TROX TROX X-CUBE Modbus TCP template

TROX X-CUBE

Central air handling unit with integrated controller for ventilation, heat recovery, heating and cooling.

The TROX X-CUBE is a central air handling unit with its own controller that ventilates, recovers heat, heats, cools and controls humidity in offices, schools and other non-residential buildings. This Modbus TCP template reads air temperatures, humidity, pressures, airflow, air quality and all fault states, and lets you set the operating mode, standby and fan and temperature setpoints from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
183, read and write
Brand
TROX
Key readings
Supply air temperature · Extract air temperature · Relative humidity · Airflow · Duct pressure · CO2 concentration · Filter differential pressure · Operating mode
Available commands
Operating mode · Standby · Fan setpoints · Temperature limits · Humidity limits
Compatible models
X-CUBE · X-CUBE Compact · X-CUBE with X-CUBE CONTROL
Last updated

Registers (183)

168 read, 15 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
BMS Command BitsWrite32768FC06uint16
System Mode CommandWrite32769FC06uint16
Outdoor Temperature Input°CWrite32770FC06int16
Standby CommandWrite32791FC06uint16
Supply Fan SetpointWrite32792FC06uint16
Extract Fan SetpointWrite
Minimum Air Temperature Setpoint°CWrite
Maximum Air Temperature Setpoint°CWrite
Minimum Air Humidity Setpoint%Write
Maximum Air Humidity Setpoint%Write
Cooling Power Demand%Write
Supply Air Temperature Minimum°CWrite
Supply Air Temperature Maximum°CWrite
Supply Air Humidity MinimumWrite
Supply Air Humidity MaximumWrite
Supply Air Temperature°CRead
Extract Air Temperature°CRead
Outdoor Air Temperature°CRead
Exhaust Air Temperature°CRead
Outdoor Temperature Value°CRead
Outdoor Air Humidity%Read
Supply Air Humidity%Read
Extract Air Humidity%Read
Exhaust Air Humidity%Read
Supply Duct PressurePaRead
Exhaust Duct PressurePaRead
VOC ConcentrationppmRead
CO2 ConcentrationppmRead
Supply Air Temperature Setpoint°CRead
Extract Air Temperature Setpoint°CRead
Operation ModeRead
Event NotificationRead
System Status BitsRead
Smoke Detector BitsRead
External Alarm BitsRead
Supply Fan Speed Command%Read
Supply Fan Differential PressurePaRead
Supply Airflowm³/hRead
Supply Fan 2 Speed Command%Read
Supply Fan 2 Differential PressurePaRead
Supply Airflow 2m³/hRead
Extract Fan Speed Command%Read
Extract Fan Differential PressurePaRead
Extract Airflowm³/hRead
Extract Fan 2 Speed Command%Read
Extract Fan 2 Differential PressurePaRead
Extract Airflow 2m³/hRead
Supply Fan Status BitsRead
Extract Fan Status BitsRead
Outdoor Air Filter Holding TimehRead
Supply Air Filter Holding TimehRead
Extract Air Filter Holding TimehRead
Outdoor Air Filter Operating TimehRead
Supply Air Filter Operating TimehRead
Extract Air Filter Operating TimehRead
Outdoor Air Filter Differential PressurePaRead
Supply Air Filter Differential PressurePaRead
Extract Air Filter Differential PressurePaRead
Outdoor Air Filter 2 Holding TimehRead
Supply Air Filter 2 Holding TimehRead
Extract Air Filter 2 Holding TimehRead
Outdoor Air Filter 2 Operating TimehRead
Supply Air Filter 2 Operating TimehRead
Extract Air Filter 2 Operating TimehRead
Outdoor Air Filter 2 Differential PressurePaRead
Supply Air Filter 2 Differential PressurePaRead
Extract Air Filter 2 Differential PressurePaRead
Filter Status BitsRead
Plate Heat Exchanger Bypass Position%Read
Plate Heat Exchanger Bypass 2 Position%Read
Recovery Air Temperature°CRead
Plate Heat Exchanger Differential PressureRead
Plate Heat Exchanger Bypass Command%Read
Plate Heat Exchanger Bypass 2 Command%Read
Plate Heat Exchanger Status BitsRead
Heat Recovery Wheel Speed Command%Read
Heat Recovery Wheel Status BitsRead
Cooler Valve Position%Read
Cooler Inlet Temperature°CRead
Cooler Valve Command%Read
Preheater Valve Position%Read
Preheater Outlet Temperature°CRead
Preheater Valve Command%Read
Reheater Valve Position%Read
Reheater Outlet Temperature°CRead
Reheater Valve Command%Read
Cooler Status BitsRead
Preheater Status BitsRead
Reheater Status BitsRead
Outdoor Air Damper Position%Read
Supply Air Damper Position%Read
Extract Air Damper Position%Read
Exhaust Air Damper Position%Read
Recovery Air Damper Position%Read
Outdoor Air 2 Damper Position%Read
Supply Air 2 Damper Position%Read
Extract Air 2 Damper Position%Read
Exhaust Air 2 Damper Position%Read
Recovery Air 2 Damper Position%Read
Supply Fan Damper Position%Read
Extract Fan Damper Position%Read
Supply Fan 2 Damper Position%Read
Extract Fan 2 Damper Position%Read
Outdoor Air Damper Command%Read
Supply Air Damper Command%Read
Extract Air Damper Command%Read
Exhaust Air Damper Command%Read
Recovery Air Damper Command%Read
Outdoor Air 2 Damper Command%Read
Supply Air 2 Damper Command%Read
Extract Air 2 Damper Command%Read
Exhaust Air 2 Damper Command%Read
Recovery Air 2 Damper Command%Read
Supply Fan Damper Command%Read
Extract Fan Damper Command%Read
Supply Fan 2 Damper Command%Read
Extract Fan 2 Damper Command%Read
Damper Communication Error BitsRead
Sensor Communication Error BitsRead
Run Around Coil Status BitsRead
Run Around Coil Status Bits 2Read
Run Around Coil Pump Speed Command%Read
Run Around Coil Power Valve Command%Read
Run Around Coil Frost Valve Command%Read
Supply Exchanger Inlet Temperature°CRead
Supply Exchanger Outlet Temperature°CRead
Exhaust Exchanger Inlet Temperature°CRead
Exhaust Exchanger Return Temperature°CRead
Brine Temperature°CRead
Brine Volume Flowm³/hRead
Supply Exchanger Thermal PowerkWRead
Exhaust Exchanger Thermal PowerkWRead
Heating Feed Thermal PowerkWRead
Cooling Feed Thermal PowerkWRead
Refrigeration Status BitsRead
Fire Damper Closed 1 to 16Read
Fire Damper Closed 17 to 32Read
Fire Damper Closed 33 to 48Read
Fire Damper Closed 49 to 62Read
Fire Damper Opened 1 to 16Read
Fire Damper Opened 17 to 32Read
Fire Damper Opened 33 to 48Read
Fire Damper Opened 49 to 62Read
Fire Damper Closing Error 1 to 16Read
Fire Damper Closing Error 17 to 32Read
Fire Damper Closing Error 33 to 48Read
Fire Damper Closing Error 49 to 62Read
Fire Damper Opening Error 1 to 16Read
Fire Damper Opening Error 17 to 32Read
Fire Damper Opening Error 33 to 48Read
Fire Damper Opening Error 49 to 62Read
Fire Damper Position Error 1 to 16Read
Fire Damper Position Error 17 to 32Read
Fire Damper Position Error 33 to 48Read
Fire Damper Position Error 49 to 62Read
Fire Damper Triggered 1 to 16Read
Fire Damper Triggered 17 to 32Read
Fire Damper Triggered 33 to 48Read
Fire Damper Triggered 49 to 62Read
Supply Fans 3 to 16 OnRead
Supply Fans 3 to 16 ErrorRead
Supply Fans 3 to 16 Communication ErrorRead
Supply Fans 3 to 16 Repair SwitchRead
Extract Fans 3 to 16 OnRead
Extract Fans 3 to 16 ErrorRead
Extract Fans 3 to 16 Communication ErrorRead
Extract Fans 3 to 16 Repair SwitchRead
Electric Preheater Status BitsRead
Electric Preheater Power Command%Read
Electric Reheater Status BitsRead
Electric Reheater Power Command%Read
External Chiller Status BitsRead
External Chiller Power Command%Read
Humidifier Status BitsRead
Humidifier Power Command%Read
Heat Pump 1 Status BitsRead
Heat Pump 1 Power Command%Read
Heat Pump 2 Status BitsRead
Heat Pump 2 Power Command%Read
Heat Pump 3 Status BitsRead
Heat Pump 3 Power Command%Read
Heat Pump 4 Status BitsRead
Heat Pump 4 Power Command%Read

