Solis S6-EH3P
Three-phase hybrid inverter that manages PV, a high-voltage battery, grid exchange and backup loads.
The Solis S6-EH3P is a three-phase hybrid inverter that converts PV power, charges and discharges a high-voltage battery and supplies backup loads in homes and businesses. This Modbus RTU template reads PV, battery, grid, load and energy values and lets you write battery limits, time-of-use slots and remote power settings from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 766, read and write
- Brand
- Solis
- Key readings
- PV power · Battery state of charge · Battery power · Grid power · Backup load power · Energy counters · Inverter status and faults
- Available commands
- Battery charge and discharge power · Time-of-use charge slots · SOC limits · Export limit · Remote dispatch mode
- Compatible models
- S6-EH3P(3-12)K-H · S6-EH3P(12-20)K-H · S6-EH3P(29.9-60)K-H · S6-EH3P(75-125)K10-NV-YD-H · RHI-3P(3-10)K-HVES-5G
- Last updated
Registers (766)
766 read, 424 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Total PV Input Power | W | Read | |||
| PV DC Voltage 1 | V | Read | |||
| PV DC Current 1 | A | Read | |||
| PV DC Voltage 2 | V | Read | |||
| PV DC Current 2 | A | Read | |||
| Battery 1 State of Charge (SOC) | % | Read | |||
| Battery 1 State of Health (SOH) | % | Read | |||
| Battery 1 Real-time Voltage | V | Read | |||
| Battery 1 Real-time Current | A | Read | |||
| Battery 1 Real-time Charge/Discharge Direction | Read | ||||
| Battery 1 Real-time Power | W | Read | |||
| Active Power Value | W | Read | |||
| Grid Frequency | Hz | Read | |||
| AB Line Voltage / A Phase Voltage | V | Read | |||
| BC Line Voltage / B Phase Voltage | V | Read | |||
| CA Line Voltage / C Phase Voltage | V | Read | |||
| Meter Total Active Power | W | Read | |||
| Grid Load Power (Low Register) | W | Read | |||
| Backup Load Power (Low Register) | W | Read | |||
| Total PV Energy Generation | kWh | Read | |||
| Today's PV Energy Generation | kWh | Read | |||
| Grid Total Power Consumption | kWh | Read | |||
| Grid Total Power Feed-in | kWh | Read | |||
| Battery Total Charging Energy | kWh | Read | |||
| Battery Total Discharging Energy | kWh | Read | |||
| Inverter Current Status | Read | ||||
| Warning/Fault Message Data | Read | ||||
| Operating Status | Read | ||||
| Inverter Warning | Read | ||||
| Module ID 7 (Remote Control Information) | Read | ||||
| Module 7 Register Count | Read | ||||
| Remote Control Information Valid Identifier | Read | ||||
| Remote Control Status | Read | ||||
| Battery Available Charge Power Value | W | Read | |||
| Battery Available Discharge Power Value | W | Read | |||
| AC Grid Port Available Import Active Power Value | W | Read | |||
| AC Grid Port Available Export Active Power Value | W | Read | |||
| Parallel System Battery Available Charge Power Value | W | Read | |||
| Parallel System Battery Available Discharge Power Value | W | Read | |||
| Parallel System AC Grid Port Available Import Active Power Value | W | Read | |||
| Parallel System AC Grid Port Available Export Active Power Value | W | Read | |||
| Parallel System Inverter Online Bits | Read | ||||
| Product Model Number | Read | ||||
| DSP Software Major Version | Read | ||||
| HMI Software Major Version | Read | ||||
| Inverter Serial Number | Read | ||||
| DSP Software Sub Version | Read | ||||
| Maximum Charge/Discharge Current of This Device Battery | A | Read | |||
| Rated Output Current of This Device AC Grid Port | A | Read | |||
| Battery 1 Temperature | °C | Read | |||
| Inverter Battery MOSFET Temperature | °C | Read | |||
| DC Input Type | Read | ||||
| PV DC Voltage 3 | V | Read | |||
| PV DC Current 3 | A | Read | |||
| PV DC Voltage 4 | V | Read | |||
| PV DC Current 4 | A | Read | |||
| PV DC Voltage 5 | V | Read | |||
| PV DC Current 5 | A | Read | |||
| PV DC Voltage 6 | V | Read | |||
| PV DC Current 6 | A | Read | |||
| PV DC Voltage 7 | V | Read | |||
| PV DC Current 7 | A | Read | |||
| PV DC Voltage 8 | V | Read | |||
| PV DC Current 8 | A | Read | |||
| This Device Rated Apparent Power | VA | Read | |||
| Safety Regulation Version Number | Read | ||||
| HMI Software Sub Version | Read | ||||
| A Phase Current | A | Read | |||
| B Phase Current | A | Read | |||
| C Phase Current | A | Read | |||
| Reactive Power Value | var | Read | |||
| Apparent Power Value | VA | Read | |||
| National Standard Number | Read | ||||
| Inverter Module Temperature | °C | Read | |||
| Lead-Acid Battery Ambient Temperature | °C | Read | |||
| Current DRM Status | Read | ||||
| Standard Operating Mode Startup Status | Read | ||||
| Backup Port AC Voltage A | V | Read | |||
| Backup Port AC Current A | A | Read | |||
| Inverter AC Grid Port Real-time Total Active Power | W | Read | |||
| Backup Port AC Voltage B | V | Read | |||
| Backup Port AC Current B | A | Read | |||
| Backup Port AC Voltage C | V | Read | |||
| Backup Port AC Current C | A | Read | |||
| Battery Daily Charging Energy | kWh | Read | |||
| Battery Daily Discharging Energy | kWh | Read | |||
| Grid Daily Power Consumption | kWh | Read | |||
| Grid Daily Power Feed-in | kWh | Read | |||
| Load Total Power Consumption | kWh | Read | |||
| Load Daily Power Consumption | kWh | Read | |||
| Inverter AC Grid Port Total Power Feed-in | kWh | Read | |||
| Inverter AC Grid Port Total Power Consumption | kWh | Read | |||
| Italian Self-test Single Item | Read | ||||
| Italian Self-test Full Test Status | Read | ||||
| 59.S1 Measurement Voltage Value | V | Read | |||
| 59.S1 Measurement Time Value | ms | Read | |||
| 59.S2 Measurement Voltage Value | V | Read | |||
| 59.S2 Measurement Time Value | ms | Read | |||
| 27.S1 Measurement Voltage Value | V | Read | |||
| 27.S1 Measurement Time Value | ms | Read | |||
| 27.S2 Measurement Voltage Value | V | Read | |||
| 27.S2 Measurement Time Value | ms | Read | |||
| 81>.S1 Measurement Frequency Value | Hz | Read | |||
| 81>.S1 Measurement Time Value | ms | Read | |||
