Solis PV Grid-Tied Inverter

Grid-tied PV inverter that reports yield, string data and faults and accepts power limits.

The Solis PV grid-tied inverter converts the DC power of a solar array into AC power and feeds it into the grid, in single-phase and three-phase models from 0.7 kW to 320 kW. This Modbus RTU template reads power, energy yield, string and MPPT values, grid values and fault codes, and lets you set the active power limit, reactive power and power factor from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
152, read and write
Brand
Solis
Key readings
Active power · Energy today · Total energy · MPPT voltage and current · Grid voltage and frequency · Inverter temperature · Inverter status
Available commands
Active power limit · Reactive power · Power factor · Inverter on or off
Compatible models
Solis single-phase grid-tied inverters 0.7-10K · Solis three-phase grid-tied inverters 5-30K · Solis three-phase string inverters 25-136K · Solis three-phase string inverters 125-200K · Solis three-phase string inverters 250K and 320K · Solis MAX and PRO series
Last updated

Registers (152)

152 read, 17 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Active PowerWRead3004FC04int32
Total DC Output PowerWRead3006FC04uint32
Total EnergykWhRead3008FC04uint32
Energy This MonthkWhRead3010FC04uint32
Energy Last MonthkWhRead3012FC04uint32
Energy TodaykWhRead
Energy YesterdaykWhRead
DC Voltage 1VRead
DC Current 1ARead
DC Voltage 2VRead
DC Current 2ARead
DC Voltage 3VRead
DC Current 3ARead
DC Voltage 4VRead
DC Current 4ARead
AB Line Voltage / Phase A VoltageVRead
BC Line Voltage / Phase B VoltageVRead
CA Line Voltage / Phase C VoltageVRead
Phase A CurrentARead
Phase B CurrentARead
Phase C CurrentARead
Inverter Temperature°CRead
Grid FrequencyHzRead
Reactive PowervarRead
Apparent PowerVARead
Real-Time Power FactorRead
Total PV VoltageVRead
Total PV CurrentARead
PV1 CurrentARead
PV2 CurrentARead
PV3 CurrentARead
PV4 CurrentARead
PV5 CurrentARead
PV6 CurrentARead
PV7 CurrentARead
PV8 CurrentARead
PV9 CurrentARead
PV10 CurrentARead
PV11 CurrentARead
PV12 CurrentARead
PV13 CurrentARead
PV14 CurrentARead
PV15 CurrentARead
PV16 CurrentARead
PV17 CurrentARead
PV18 CurrentARead
PV19 CurrentARead
PV20 CurrentARead
PV21 CurrentARead
PV22 CurrentARead
PV23 CurrentARead
PV24 CurrentARead
PV25 CurrentARead
PV26 CurrentARead
PV27 CurrentARead
PV28 CurrentARead
PV29 CurrentARead
PV30 CurrentARead
PV31 CurrentARead
PV32 CurrentARead
MPPT 1 VoltageVRead
MPPT 2 VoltageVRead
MPPT 3 VoltageVRead
MPPT 4 VoltageVRead
MPPT 5 VoltageVRead
MPPT 6 VoltageVRead
MPPT 7 VoltageVRead
MPPT 8 VoltageVRead
MPPT 9 VoltageVRead
MPPT 10 VoltageVRead
MPPT 11 VoltageVRead
MPPT 12 VoltageVRead
MPPT 13 VoltageVRead
MPPT 14 VoltageVRead
MPPT 15 VoltageVRead
MPPT 1 CurrentARead
MPPT 2 CurrentARead
MPPT 3 CurrentARead
MPPT 4 CurrentARead
MPPT 5 CurrentARead
MPPT 6 CurrentARead
MPPT 7 CurrentARead
MPPT 8 CurrentARead
MPPT 9 CurrentARead
MPPT 10 CurrentARead
MPPT 11 CurrentARead
MPPT 12 CurrentARead
MPPT 13 CurrentARead
MPPT 14 CurrentARead
MPPT 15 CurrentARead
MPPT 16 VoltageVRead
MPPT 16 CurrentARead
Inverter StatusRead
Alarm Code DataRead
Working StatusRead
Limiting StatusRead
Fault Code 01Read
Fault Code 02Read
Fault Code 03Read
Fault Code 04Read
Fault Code 05Read
Fault Code 06Read
Fault Code 07Read
Fault Code 08Read
Warning Message DSPRead
Warning Message HMIRead
Fault Code 10Read
Fault Code 11Read
Fault Code 12Read
Standard Working ModeRead
Limited Active Power OutputWRead
Reactive Power Regulation OutputvarRead
Active Power Percentage%Read
Power Factor Adjustment ValueRead
Reactive Power Percentage%Read
Grid StandardRead
Power Limit Switch StatusRead
Reactive Power Switch StatusRead
Rated Output PowerWRead
Inverter TypeRead
Product ModelRead
DSP VersionRead
HMI VersionRead
HMI Version MinorRead
DC Input TypeRead
Serial Number Part 1Read
Serial Number Part 2Read
Serial Number Part 3Read
Serial Number Part 4Read
System Time YearRead
System Time MonthRead
System Time DayRead
System Time HourRead
System Time MinuteRead
System Time SecondRead
Clock Setting YearRead and write
Clock Setting MonthRead and write
Clock Setting DayRead and write
Clock Setting HourRead and write
Clock Setting MinuteRead and write
Clock Setting SecondRead and write
Inverter On/OffRead and write
Reactive Power Limit%Read and write
Active Power Limit%Read and write
Power Factor SetpointRead and write
Power-Off SavingRead and write
Active Power SwitchRead and write
Reactive Power SwitchRead and write
Active Power Setpoint 1WRead and write
Reactive Power Setpoint 1varRead and write
Active Power Setpoint 2WRead and write
Reactive Power Setpoint 2varRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show AC power, daily yield and lifetime energy of each Solis inverter on one dashboard.
  • Get an alert when Inverter Status reports a fault code instead of generating.
  • Compare MPPT currents over time to spot a shaded or failing string.
  • Lower the active power limit remotely when the grid operator asks for an export cap.
  • Track inverter temperature in summer to check ventilation of the installation room.

