SunSpec SunSpec Model 701 — DER AC Measurement Modbus TCP template

SunSpec Model 701 — DER AC Measurement

SunSpec Model 701, known as DERMeasureAC, is the approved AC measurement information model for Distributed Energy Resources such as solar inverters and battery storage systems. Accessed over Modbus TCP, it exposes a comprehensive read-only register set covering per-system and per-phase active power, apparent power, reactive power, power factor, current, line-to-line and line-to-neutral voltage, grid frequency, cumulative injected and absorbed energy in both watt-hours and var-hours, six temperature points, throttling state, DER operating mode, alarm bitfields, and SunSpec scale factors. This template gives installers a single standardized interface for monitoring any IEEE 1547-2018 compliant DER without device-specific register hunting.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
72, read only
Brand
SunSpec
Last updated

Registers (72)

72 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
idRead
lRead
actypeRead
stRead
invstRead
connstRead
alrmRead
dermodeRead
wWRead
vaVARead
varVarRead
pfRead
aARead
llvVRead
lnvVRead
hzHzRead
totwhinjWhRead
totwhabsWhRead
totvarhinjVarhRead
totvarhabsVarhRead
tmpamb°CRead
tmpcab°CRead
tmpsnk°CRead
tmptrns°CRead
tmpsw°CRead
tmpot°CRead
wl1WRead
val1VARead
varl1VarRead
pfl1Read
al1ARead
vl1l2VRead
vl1VRead
totwhinjl1WhRead
totwhabsl1WhRead
totvarhinjl1VarhRead
totvarhabsl1VarhRead
wl2WRead
val2VARead
varl2VarRead
pfl2Read
al2ARead
vl2l3VRead
vl2VRead
totwhinjl2WhRead
totwhabsl2WhRead
totvarhinjl2VarhRead
totvarhabsl2VarhRead
wl3WRead
val3VARead
varl3VarRead
pfl3Read
al3ARead
vl3l1VRead
vl3VRead
totwhinjl3WhRead
totwhabsl3WhRead
totvarhinjl3VarhRead
totvarhabsl3VarhRead
throtpctPctRead
throtsrcRead
a_sfRead
v_sfRead
hz_sfRead
w_sfRead
pf_sfRead
va_sfRead
var_sfRead
totwh_sfRead
totvarh_sfRead
tmp_sfRead
mnalrminfoRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Monitor total and per-phase active power to verify that each phase carries the expected generation load.
  • Track cumulative injected and absorbed energy registers over time to produce accurate net-metering reports.
  • Alert on alarm bitfield changes to detect fault conditions on a DER before they cause grid disconnection.
  • Compare per-phase voltage and current to identify imbalance conditions requiring site investigation.
  • Verify throttling percentage and throttle source to confirm why output is being curtailed during grid events.

Installation

  1. Enable Modbus TCP on the DER device: log into the device web interface and activate the Modbus server under the communication or Modbus settings section, noting the TCP port (default 502).

  2. Connect the DER device to the same LAN segment as the ModbusCloud Gateway, confirm the device has a reachable static or DHCP-reserved IP address, and that port 502 is not blocked by a firewall.

  3. In the ModbusCloud portal, add the Gateway, create a new device, import the SunSpec Model 701 template, and enter the device IP address, port, and Modbus unit ID as configured on the DER.

  4. Trigger a manual poll and spot-check registers w (active power) and hz (frequency) against the device's own display to confirm correct scaling and byte order before saving the configuration.

Things to watch for

All values read as zero or the SunSpec NaN sentinel. Why?

SunSpec Model 701 registers are at model-relative offsets, not fixed absolute addresses. The actual holding register base shifts depending on which models precede it in the device's SunSpec map. Perform a full SunSpec model scan (read from address 40001 and walk the model chain) to locate the correct base address before reading any point.

Power and energy readings look wrong by a factor of 10 or 100. What is happening?

All measurement registers in Model 701 are raw integers that must be multiplied by 10 raised to the power of the corresponding scale factor register (for example, w_sf for active power). The scale factor is a signed int16 and may be negative. Read the relevant _sf register and apply it before displaying or storing the value.

The gateway connects but per-phase registers (wl2, wl3) all return NaN. Is this a wiring problem?

NaN on per-phase registers is expected for single-phase and split-phase devices: only L1 registers are populated in those configurations. Check the actype register first. If actype confirms three-phase but L2 and L3 registers still return NaN, the device firmware may not implement those optional points; consult the device PICS document.

Frequency register hz returns an implausible value. How do I interpret it?

The hz register is a uint32 spanning two Modbus registers. SunSpec encodes all values in big-endian byte order across registers. If your Modbus client is reading the two 16-bit words in the wrong order, the result will be wrong. Confirm your client uses big-endian word order, then apply hz_sf to obtain hertz.

Want to see how it works?