| 81<.S1 Measurement Frequency Value | Hz | Read | |||
| 81<.S1 Measurement Time Value | ms | Read | |||
| 81>.S2F Measurement Frequency Value | Hz | Read | |||
| 81>.S2F Measurement Time Value | ms | Read | |||
| 81<.S2F Measurement Frequency Value | Hz | Read | |||
| 81<.S2F Measurement Time Value | ms | Read | |||
| 81>.S2S Measurement Frequency Value | Hz | Read | |||
| 81>.S2S Measurement Time Value | ms | Read | |||
| 81<.S2S Measurement Frequency Value | Hz | Read | |||
| 81<.S2S Measurement Time Value | ms | Read | |||
| Parallel Inverter Power | kW | Read | |||
| Parallel Inverter CT Detection Switch | Read | ||||
| Meter AC Voltage A | V | Read | |||
| Meter AC Current A | A | Read | |||
| Meter AC Voltage B | V | Read | |||
| Meter AC Current B | A | Read | |||
| Meter AC Voltage C | V | Read | |||
| Meter AC Current C | A | Read | |||
| Meter Active Power A | W | Read | |||
| Meter Active Power B | W | Read | |||
| Meter Active Power C | W | Read | |||
| Meter Reactive Power A | var | Read | |||
| Meter Reactive Power B | var | Read | |||
| Meter Reactive Power C | var | Read | |||
| Meter Total Reactive Power | var | Read | |||
| Meter Apparent Power A | VA | Read | |||
| Meter Apparent Power B | VA | Read | |||
| Meter Apparent Power C | VA | Read | |||
| Meter Total Apparent Power | VA | Read | |||
| Meter Power Factor | Read | ||||
| Meter Grid Frequency | Hz | Read | |||
| Meter Total Active Energy Imported from Grid | kWh | Read | |||
| Meter Total Active Energy Exported to Grid | kWh | Read | |||
| Optimal Revenue Function Version Identification | Read | ||||
| Battery 1 BMS Real-time Status | Read | ||||
| Meter 2 Total Active Power | W | Read | |||
| Parallel System Inverter Online Status | Read | ||||
| 59.S1 Measurement Voltage Value (Phase B) | V | Read | |||
| 59.S1 Measurement Time Value (Phase B) | ms | Read | |||
| 59.S2 Measurement Voltage Value (Phase B) | V | Read | |||
| 59.S2 Measurement Time Value (Phase B) | ms | Read | |||
| 27.S1 Measurement Voltage Value (Phase B) | V | Read | |||
| 27.S1 Measurement Time Value (Phase B) | ms | Read | |||
| 27.S2 Measurement Voltage Value (Phase B) | V | Read | |||
| 27.S2 Measurement Time Value (Phase B) | ms | Read | |||
| 81>.S1 Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81>.S1 Measurement Time Value (Phase B) | ms | Read | |||
| 81<.S1 Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81<.S1 Measurement Time Value (Phase B) | ms | Read | |||
| 81>.S2F Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81>.S2F Measurement Time Value (Phase B) | ms | Read | |||
| 81<.S2F Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81<.S2F Measurement Time Value (Phase B) | ms | Read | |||
| 81>.S2S Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81>.S2S Measurement Time Value (Phase B) | ms | Read | |||
| 81<.S2S Measurement Frequency Value (Phase B) | Hz | Read | |||
| 81<.S2S Measurement Time Value (Phase B) | ms | Read | |||
| 59.S1 Measurement Voltage Value (Phase C) | V | Read | |||
| 59.S1 Measurement Time Value (Phase C) | ms | Read | |||
| 59.S2 Measurement Voltage Value (Phase C) | V | Read | |||
| 59.S2 Measurement Time Value (Phase C) | ms | Read | |||
| 27.S1 Measurement Voltage Value (Phase C) | V | Read | |||
| 27.S1 Measurement Time Value (Phase C) | ms | Read | |||
| 27.S2 Measurement Voltage Value (Phase C) | V | Read | |||
| 27.S2 Measurement Time Value (Phase C) | ms | Read | |||
| 81>.S1 Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81>.S1 Measurement Time Value (Phase C) | ms | Read | |||
| 81<.S1 Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81<.S1 Measurement Time Value (Phase C) | ms | Read | |||
| 81>.S2F Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81>.S2F Measurement Time Value (Phase C) | ms | Read | |||
| 81<.S2F Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81<.S2F Measurement Time Value (Phase C) | ms | Read | |||
| 81>.S2S Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81>.S2S Measurement Time Value (Phase C) | ms | Read | |||
| 81<.S2S Measurement Frequency Value (Phase C) | Hz | Read | |||
| 81<.S2S Measurement Time Value (Phase C) | ms | Read | |||
| Inverter AC Grid Port Phase A Active Power | W | Read | |||
| Inverter AC Grid Port Phase A Reactive Power | var | Read | |||
| Inverter AC Grid Port Phase A Apparent Power | VA | Read | |||
| Inverter AC Grid Port Phase B Active Power | W | Read | |||
| Inverter AC Grid Port Phase B Reactive Power | var | Read | |||
| Inverter AC Grid Port Phase B Apparent Power | VA | Read | |||
| Inverter AC Grid Port Phase C Active Power | W | Read | |||
| Inverter AC Grid Port Phase C Reactive Power | var | Read | |||
| Inverter AC Grid Port Phase C Apparent Power | VA | Read | |||
| Inverter Backup Port Phase A Active Power | W | Read | |||
| Inverter Backup Port Phase A Reactive Power | var | Read | |||
| Inverter Backup Port Phase A Apparent Power | VA | Read | |||
| Inverter Backup Port Phase B Active Power | W | Read | |||
| Inverter Backup Port Phase B Reactive Power | var | Read | |||
| Inverter Backup Port Phase B Apparent Power | VA | Read | |||
| Inverter Backup Port Phase C Active Power | W | Read | |||
| Inverter Backup Port Phase C Reactive Power | var | Read | |||
| Inverter Backup Side Phase C Apparent Power | VA | Read | |||
| Generator Phase A Active Power | W | Read | |||
| Generator Daily Power Generation | kWh | Read | |||
| Generator Total Power Generation | kWh | Read | |||
| Generator Phase B Active Power | W | Read | |||
| Generator Phase C Active Power | W | Read | |||
| Inverter AC Grid Port Daily Power Export | kWh | Read | |||
| Inverter AC Grid Port Daily Power Import | kWh | Read | |||
| Grid Load Total Power Consumption | kWh | Read | |||
| Grid Load Daily Power Consumption | kWh | Read | |||
| Backup Load Total Power Consumption | kWh | Read | |||
| Backup Load Daily Power Consumption | kWh | Read | |||
| LG 10H/16H Master Battery SOC | % | Read | |||
