Solis PV Grid-Tied Inverter
Grid-tied PV inverter that reports yield, string data and faults and accepts power limits.
The Solis PV grid-tied inverter converts the DC power of a solar array into AC power and feeds it into the grid, in single-phase and three-phase models from 0.7 kW to 320 kW. This Modbus RTU template reads power, energy yield, string and MPPT values, grid values and fault codes, and lets you set the active power limit, reactive power and power factor from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 152, read and write
- Brand
- Solis
- Key readings
- Active power · Energy today · Total energy · MPPT voltage and current · Grid voltage and frequency · Inverter temperature · Inverter status
- Available commands
- Active power limit · Reactive power · Power factor · Inverter on or off
- Compatible models
- Solis single-phase grid-tied inverters 0.7-10K · Solis three-phase grid-tied inverters 5-30K · Solis three-phase string inverters 25-136K · Solis three-phase string inverters 125-200K · Solis three-phase string inverters 250K and 320K · Solis MAX and PRO series
- Last updated
Registers (152)
152 read, 17 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Active Power | W | Read | 3004 | FC04 | int32 |
| Total DC Output Power | W | Read | 3006 | FC04 | uint32 |
| Total Energy | kWh | Read | 3008 | FC04 | uint32 |
| Energy This Month | kWh | Read | 3010 | FC04 | uint32 |
| Energy Last Month | kWh | Read | 3012 | FC04 | uint32 |
| Energy Today | kWh | Read | |||
| Energy Yesterday | kWh | Read | |||
| DC Voltage 1 | V | Read | |||
| DC Current 1 | A | Read | |||
| DC Voltage 2 | V | Read | |||
| DC Current 2 | A | Read | |||
| DC Voltage 3 | V | Read | |||
| DC Current 3 | A | Read | |||
| DC Voltage 4 | V | Read | |||
| DC Current 4 | A | Read | |||
| AB Line Voltage / Phase A Voltage | V | Read | |||
| BC Line Voltage / Phase B Voltage | V | Read | |||
| CA Line Voltage / Phase C Voltage | V | Read | |||
| Phase A Current | A | Read | |||
| Phase B Current | A | Read | |||
| Phase C Current | A | Read | |||
| Inverter Temperature | °C | Read | |||
| Grid Frequency | Hz | Read | |||
| Reactive Power | var | Read | |||
| Apparent Power | VA | Read | |||
| Real-Time Power Factor | Read | ||||
| Total PV Voltage | V | Read | |||
| Total PV Current | A | Read | |||
| PV1 Current | A | Read | |||
| PV2 Current | A | Read | |||
| PV3 Current | A | Read | |||
| PV4 Current | A | Read | |||
| PV5 Current | A | Read | |||
| PV6 Current | A | Read | |||
| PV7 Current | A | Read | |||
| PV8 Current | A | Read | |||
| PV9 Current | A | Read | |||
| PV10 Current | A | Read | |||
| PV11 Current | A | Read | |||
| PV12 Current | A | Read | |||
| PV13 Current | A | Read | |||
| PV14 Current | A | Read | |||
| PV15 Current | A | Read | |||
| PV16 Current | A | Read | |||
| PV17 Current | A | Read | |||
| PV18 Current | A | Read | |||
| PV19 Current | A | Read | |||
| PV20 Current | A | Read | |||
| PV21 Current | A | Read | |||
| PV22 Current | A | Read | |||
| PV23 Current | A | Read | |||
| PV24 Current | A | Read | |||
| PV25 Current | A | Read | |||
| PV26 Current | A | Read | |||
| PV27 Current | A | Read | |||
| PV28 Current | A | Read | |||
| PV29 Current | A | Read | |||
| PV30 Current | A | Read | |||
| PV31 Current | A | Read | |||
| PV32 Current | A | Read | |||
| MPPT 1 Voltage | V | Read | |||
| MPPT 2 Voltage | V | Read | |||
| MPPT 3 Voltage | V | Read | |||
| MPPT 4 Voltage | V | Read | |||
| MPPT 5 Voltage | V | Read | |||
| MPPT 6 Voltage | V | Read | |||
| MPPT 7 Voltage | V | Read | |||
| MPPT 8 Voltage | V | Read | |||
| MPPT 9 Voltage | V | Read | |||
| MPPT 10 Voltage | V | Read | |||
| MPPT 11 Voltage | V | Read | |||
| MPPT 12 Voltage | V | Read | |||
| MPPT 13 Voltage | V | Read | |||
| MPPT 14 Voltage | V | Read | |||
| MPPT 15 Voltage | V | Read | |||
| MPPT 1 Current | A | Read | |||
| MPPT 2 Current | A | Read | |||
| MPPT 3 Current | A | Read | |||
| MPPT 4 Current | A | Read | |||
| MPPT 5 Current | A | Read | |||
| MPPT 6 Current | A | Read | |||
| MPPT 7 Current | A | Read | |||
| MPPT 8 Current | A | Read | |||
| MPPT 9 Current | A | Read | |||
| MPPT 10 Current | A | Read | |||
| MPPT 11 Current | A | Read | |||
| MPPT 12 Current | A | Read | |||
| MPPT 13 Current | A | Read | |||
| MPPT 14 Current | A | Read | |||
| MPPT 15 Current | A | Read | |||
| MPPT 16 Voltage | V | Read | |||
| MPPT 16 Current | A | Read | |||
| Inverter Status | Read | ||||
| Alarm Code Data | Read | ||||
| Working Status | Read | ||||
| Limiting Status | Read | ||||
| Fault Code 01 | Read | ||||
