 | int16 | V | W |
voltage_and_reactive_power_adjustment_point_v3_b Write volt-var curve voltage breakpoint V3. | 851 | FC16 | int16 | V | W |
voltage_and_reactive_power_adjustment_point_v4_b Write volt-var curve voltage breakpoint V4. | 852 | FC16 | int16 | V | W |
max_capacitive_reactive_regulation_q1_b Write maximum capacitive reactive power limit Q1. | 853 | FC16 | int16 | var | W |
initial_capacitive_reactive_regulation_q2_b Write initial capacitive reactive power value Q2. | 854 | FC16 | int16 | var | W |
initial_inductive_reactive_regulation_q3_b Write initial inductive reactive power value Q3. | 855 | FC16 | int16 | var | W |
max_inductive_reactive_regulation_q4_b Write maximum inductive reactive power limit Q4. | 856 | FC16 | int16 | var | W |
voltage_and_reactive_response_time_b Write response time for volt-var adjustment. | 857 | FC16 | int16 | s | W |
reactive_first_order_response_time_b Write first-order filter response time for reactive power. | 858 | FC16 | int16 | s | W |
initial_voltage_v_start_b Write volt-watt curve start voltage threshold. | 862 | FC16 | int16 | V | W |
end_voltage_v_stop_b Write volt-watt curve stop voltage threshold. | 863 | FC16 | int16 | V | W |
initial_power_p_start_b Write volt-watt curve start power level. | 864 | FC16 | int16 | W | W |
end_power_p_stop_b Write volt-watt curve stop power level. | 865 | FC16 | int16 | W | W |
return_to_service_delay_b Write return-to-service delay after a trip. | 866 | FC16 | int16 | s | W |
volt_watt_response_time_b Write response time for volt-watt control. | 867 | FC16 | int16 | s | W |
start_of_frequeny_drop_b Write frequency droop start threshold. | 868 | FC16 | int16 | Hz | W |
slope_of_frequency_drop_b Write droop slope for frequency-watt control. | 869 | FC16 | int16 | | W |
frequency_watt_f_stop_discharge_b Write frequency threshold to stop discharge. | 870 | FC16 | int16 | Hz | W |
frequency_watt_f_stop_charge_b Write frequency threshold to stop charging. | 871 | FC16 | int16 | Hz | W |
volt_watt_v_start_charge_b Write voltage threshold to start charging in volt-watt mode. | 872 | FC16 | int16 | V | W |
soft_start_ramp_rate_b Write power ramp rate for soft start. | 876 | FC16 | int16 | | W |
power_ramp_rate_b Write normal power ramp rate. | 877 | FC16 | int16 | | W |
power_factor_setting_b Write fixed power factor setpoint. | 878 | FC16 | int16 | | W |
power_factor_p1_b Write power factor curve power breakpoint P1. | 879 | FC16 | int16 | W | W |
power_factor_p2_b Write power factor curve power breakpoint P2. | 880 | FC16 | int16 | W | W |
power_factor_p3_b Write power factor curve power breakpoint P3. | 881 | FC16 | int16 | W | W |
power_factor_p4_b Write power factor curve power breakpoint P4. | 882 | FC16 | int16 | W | W |
power_factor_curve_mode_p1_b Write power factor curve mode value at P1. | 883 | FC16 | int16 | | W |
power_factor_curve_mode_p2_b Write power factor curve mode value at P2. | 884 | FC16 | int16 | | W |
power_factor_curve_mode_p3_b Write power factor curve mode value at P3. | 885 | FC16 | int16 | | W |
power_factor_curve_mode_p4_b Write power factor curve mode value at P4. | 886 | FC16 | int16 | | W |
continuos_over_voltage_trip_threshold_b Write continuous overvoltage trip threshold. | 887 | FC16 | int16 | V | W |
frequency_variation_rate_trip_threshold_b Write rate-of-change-of-frequency (ROCOF) trip threshold. | 888 | FC16 | int16 | | W |
phase_angle_abrupt_trip_threshold_b Write abrupt phase angle change trip threshold. | 889 | FC16 | int16 | | W |
grid_reconnection_voltage_upper_limit_b Write upper voltage limit for grid reconnection. | 890 | FC16 | int16 | V | W |
grid_reconnection_voltage_lower_limit_b Write lower voltage limit for grid reconnection. | 891 | FC16 | int16 | V | W |
grid_reconnection_frequency_upper_limit_b Write upper frequency limit for grid reconnection. | 892 | FC16 | int16 | Hz | W |
grid_reconnection_frequency_lower_limit_b Write lower frequency limit for grid reconnection. | 893 | FC16 | int16 | Hz | W |
low_frequency_ramp_rate_b Write power ramp rate under low-frequency conditions. | 894 | FC16 | int16 | | W |
meter_active_power_b Write active power value from external meter, in watts. | 934 | FC16 | int16 | W | W |
grid_voltage_calibration_l1_b Write grid voltage calibration factor, phase L1. | 948 | FC16 | uint16 | | W |
grid_voltage_calibration_l2_b Write grid voltage calibration factor, phase L2. | 949 | FC16 | uint16 | | W |
grid_voltage_calibration_l3_b Write grid voltage calibration factor, phase L3. | 950 | FC16 | uint16 | | W |
inverter_voltage_calibration_l1_b Write inverter voltage calibration factor, phase L1. | 951 | FC16 | uint16 | | W |
inverter_voltage_calibration_l2_b Write inverter voltage calibration factor, phase L2. | 952 | FC16 | uint16 | | W |
inverter_voltage_calibration_l3_b Write inverter voltage calibration factor, phase L3. | 953 | FC16 | uint16 | | W |
inductor_current_calibration_l1_parameters_1_b Write inductor current calibration parameter 1, phase L1. | 954 | FC16 | uint16 | | W |
inductor_current_calibration_l2_parameters_1_b Write inductor current calibration parameter 1, phase L2. | 955 | FC16 | uint16 | | W |
inductor_current_calibration_l3_parameters_1_b Write inductor current calibration parameter 1, phase L3. | 956 | FC16 | uint16 | | W |
inductor_current_calibration_l1_parameters_2_b Write inductor current calibration parameter 2, phase L1. | 957 | FC16 | uint16 | | W |
inductor_current_calibration_l2_parameters_2_b Write inductor current calibration parameter 2, phase L2. | 958 | FC16 | uint16 | | W |
inductor_current_calibration_l3_parameters_2_b Write inductor current calibration parameter 2, phase L3. | 959 | FC16 | uint16 | | W |
output_current_calibration_l1_b Write output current calibration factor, phase L1. | 960 | FC16 | uint16 | | W |
output_current_calibration_l2_b Write output current calibration factor, phase L2. | 961 | FC16 | uint16 | | W |
output_current_calibration_l3_b Write output current calibration factor, phase L3. | 962 | FC16 | uint16 | | W |
positive_bus_voltage_calibration_b Write positive DC bus voltage calibration factor. | 963 | FC16 | uint16 | | W |
negative_bus_voltage_calibration_b Write negative DC bus voltage calibration factor. | 964 | FC16 | uint16 | | W |
dc_voltage_calibration_b Write DC voltage measurement calibration factor. | 965 | FC16 | uint16 | | W |
dc_current_calibration_b Write DC current measurement calibration factor. | 966 | FC16 | uint16 | | W |
dc_inductor_current_calibration_b Write DC inductor current calibration factor. | 967 | FC16 | uint16 | | W |
time_setting Write system time or time-zone configuration. | 4001 | FC16 | int16 | | W |
password Write access password for protected configuration changes. | 4007 | FC16 | int16 | | W |