| LG 10H/16H Master Battery SOH | % | Read | |||
| LG 10H/16H Master Battery Voltage | V | Read | |||
| LG 10H/16H Master Battery Current | A | Read | |||
| LG 10H/16H Master Battery Maximum Charging Power | W | Read | |||
| LG 10H/16H Master Battery Maximum Discharging Power | W | Read | |||
| LG 10H/16H Master Battery DCDC Firmware Version (Main) | Read | ||||
| LG 10H/16H Master Battery DCDC Firmware Version (Test) | Read | ||||
| LG 10H/16H Master Battery BMS Firmware Version High Byte | Read | ||||
| LG 10H/16H Master Battery BMS Firmware Version Low Byte | Read | ||||
| LG 10H/16H Master Battery Fault ID | Read | ||||
| LG 10H/16H Master Battery Diagnostic Result | Read | ||||
| LG 10H/16H Master Battery Status/Mode | Read | ||||
| LG 10H/16H Master Battery Current Power | W | Read | |||
| LG 10H/16H Master Battery Maximum Temperature | °C | Read | |||
| LG 10H/16H Master Battery Status Flags | Read | ||||
| LG 10H/16H Secondary Battery SOC | % | Read | |||
| LG 10H/16H Secondary Battery SOH | % | Read | |||
| LG 10H/16H Secondary Battery Voltage | V | Read | |||
| LG 10H/16H Secondary Battery Current | A | Read | |||
| LG 10H/16H Secondary Battery Maximum Charging Power | W | Read | |||
| LG 10H/16H Secondary Battery Maximum Discharging Power | W | Read | |||
| LG 10H/16H Secondary Battery DCDC Firmware Version (Main) | Read | ||||
| LG 10H/16H Secondary Battery DCDC Firmware Version (Test) | Read | ||||
| LG 10H/16H Secondary Battery BMS Firmware Version High Byte | Read | ||||
| LG 10H/16H Secondary Battery BMS Firmware Version Low Byte | Read | ||||
| LG 10H/16H Secondary Battery Fault ID | Read | ||||
| LG 10H/16H Secondary Battery Diagnostic Result | Read | ||||
| LG 10H/16H Secondary Battery Status/Mode | Read | ||||
| LG 10H/16H Secondary Battery Current Power | W | Read | |||
| LG 10H/16H Secondary Battery Maximum Temperature | °C | Read | |||
| LG 10H/16H Secondary Battery Status Flags | Read | ||||
| AFCI Board Software Version | Read | ||||
| BMS2 Temperature | °C | Read | |||
| BMS2 SOC | % | Read | |||
| BMS2 SOH | % | Read | |||
| BMS2 Charging Voltage Limit | V | Read | |||
| BMS2 Charging Current Limit | A | Read | |||
| BMS2 Discharging Current Limit | A | Read | |||
| Battery 2 Real-time Voltage Value | V | Read | |||
| Battery 2 Real-time Current Value | A | Read | |||
| Battery 2 Real-time Charge/Discharge Direction | Read | ||||
| Smartport Phase A AC Voltage | V | Read | |||
| Smartport Phase B AC Voltage | V | Read | |||
| Smartport Phase C AC Voltage | V | Read | |||
| Smartport Phase A AC Current | A | Read | |||
| Smartport Phase B AC Current | A | Read | |||
| Smartport Phase C AC Current | A | Read | |||
| Grid Load Power (High Register) | W | Read | |||
| Backup Load Power (High Register) | W | Read | |||
| Battery 1 BMS Minimum Cell Voltage | V | Read | |||
| Battery 1 BMS Maximum Cell Voltage | V | Read | |||
| Battery 1 BMS Minimum Cell Temperature | °C | Read | |||
| Battery 1 BMS Maximum Cell Temperature | °C | Read | |||
| HMI-LCD Firmware Version | Read | ||||
| Battery 2 Real-time Power Value | W | Read | |||
| BMS2 Discharge Voltage Limit Value | V | Read | |||
| BMS2 Minimum Cell Voltage | V | Read | |||
| BMS2 Maximum Cell Voltage | V | Read | |||
| BMS2 Minimum Cell Temperature | °C | Read | |||
| BMS2 Maximum Cell Temperature | °C | Read | |||
| Smart Port Phase A Active Power | W | Read | |||
| Smart Port Phase B Active Power | W | Read | |||
| Smart Port Phase C Active Power | W | Read | |||
| Generator Frequency | Hz | Read | |||
| Smart Load Total Power Consumption | kWh | Read | |||
| Smart Load Daily Power Consumption | kWh | Read | |||
| Grid Load Phase A Active Power | W | Read | |||
| Grid Load Phase B Active Power | W | Read | |||
| Grid Load Phase C Active Power | W | Read | |||
| Parallel System Information Valid Flag | Read | ||||
| Parallel System Total PV Power | W | Read | |||
| Parallel System Total Generator Active Power | W | Read | |||
| Parallel System Total Battery Power | W | Read | |||
| Parallel System Total Backup Load Active Power | W | Read | |||
| Parallel System Total Inverter Active Power | W | Read | |||
| Parallel System Total Smart Load Active Power | W | Read | |||
| Parallel System AC Couple Total Active Power | W | Read | |||
| AC Coupling Total Power Generation | kWh | Read | |||
| AC Coupling Daily Power Generation | kWh | Read | |||
| Parallel System Grid Load Total Active Power | W | Read | |||
| Parallel System Public Grid Total Active Power | W | Read | |||
| PV DC Voltage 9 | V | Read | |||
| PV DC Current 9 | A | Read | |||
| PV DC Voltage 10 | V | Read | |||
| PV DC Current 10 | A | Read | |||
| Remote Dispatch Mode Valid Flag | Read | ||||
| Remote Dispatch Mode Function Version | Read | ||||
| Remote Dispatch Mode Running Status | Read | ||||
| Parallel System AC Grid Port Total Active Power | W | Read | |||
| Battery 2 BMS Real-time Status | Read | ||||
| Generator Preheat/Cooling Operation Status | Read | ||||
| Module ID 1 (Unit Port Powers) | Read | ||||
| Module 1 Register Count | Read | ||||
| Unit Port Powers Valid Identifier | Read | ||||
| PV Power | W | Read | |||
| Battery 1 Power | W | Read | |||
| Battery 2 Power | W | Read | |||
| Inverting Bridge Total Active Power | W | Read | |||
| Backup Load Total Active Power | W | Read | |||
| Backup Load Total Apparent Power | VA | Read | |||
| Inverter AC Grid Port Total Active Power | W | Read | |||
| Generator Total Active Power | W | Read | |||
| Smart Load Total Active Power | W | Read | |||
| Grid-tied Inverter Output Total Active Power | W | Read | |||
| Grid Load Total Active Power | W | Read | |||
| Public Grid Total Active Power | W | Read | |||
| Local PV Power | W | Read | |||
| Total Power of the Local Battery | W | Read | |||
| Total Active Power of the Local AC Grid Port | W | Read | |||
| Parallel System PV Power Value | W | Read | |||
| Parallel System Battery Charge/Discharge Power Value | W | Read | |||
