Thessla Green Recuperator AirPack
Monitors and controls Thessla Green AirPack recuperator ventilation units via Modbus RTU.
This template integrates with Thessla Green AirPack and AirPack Home recuperator units via Modbus RTU. It reads temperatures, airflow status, and bypass state while providing control over ventilation modes, airflow setpoints, and on/off switching.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 13, read and write
- Brand
- Thessla Green
- Key readings
- Temp. Outside, Intake, Extract, After pre-heating · Temp. Unit surroundings · Bypass status · Intake and Extract air flow status · Summer/winter mode status · Auto/manual mode status
- Available commands
- Vent. Unit On/Off · Bypass status · Air flow setpoint · Summer/winter and Auto/manual mode
- Compatible models
- AirPack · AirPack Home
- Last updated
Registers (13)
12 read, 6 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Bypass status | Read and write | ||||
| Vent.Unit On_Off status | Read and write | ||||
| Temp. Outside | °C | Read | |||
| Temp. Intake air | °C | Read | |||
| Summer_winter mode status | Read and write | ||||
| Auto_manual mode status | Read and write | ||||
| Temp. After pre-heating | °C | Read | |||
| Temp. Extract air | °C | Read | |||
| Temp. Unit surroundings | °C | Read | |||
| Special functions status | Read and write | ||||
| Intake air flow status | Read | ||||
| Extract air flow status | Read | ||||
| Air flow | Write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Monitor intake, extract, and outside temperatures on a live dashboard to verify recuperator efficiency.
- Control airflow setpoints remotely to adjust ventilation levels without a site visit.
- Create an alert when bypass status changes unexpectedly or outside temperature drops below a threshold.
- Switch between summer and winter mode remotely based on seasonal weather changes.
- Log historical temperature and airflow data to identify performance degradation over time.
- Toggle the ventilation unit on or off remotely for maintenance scheduling or emergency shutdown.
Installation
Connect the ModbusCloud Gateway to the Modbus RTU port on the Thessla Green AirPack unit using a twisted pair cable for the A and B data lines, plus a ground reference.
Set the gateway baud rate to 9600 to match the AirPack default Modbus RTU configuration.
Confirm with the HVAC installer that a free Modbus slot is available on the ventilation unit, as some stock control panels already occupy a Modbus connection.
Assign a unique Modbus slave address on the AirPack unit and configure the same address on the gateway.
Import the Thessla Green AirPack template in the ModbusCloud platform and link it to the configured gateway.
Verify that temperature readings and mode statuses appear correctly on the ModbusCloud dashboard before handing over to the customer.
Things to watch for
The gateway cannot communicate with the AirPack unit. What should I check first?
Verify that the baud rate on both the gateway and the AirPack is set to 9600. Also confirm that the Modbus slave address matches on both sides and that wiring polarity (A and B lines) is correct.
Can I connect the gateway if a wall-mounted control panel is already using Modbus?
Some factory control panels use Modbus to communicate with the main board. You need to verify that a free Modbus slot is available. Connecting two masters to the same port will cause communication conflicts.
Does this template work with both the AirPack and AirPack Home models?
Yes. The template is compatible with all Thessla Green AirPack series units, including the AirPack and AirPack Home models.
Temperature values appear as zero or unrealistic numbers. What could be wrong?
Check that the wiring is secure and that there are no termination resistor issues on the RS-485 bus. Also confirm that the correct Modbus register map is being used by verifying the template version matches your unit firmware.
Want to see how it works?