| Fault Code 02 | Read | ||||
| Fault Code 03 | Read | ||||
| Fault Code 04 | Read | ||||
| Fault Code 05 | Read | ||||
| Fault Code 06 | Read | ||||
| Fault Code 07 | Read | ||||
| Fault Code 08 | Read | ||||
| Warning Message DSP | Read | ||||
| Warning Message HMI | Read | ||||
| Fault Code 10 | Read | ||||
| Fault Code 11 | Read | ||||
| Fault Code 12 | Read | ||||
| Standard Working Mode | Read | ||||
| Limited Active Power Output | W | Read | |||
| Reactive Power Regulation Output | var | Read | |||
| Active Power Percentage | % | Read | |||
| Power Factor Adjustment Value | Read | ||||
| Reactive Power Percentage | % | Read | |||
| Grid Standard | Read | ||||
| Power Limit Switch Status | Read | ||||
| Reactive Power Switch Status | Read | ||||
| Rated Output Power | W | Read | |||
| Inverter Type | Read | ||||
| Product Model | Read | ||||
| DSP Version | Read | ||||
| HMI Version | Read | ||||
| HMI Version Minor | Read | ||||
| DC Input Type | Read | ||||
| Serial Number Part 1 | Read | ||||
| Serial Number Part 2 | Read | ||||
| Serial Number Part 3 | Read | ||||
| Serial Number Part 4 | Read | ||||
| System Time Year | Read | ||||
| System Time Month | Read | ||||
| System Time Day | Read | ||||
| System Time Hour | Read | ||||
| System Time Minute | Read | ||||
| System Time Second | Read | ||||
| Clock Setting Year | Read and write | ||||
| Clock Setting Month | Read and write | ||||
| Clock Setting Day | Read and write | ||||
| Clock Setting Hour | Read and write | ||||
| Clock Setting Minute | Read and write | ||||
| Clock Setting Second | Read and write | ||||
| Inverter On/Off | Read and write | ||||
| Reactive Power Limit | % | Read and write | |||
| Active Power Limit | % | Read and write | |||
| Power Factor Setpoint | Read and write | ||||
| Power-Off Saving | Read and write | ||||
| Active Power Switch | Read and write | ||||
| Reactive Power Switch | Read and write | ||||
| Active Power Setpoint 1 | W | Read and write | |||
| Reactive Power Setpoint 1 | var | Read and write | |||
| Active Power Setpoint 2 | W | Read and write | |||
| Reactive Power Setpoint 2 | var | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show AC power, daily yield and lifetime energy of each Solis inverter on one dashboard.
- Get an alert when Inverter Status reports a fault code instead of generating.
- Compare MPPT currents over time to spot a shaded or failing string.
- Lower the active power limit remotely when the grid operator asks for an export cap.
- Track inverter temperature in summer to check ventilation of the installation room.
Installation
Connect RS485 A and B of the inverter COM port to the RS485 port of the ModbusCloud Gateway. Terminate the bus with 120 ohm at both ends.
Set a unique Modbus address (1 to 99) on the inverter display. The serial settings are fixed at 9600 baud, 8N1.
In ModbusCloud, add a Modbus device (RTU) with that address and 9600 baud, no parity, 1 stop bit, and import this template.
Check that Active Power and Grid Frequency show plausible values during daylight.
To use power limits, first enable Active Power Switch or Reactive Power Switch, then write the setpoint.
Things to watch for
The inverter does not answer. What should I check?
Check that the address on the display matches the device in ModbusCloud and that the link is 9600 baud, 8 data bits, no parity, 1 stop bit. Swap A and B if nothing answers. Many inverters only power their RS485 port while PV voltage is present, so test during daylight.
Why does Active Power Limit not change the output?
The limit is only used after Active Power Switch is set to 0xAA (170). For reactive power and power factor, Reactive Power Switch must be 0xA1 or 0xA2 first. The switch registers are stored in flash, so set them once and then write only the setpoint.
What should I watch out for when I write registers?
A power limit, power factor or the off command changes what the inverter feeds into the grid, so agree setpoints with the installer or grid operator first. By default a setpoint is lost after a power cut; Power-Off Saving keeps it. Write one register per request.
The string currents are all zero on my inverter.
Not every model measures every string. Smaller models report DC Voltage 1 to 4 and DC Current 1 to 4; larger string inverters fill the PV and MPPT registers. Registers a model does not have read as 0.
Can I connect several inverters on one bus?
Yes. Give each inverter its own address from 1 to 99 and add each one as a separate Modbus device in ModbusCloud with this template. Keep the bus as one line without branches and terminate both ends.