| Parallel System AC Grid Port Active Power Value | W | Read | |||
| Parallel System PCC Active Power Value | W | Read | |||
| Max Battery SOC of Parallel System | % | Read | |||
| Min Battery SOC of Parallel System | % | Read | |||
| Remote Control Protocol Version | Read | ||||
| Module ID 6 (PV and Storage System) | Read | ||||
| Module 6 Register Count | Read | ||||
| PV and Storage System Valid Identifier | Read | ||||
| Hybrid Inverters PV Total Power | W | Read | |||
| Hybrid Inverters Total Battery Power | W | Read | |||
| Hybrid Inverters Total Inverter Active Power | W | Read | |||
| System Backup Load Total Active Power | W | Read | |||
| Hybrid Inverters AC Grid Port Total Active Power | W | Read | |||
| Generator Total Active Power 2 | W | Read | |||
| Hybrid Inverters Smart Load Total Active Power | W | Read | |||
| Grid-tied Inverters Total Active Power | W | Read | |||
| System Grid Load Total Active Power | W | Read | |||
| System Public Grid Total Active Power | W | Read | |||
| Number of Grid-tied Inverters Online | Read | ||||
| Definition of Solis Inverter Types | Read | ||||
| Real-Time Clock: Year | Read and write | ||||
| Real-Time Clock: Month | Read and write | ||||
| Real-Time Clock: Day | Read and write | ||||
| Real-Time Clock: Hour | Read and write | ||||
| Real-Time Clock: Minute | Read and write | ||||
| Real-Time Clock: Second | Read and write | ||||
| Slave Address Setting | Read and write | ||||
| Startup/Shutdown | Read and write | ||||
| Current Battery Model | Read and write | ||||
| Maximum Charging SOC | % | Read and write | |||
| Over-Discharge SOC | % | Read and write | |||
| Forced Charge SOC | % | Read and write | |||
| Rated Capacity | Read and write | ||||
| Over-Discharge Voltage | V | Read and write | |||
| Forced Charge Voltage | V | Read and write | |||
| Lead-Acid Battery Temperature Compensation Coefficient | Read and write | ||||
| Ambient Temperature Status Selection | Read and write | ||||
| 81>S1 | Hz | Read and write | |||
| 81>S1-T | s | Read and write | |||
| 81<S1 | Hz | Read and write | |||
| 81<S1-T | s | Read and write | |||
| 81>S2F | Hz | Read and write | |||
| 81>S2F-T | s | Read and write | |||
| 81<S2F | Hz | Read and write | |||
| 81<S2F-T | s | Read and write | |||
| 81>S2S | Hz | Read and write | |||
| 81>S2S-T | s | Read and write | |||
| 81<S2S | Hz | Read and write | |||
| 81<S2S-T | s | Read and write | |||
| National Standard Number Setting | Read and write | ||||
| Built-in EPM Hard Limit Switch | Read and write | ||||
| Built-in EPM Hard Limit Backflow Power | W | Read and write | |||
| Meter/CT Placement Setting | Read and write | ||||
| Setting of Maximum Grid-Fed Total Active Power | W | Read and write | |||
| AFCI Turn On / Turn Off | Read and write | ||||
| Italian Standard Mode Switching Digital Signal | Read and write | ||||
| Italian Self-test Full Test Start | Read and write | ||||
| Grid Upper Voltage Limit Required for Post-Fault Recovery | V | Read and write | |||
| Grid Lower Voltage Limit Required for Post-Fault Recovery | V | Read and write | |||
| Grid Upper Frequency Limit Required for Post-Fault Recovery | Hz | Read and write | |||
| Grid Lower Frequency Limit Required for Post-Fault Recovery | Hz | Read and write | |||
| Grid Upper Voltage Limit Required for First Power-On | V | Read and write | |||
| Grid Lower Voltage Limit Required for First Power-On | V | Read and write | |||
| Grid Upper Frequency Limit Required for First Power-On | Hz | Read and write | |||
| Grid Lower Frequency Limit Required for First Power-On | Hz | Read and write | |||
| Grid Primary Over-Voltage Threshold | V | Read and write | |||
| Grid Primary Over-Voltage Delay Threshold | ms | Read and write | |||
| Grid Secondary Over-Voltage Threshold | V | Read and write | |||
| Grid Secondary Over-Voltage Delay Threshold | ms | Read and write | |||
| Grid Primary Under-Voltage Threshold | V | Read and write | |||
| Grid Primary Under-Voltage Delay Threshold | ms | Read and write | |||
| Grid Secondary Under-Voltage Threshold | V | Read and write | |||
| Grid Secondary Under-Voltage Delay Threshold | ms | Read and write | |||
| Grid Primary Over-Frequency Threshold | Hz | Read and write | |||
| Grid Primary Over-Frequency Delay Threshold | ms | Read and write | |||
| Grid Secondary Over-Frequency Threshold | Hz | Read and write | |||
| Grid Secondary Over-Frequency Delay Threshold | ms | Read and write | |||
| Grid Primary Under-Frequency Threshold | Hz | Read and write | |||
| Grid Primary Under-Frequency Delay Threshold | ms | Read and write | |||
| Grid Secondary Under-Frequency Threshold | Hz | Read and write | |||
| Grid Secondary Under-Frequency Delay Threshold | ms | Read and write | |||
| Start-up Time | s | Read and write | |||
| Recovery Time Fault | s | Read and write | |||
| 10-Minute Average Over-Voltage Protection Threshold | V | Read and write | |||
| Energy Storage Control Switch | Read and write | ||||
| Backup Load Function Enable Setting | Read and write | ||||
| Backup Port AC Output Voltage Setting | V | Read and write | |||
| Battery 1 Maximum Charging Current Setting | A | Read and write | |||
| Battery 1 Maximum Discharging Current Setting | A | Read and write | |||
| Overload Voltage Droop Setting | Read and write | ||||
| Phase A Reverse Power Flow Setting | W | Read and write | |||
| Phase B Reverse Power Flow Setting | W | Read and write | |||
| Phase C Reverse Power Flow Setting | W | Read and write | |||
| Remote Control: Inverter AC Grid Port Active Power Setting | W | Read and write | |||
| Remote Control: Battery Discharging Power Setting | W | Read and write | |||
| Remote Control: Battery Charging Limit Power | W | Read and write | |||
| Remote Control: Battery Discharging Limit Power | W | Read and write | |||
| Remote Control: Grid Regulation via Remote Control | Read and write | ||||
| Remote Control: Battery Charge/Discharge Mode Setting | Read and write | ||||