Installation

  1. Connect RS485 A and B of the inverter COM port to the RS485 port of the ModbusCloud Gateway. Terminate the bus with 120 ohm at both ends.

  2. Set a unique Modbus address (1 to 99) on the inverter display. The serial settings are fixed at 9600 baud, 8N1.

  3. In ModbusCloud, add a Modbus device (RTU) with that address and 9600 baud, no parity, 1 stop bit, and import this template.

  4. Check that Active Power and Grid Frequency show plausible values during daylight.

  5. To use power limits, first enable Active Power Switch or Reactive Power Switch, then write the setpoint.

Things to watch for

The inverter does not answer. What should I check?

Check that the address on the display matches the device in ModbusCloud and that the link is 9600 baud, 8 data bits, no parity, 1 stop bit. Swap A and B if nothing answers. Many inverters only power their RS485 port while PV voltage is present, so test during daylight.

Why does Active Power Limit not change the output?

The limit is only used after Active Power Switch is set to 0xAA (170). For reactive power and power factor, Reactive Power Switch must be 0xA1 or 0xA2 first. The switch registers are stored in flash, so set them once and then write only the setpoint.

What should I watch out for when I write registers?

A power limit, power factor or the off command changes what the inverter feeds into the grid, so agree setpoints with the installer or grid operator first. By default a setpoint is lost after a power cut; Power-Off Saving keeps it. Write one register per request.

The string currents are all zero on my inverter.

Not every model measures every string. Smaller models report DC Voltage 1 to 4 and DC Current 1 to 4; larger string inverters fill the PV and MPPT registers. Registers a model does not have read as 0.

Can I connect several inverters on one bus?

Yes. Give each inverter its own address from 1 to 99 and add each one as a separate Modbus device in ModbusCloud with this template. Keep the bus as one line without branches and terminate both ends.

Want to see how it works?