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show supply and extract air temperature, humidity and airflow per unit on one dashboard.
  • Get an email when the event notification reports a warning or a critical error.
  • Track filter differential pressure and running hours to plan filter changes.
  • Watch fire damper and smoke detector states across a building from the portal.
  • Switch a unit to standby or change its temperature limits remotely.

Installation

  1. Connect the ModbusCloud Gateway to the network of the X-CUBE controller with an Ethernet cable.

  2. Note the IP address of the controller; the factory setting is 192.168.0.180 or 192.168.0.200.

  3. In ModbusCloud, add a Modbus device (TCP) with that IP address, port 502 and unit ID 1, then import this template.

  4. Check that the supply air temperature and operating mode show plausible values.

  5. To write setpoints, release writing in the controller under Management operating level.

Things to watch for

The controller does not answer. What should I check?

Check that the Gateway and the controller are in the same subnet and that you can reach the IP address. Then try unit ID 1 or 255 and port 502; TROX does not publish fixed values. A firewall between both can block port 502.

Why do many registers stay at zero?

The register list covers every option of the X-CUBE. A unit without a humidifier, heat pump, run around coil or fire dampers reports zero for those parts. Hide the registers you do not need on your dashboard.

How do I read the status bits?

Most faults are packed as bits into one register per component, for example all supply fan states in one value. A value of 0 means no bit is set. An alarm rule 'not equal to 0' on such a register reports any fault of that component.

Why does writing a setpoint have no effect?

The controller blocks writes until they are released under Management operating level, and some setpoints can be blocked separately. Writing from the portal also has to be enabled for your Gateway. Temperature setpoints use steps of 0.1 °C.

Want to see how it works?