| Remote Control: Battery Charging Power Setting | W | Read and write | |||
| EPS Switchover Time | ms | Read and write | |||
| Meter Type and Its Installation Location | Read and write | ||||
| TOU Scheduled Charging Current Setting | A | Read and write | |||
| TOU Scheduled Discharging Current Setting | A | Read and write | |||
| TOU Scheduled Charging Start Hour Setting | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting | min | Read and write | |||
| TOU Scheduled Charging Start Hour Setting 2 | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting 2 | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting 2 | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting 2 | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting 2 | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting 2 | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting 2 | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting 2 | min | Read and write | |||
| TOU Scheduled Charging Start Hour Setting 3 | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting 3 | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting 3 | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting 3 | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting 3 | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting 3 | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting 3 | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting 3 | min | Read and write | |||
| TOU Scheduled Charging Start Hour Setting 4 | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting 4 | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting 4 | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting 4 | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting 4 | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting 4 | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting 4 | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting 4 | min | Read and write | |||
| TOU Scheduled Charging Start Hour Setting 5 | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting 5 | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting 5 | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting 5 | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting 5 | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting 5 | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting 5 | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting 5 | min | Read and write | |||
| Total Grid-side Active Power Control Compensation | W | Read and write | |||
| Remote Control: Function Switch | Read and write | ||||
| Remote Control: Timeout Setting | min | Read and write | |||
| Meter Communication Access Method | Read and write | ||||
| Special Function Control Word 02 | Read and write | ||||
| AC Coupling Start SOC | % | Read and write | |||
| AC Coupling Start Voltage | V | Read and write | |||
| AC Coupling Start Frequency | Hz | Read and write | |||
| G100-2022 Grid-side Apparent Current Output Limit Setting | A | Read and write | |||
| Clear AFCI Fault | Read and write | ||||
| Lead-Acid Battery Equalization Enable | Read and write | ||||
| Lead-Acid Battery Equalization Voltage | V | Read and write | |||
| Lead-Acid Battery Equalization Time | min | Read and write | |||
| Lead-Acid Battery Equalization Timeout | min | Read and write | |||
| Lead-Acid Battery Equalization Interval | d | Read and write | |||
| Lead-Acid Battery Equalization Immediate Activation | Read and write | ||||
| Lead-Acid Battery Float Current Limit | A | Read and write | |||
| Generator Setting Enable Switch | Read and write | ||||
| Generator Start Lithium Battery SOC | % | Read and write | |||
| Generator Lithium Battery Charge Cut-off SOC | % | Read and write | |||
| Generator Start Lead-Acid Battery Voltage | V | Read and write | |||
| Generator Lead-Acid Battery Charge Cut-off Voltage | V | Read and write | |||
| Battery Wake-up Voltage Setting | V | Read and write | |||
| Battery Wake-up Time Setting | s | Read and write | |||
| MPPT Active Scanning Interval | s | Read and write | |||
| CT Ratio | Read and write | ||||
| Generator Start/Stop in Manual Mode | Read and write | ||||
| Generator Rated Input Power | kW | Read and write | |||
| Generator Setting Switch | Read and write | ||||
| Forced Stop Generator | Read and write | ||||
| Generator Maximum Allowable Percentage | % | Read and write | |||
| Generator Target Power | kW | Read and write | |||
| Generator Charging Power | kW | Read and write | |||
| Function Setting Enable Switch | Read and write | ||||
| Battery Auto-Wake-up Duration Setting | s | Read and write | |||
| Upgrade Type Selection | Read and write | ||||
| Single-Function Operation | Read and write | ||||
| Manual Master/Slave Setting | Read and write | ||||
| Inverter Connection Phase Setting | Read and write | ||||
| Standalone/Parallel Setting | Read and write | ||||
| Standard Operating Mode Switch | Read and write | ||||
| Over-Discharge Hysteresis SOC | % | Read and write | |||
| Battery Healing SOC | % | Read and write | |||
| Energy Storage Function Control Word | Read and write | ||||
| AC Coupling Stop SOC | % | Read and write | |||
| AC Coupling Stop Voltage | V | Read and write | |||
| AC Coupling Maximum Load-Shedding Frequency | Hz | Read and write | |||
| Peak SOC | % | Read and write | |||
| Maximum Allowable Total Grid-side Power Import | W | Read and write | |||
| TOU Scheduled Charging Start Hour Setting 6 | h | Read and write | |||
| TOU Scheduled Charging Start Minute Setting 6 | min | Read and write | |||
| TOU Scheduled Charging End Hour Setting 6 | h | Read and write | |||
| TOU Scheduled Charging End Minute Setting 6 | min | Read and write | |||
| TOU Scheduled Discharging Start Hour Setting 6 | h | Read and write | |||
| TOU Scheduled Discharging Start Minute Setting 6 | min | Read and write | |||
| TOU Scheduled Discharging End Hour Setting 6 | h | Read and write | |||
| TOU Scheduled Discharging End Minute Setting 6 | min | Read and write | |||
| LG High Voltage Battery Parallel Switch | Read and write | ||||
| LG High Voltage Battery Dead-Zone Lower Limit | V | Read and write | |||
| LG High Voltage Battery Dead-Zone Upper Limit | V | Read and write | |||
| LG High Voltage Battery Charging Slope | Read and write | ||||
| LG High Voltage Battery Maximum Charging Voltage | V | Read and write | |||
| LG High Voltage Battery Discharging Slope | Read and write | ||||
| LG High Voltage Battery Maximum Discharging Voltage | V | Read and write | |||
| LG High Voltage Battery Charging Limit Power | W | Read and write | |||
| LG High Voltage Battery Discharging Limit Power | W | Read and write | |||
| LG High Voltage Battery Communication Fault Timeout | min | Read and write | |||
| LG High Voltage Battery Sleep Hold Time | s | Read and write | |||
| LG High Voltage Battery Black-Start Enable | Read and write | ||||
| LG High-Voltage Battery Black-Start Initialization Time | s | Read and write | |||
| Backup Load Droop Control Minimum Voltage | V | Read and write | |||
| Smart Load Turn-off SOC | % | Read and write | |||
| Smart Load Turn-on SOC | % | Read and write | |||
| Smart Load Turn-off Battery Voltage | V | Read and write | |||
| Smart Load Turn-on Battery Voltage | V | Read and write | |||
| Over-Discharge Full Recovery Voltage | V | Read and write | |||
| Off-Grid Battery Over-Discharge SOC Function Switch | Read and write | ||||
| EPS Function Control | Read and write | ||||
| TOU Grid-Tied Optimization Revenue V2 Switch | Read and write | ||||
| TOU V2 Charge Period 1 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 1 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 1 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 1 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 1 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 1 End Hour | h | Read and write | |||
| TOU V2 Charge Period 1 End Minute | min | Read and write | |||
| TOU V2 Charge Period 2 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 2 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 2 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 2 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 2 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 2 End Hour | h | Read and write | |||
| TOU V2 Charge Period 2 End Minute | min | Read and write | |||
| TOU V2 Charge Period 3 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 3 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 3 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 3 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 3 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 3 End Hour | h | Read and write | |||
| TOU V2 Charge Period 3 End Minute | min | Read and write | |||
| TOU V2 Charge Period 4 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 4 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 4 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 4 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 4 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 4 End Hour | h | Read and write | |||
| TOU V2 Charge Period 4 End Minute | min | Read and write | |||
| TOU V2 Charge Period 5 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 5 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 5 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 5 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 5 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 5 End Hour | h | Read and write | |||
| TOU V2 Charge Period 5 End Minute | min | Read and write | |||
| TOU V2 Charge Period 6 Cut-off SOC | % | Read and write | |||
| TOU V2 Charge Period 6 Battery Current | A | Read and write | |||
| TOU V2 Charge Period 6 Cut-off Voltage | V | Read and write | |||
| TOU V2 Charge Period 6 Start Hour | h | Read and write | |||
| TOU V2 Charge Period 6 Start Minute | min | Read and write | |||
| TOU V2 Charge Period 6 End Hour | h | Read and write | |||
| TOU V2 Charge Period 6 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 1 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 1 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 1 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 1 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 1 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 1 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 1 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 2 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 2 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 2 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 2 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 2 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 2 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 2 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 3 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 3 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 3 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 3 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 3 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 3 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 3 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 4 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 4 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 4 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 4 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 4 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 4 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 4 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 5 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 5 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 5 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 5 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 5 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 5 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 5 End Minute | min | Read and write | |||
| TOU V2 Discharge Period 6 Cut-off SOC | % | Read and write | |||
| TOU V2 Discharge Period 6 Battery Current | A | Read and write | |||
| TOU V2 Discharge Period 6 Cut-off Voltage | V | Read and write | |||
| TOU V2 Discharge Period 6 Start Hour | h | Read and write | |||
| TOU V2 Discharge Period 6 Start Minute | min | Read and write | |||
| TOU V2 Discharge Period 6 End Hour | h | Read and write | |||
| TOU V2 Discharge Period 6 End Minute | min | Read and write | |||
| Generator Minimum Input Power | W | Read and write | |||
| Dual-Battery Connection Mode | Read and write | ||||
| Battery 2 Type Setting | Read and write | ||||
| Battery 2 Maximum Charging Current Setting | A | Read and write | |||
| Battery 2 Maximum Discharging Current Setting | A | Read and write | |||
| Battery 2 Under-Voltage Protection Setting | V | Read and write | |||
| Battery 2 Equalization Charge Voltage Setting | V | Read and write | |||
| Battery 2 Over-Voltage Protection Setting | V | Read and write | |||
| Battery 2 Over-Discharge SOC | % | Read and write | |||
| Battery 2 Over-Discharge Hysteresis SOC | % | Read and write | |||
| Battery 2 Forced Charge SOC | % | Read and write | |||
| Battery 2 Auto-Wake-up Duration Setting | s | Read and write | |||
| Battery 2 Type Follows Battery 1 | Read and write | ||||
| Battery 2 Wake-up Voltage | V | Read and write | |||
| Battery 2 Wake-up Time | s | Read and write | |||
| PCS Limiting Mode Setting | Read and write | ||||
| Grid-Side Load Single-Phase Protection Current Limit | A | Read and write | |||
| PCS Input Limit Battery Current Limit | A | Read and write | |||
| PCS Output Limit Battery Current Limit | A | Read and write | |||
| PV Inverter AC Output Side CT Ratio | Read and write | ||||
| Grid-Side Load Single-Phase Overcurrent Protection Switch | Read and write | ||||
| Heat Pump Function Switch | Read and write | ||||
| Heat Pump Minimum Control Time Interval | min | Read and write | |||
| Heat Pump Intelligent Control Mode Start SOC | % | Read and write | |||
| Heat Pump Intelligent Control Mode Stop SOC | % | Read and write | |||
| Heat Pump Intelligent Control Mode Start Voltage | V | Read and write | |||
| Heat Pump Intelligent Control Mode Stop Voltage | V | Read and write | |||
| Max Total Feed-in Power in Phase Unbalance Mode | W | Read and write | |||
| Paid Leasing Function | Read and write | ||||
| Paid Rental Equipment Lock Switch | Read and write | ||||
| Heat Pump Intelligent Control Mode Enable Power | kW | Read and write | |||
| Heat Pump Intelligent Control Mode Disable Power | kW | Read and write | |||
| AC Coupling Max Export Control | Read and write | ||||
| Dynamic Reactive Power Compensation Switch | Read and write | ||||
| AC Coupling Connected to AC Side | Read and write | ||||
| Remote Dispatch Mode Switch | Read and write | ||||
| Dispatch Failsafe Interval | min | Read and write | |||
| Dispatch System Limiting Switch | Read and write | ||||
| Dispatch System Power-Draw Active Power Upper Limit | W | Read and write | |||
| Dispatch System Feed-in Active Power Upper Limit | W | Read and write | |||
| Dispatch Real-Time Control Mode | Read and write | ||||
| Dispatch Real-Time Power Setting | W | Read and write | |||
| Dispatch Real-Time Function Switch | Read and write | ||||
| Dispatch Real-Time SOC Lower Limit | % | Read and write | |||
| Dispatch Real-Time SOC Upper Limit | % | Read and write | |||
| Dispatch Real-Time Battery Reserve SOC | % | Read and write | |||
| Dispatch Real-Time PV Power-Limit Percentage | % | Read and write | |||
| Dispatch Schedule Period 1 Switch | Read and write | ||||
| Dispatch Schedule Period 1 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 1 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 1 Control Mode | Read and write | ||||
| Dispatch Schedule Period 1 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 1 Function Switch | Read and write | ||||
| Dispatch Schedule Period 1 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 1 SOC Upper Limit | % | Read and write | |||
| Dispatch Schedule Period 1 Battery Reserve SOC | % | Read and write | |||
| Dispatch Schedule Period 1 PV Power-Limit Percentage | % | Read and write | |||
| Dispatch Schedule Period 2 Switch | Read and write | ||||
| Dispatch Schedule Period 2 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 2 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 2 Control Mode | Read and write | ||||
| Dispatch Schedule Period 2 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 2 Function Switch | Read and write | ||||
| Dispatch Schedule Period 2 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 2 SOC Upper Limit | % | Read and write | |||
| Dispatch Schedule Period 3 Switch | Read and write | ||||
| Dispatch Schedule Period 3 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 3 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 3 Control Mode | Read and write | ||||
| Dispatch Schedule Period 3 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 3 Function Switch | Read and write | ||||
| Dispatch Schedule Period 3 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 3 SOC Upper Limit | % | Read and write | |||
| Dispatch Schedule Period 4 Switch | Read and write | ||||
| Dispatch Schedule Period 4 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 4 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 4 Control Mode | Read and write | ||||
| Dispatch Schedule Period 4 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 4 Function Switch | Read and write | ||||
| Dispatch Schedule Period 4 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 4 SOC Upper Limit | % | Read and write | |||
| Dispatch Schedule Period 5 Switch | Read and write | ||||
| Dispatch Schedule Period 5 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 5 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 5 Control Mode | Read and write | ||||
| Dispatch Schedule Period 5 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 5 Function Switch | Read and write | ||||
| Dispatch Schedule Period 5 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 5 SOC Upper Limit | % | Read and write | |||
| Dispatch Schedule Period 6 Switch | Read and write | ||||
| Dispatch Schedule Period 6 Start Time Setting | Read and write | ||||
| Dispatch Schedule Period 6 End Time Setting | Read and write | ||||
| Dispatch Schedule Period 6 Control Mode | Read and write | ||||
| Dispatch Schedule Period 6 Power Setting | W | Read and write | |||
| Dispatch Schedule Period 6 Function Switch | Read and write | ||||
| Dispatch Schedule Period 6 SOC Lower Limit | % | Read and write | |||
| Dispatch Schedule Period 6 SOC Upper Limit | % | Read and write | |||
| ARM EMS Port Baud Rate Setting | Read and write | ||||
| Utility Bypass Function Switch Setting | Read and write | ||||
| PV Storage System Grid-tied Inverter Total Capacity | kW | Read and write | |||
| PV Storage System Grid-tied Inverter Quantity | Read and write | ||||
| PV Storage System Anti-Reverse-Flow Control Strategy | Read and write | ||||
| PV Storage System Anti-Reverse-Flow Control Mode | Read and write | ||||
| PV Storage System Grid Power Compensation | W | Read and write | |||
| PV Storage System Maximum Feed-in Total Active Power Setting | kW | Read and write | |||
| PV Storage System Maximum Feed-in Hard Limit Power Setting | kW | Read and write | |||
| PV Storage System G100 Total Grid Current Limit | A | Read and write | |||
| PV Storage System Meter 1 PT Voltage Ratio | Read and write | ||||
| PV Storage System Meter 2 PT Voltage Ratio | Read and write | ||||
| PV Storage System Meter 2 CT Ratio | Read and write | ||||
| PV Storage System Meter 2 CT Direction | Read and write | ||||
| PV Storage System Meter 2 Type and Location | Read and write | ||||
| TCP Port Function | Read and write | ||||
| TCP Port IP Address | Read and write | ||||
| TCP Port Subnet Mask | Read and write | ||||
| TCP Port Gateway | Read and write | ||||
| TCP Port DNS Server Address | Read and write | ||||
| TCP Port Secondary DNS Server Address | Read and write | ||||
| Modbus TCP Connection Port Number Setting | Read and write | ||||
| Grid Import Over-Limit Load Disconnect Enable | Read and write | ||||
| Grid Import Over-Limit Load Disconnect Control | Read and write | ||||
| Generator Maintenance Enable | Read and write | ||||
| Generator Maintenance Interval Time | d | Read and write | |||
| Generator Maintenance Runtime | min | Read and write | |||
| Generator Minimum Operating Power | kW | Read and write | |||
| TCP Port MAC Address Byte 1 & 2 | Read and write | ||||
| TCP Port MAC Address Byte 3 & 4 | Read and write | ||||
| TCP Port MAC Address Byte 5 & 6 | Read and write | ||||
| DRM Mode 2 S1 Feed-in Limit 1 | % | Read and write | |||
| DRM Mode 2 S2 Feed-in Limit 2 | % | Read and write | |||
| DRM Mode 2 S3 Feed-in Limit 3 | % | Read and write | |||
| DRM Mode 2 S4 Grid Charge Power Limit | W | Read and write | |||
| Remote Active Power Control Port Selection Command | Read and write | ||||
| Remote Reactive Power Control Port Selection Command | Read and write | ||||
| Power Control Battery Power Value | W | Read and write | |||
| Power Control AC Power Value | W | Read and write | |||
| Power Control Reactive Power Value | var | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show PV power, battery state of charge and grid exchange on one dashboard per installation.
- Get an email when battery state of charge drops below a threshold or the fault code is not zero.
- Keep 365 days of history for PV yield, battery charge and discharge energy and grid import and export.
- Change the charge and discharge time slots remotely when the customer moves to a dynamic tariff.
- Let an automation write a battery charge power when the energy price drops below a set value.
Installation
Connect RS485 A and B from the COM port of the inverter to the RS485 port of the ModbusCloud Gateway, with a termination resistor at the end of the bus.
Check the Modbus address and baud rate in the inverter menu. The default is address 1 at 9600 baud, 8 data bits, no parity, 1 stop bit.
In ModbusCloud, add a Modbus device with these settings and import the Solis S6-EH3P template.
Check that PV power, battery SOC and grid frequency come in with plausible values, for example around 50 Hz.
Ask ModbusCloud to enable writing for this gateway before you change settings.
Things to watch for
The inverter does not answer on RS485. What should I check?
Check address 1, 9600 baud, 8 data bits, no parity and 1 stop bit, then swap A and B. Use the COM port meant for external monitoring; a port that is already used by a meter or BMS has its own master. Leave at least 300 ms between requests.
Why do some values stay at zero?
The protocol covers several Solis storage inverters. Registers for features your model lacks, such as a second battery, a generator, PV strings 5 to 10 or a smart port, return zero. That is normal and not a fault.
My remote charge command stops after a few minutes. Why?
Remote charge, discharge and grid power commands switch off again when they are not repeated within the timeout set on the inverter, five minutes by default and adjustable from 2 to 30 minutes. The setting is also lost after a power cut. Repeat the command with an automation or raise the timeout.
Is it safe to write settings to the inverter?
Write only the settings you understand and check the allowed range first. Grid protection limits, the national standard and the battery type affect safety and compliance; leave those to the installer who commissioned the system. Write single values and keep at least 700 ms between write commands.
Grid load power looks wrong above 65 kW. What happened?
On large systems the grid load and backup load power are split over a low and a high register. Combine both registers as one 32-bit value, high register first, to get the full power.
Want to see how it works?