Vertiv Liebert PDX and PCW (iCOM 3)

Precision cooling for server rooms with temperatures, humidity, alarms and setpoints over Modbus TCP.

The Vertiv Liebert PDX is a direct expansion precision cooling unit for server rooms and data centres, and the Liebert PCW is its chilled water counterpart, both run by the Liebert iCOM 3 controller. This Modbus TCP template reads temperatures, humidity, pressures, alarms and working hours and lets you write on/off, setpoints and settings from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
659, read and write
Brand
Vertiv
Key readings
Return temperature · Supply temperature · Return humidity · Discharge pressure · Fan speed · Common alarm active · Energy consumption
Available commands
Unit on/off · Alarm reset · Return temperature setpoint · Relative humidity setpoint
Compatible models
Liebert PDX with iCOM 3, V1A application · Liebert PCW with iCOM 3, V1A application · Vertiv Liebert PDX direct expansion perimeter cooling unit · Vertiv Liebert PCW chilled water perimeter cooling unit
Last updated

Registers (659)

659 read, 189 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Current Temperature Setpoint (Used by Application)°CRead3FC03uint16
Actual Humidity Setpoint (Used by Application)Read17FC03uint16
Current Fan Speed Setpoint (Used by Application)Read30FC03uint16
Static Pressure Local ValuePaRead38FC03int16
Static Pressure System ValuePaRead39FC03int16
Suction Pressure Value Circ 1barRead
Suction Pressure Value Circ 2barRead
Discharge Pressure Value Circ 1barRead
Discharge Pressure Value Circ 2barRead
Suction Temperature Value Circ 1°CRead
Suction Temperature Value Circ 2°CRead
Discharge Temperature Value Circ 1°CRead
Discharge Temperature Value Circ 2°CRead
Return Temperature 1 Value°CRead
Return Temperature 2 Value°CRead
Return Temperature 3 Value°CRead
Return Temperature 4 Value°CRead
Return Temperature Value (Result)°CRead
Return Humidity 1 Value%Read
Return Humidity 2 Value%Read
Return Humidity 3 Value%Read
Return Humidity 4 Value%Read
Return Humidity Value (Result)Read
Supply Temperature 1 Value°CRead
Supply Temperature 2 Value°CRead
Supply Temperature 3 Value°CRead
Supply Temperature Value (Result)°CRead
Supply Fan Safe Value°CRead
Outdoor Temperature Value°CRead
Glycol Temperature Value°CRead
Remote Temperature 1 Value°CRead
Remote Temperature 2 Value°CRead
Remote Temperature 3 Value°CRead
Remote Temperature 4 Value°CRead
Remote Temperature 5 Value°CRead
Remote Temperature 6 Value°CRead
Remote Temperature 7 Value°CRead
Remote Temperature 8 Value°CRead
Remote Temperature 9 Value°CRead
Remote Temperature 10 Value°CRead
Remote Temperature Value (Result)°CRead
Remote Humidity 1 Value%Read
Remote Humidity 2 Value%Read
Remote Humidity 3 Value%Read
Remote Humidity 4 Value%Read
Remote Humidity 5 Value%Read
Remote Humidity 6 Value%Read
Remote Humidity 7 Value%Read
Remote Humidity 8 Value%Read
Remote Humidity 9 Value%Read
Remote Humidity 10 Value%Read
Remote Humidity Value (Result)%Read
Optional Sensor Temperature 1 Value°CRead
Optional Sensor Temperature 2 Value°CRead
Optional Sensor Temperature 3 Value°CRead
Optional Sensor Humidity 1 Value%Read
Optional Sensor Humidity 2 Value%Read
Optional Sensor Humidity 3 Value%Read
Air Eco Temperature Value°CRead
Air Eco Humidity Value%Read
Inlet Water Temperature C1 Value°CRead
Outlet Water Temperature C1 Value°CRead
Inlet Water Temperature C2 Value°CRead
Outlet Water Temperature C2 Value°CRead
Water Flow Circ 1 Value (l/s)l/sRead
Water Flow Circ 2 Value (l/s)l/sRead
Cool Gross Circ 1 ValuekWRead
Cool Gross Circ 2 ValuekWRead
System Return Temperature Value°CRead
System Return Humidity Value%Read
System Supply Temperature Value°CRead
System Remote Temperature Value°CRead
System Remote Humidity Value%Read
Input RMS A-NVRead
Input RMS B-NVRead
Input RMS C-NVRead
Input RMS A-BVRead
Input RMS B-CVRead
Input RMS C-AVRead
Input RMS Current Phase AARead
Input RMS Current Phase BARead
Input RMS Current Phase CARead
Instantaneous PowerWRead
Energy ConsumptionkWhRead
Water Flow Circ 1 Value (m3/h)m³/hRead
Water Flow Circ 2 Value (m3/h)m³/hRead
Analog Output 1 Value%Read
Analog Output 2 Value%Read
Analog Output 3 Value%Read
Analog Output 4 Value%Read
Analog Output 5 Value%Read
Evaporator Fan 1 Status (Modbus)Read
Evaporator Fan 2 Status (Modbus)Read
Evaporator Fan 3 Status (Modbus)Read
Evaporator Fan 4 Status (Modbus)Read
Evaporator Fan 5 Status (Modbus)Read
Evaporator Fan 6 Status (Modbus)Read
Compressor 1 Circ 1 StatusRead
Compressor 1 Circ 1 Request%Read
Compressor 2 Circ 1 StatusRead
Compressor 2 Circ 1 Request%Read
Compressor 1 Circ 2 StatusRead
Compressor 1 Circ 2 Request%Read
Compressor 2 Circ 2 StatusRead
Compressor 2 Circ 2 Request%Read
CW2 Opening Position%Read
Condenser 1 Request%Read
Condenser 1 Fan/Valve 1 Status (Modbus)Read
Condenser 1 Fan/Valve 2 Status (Modbus)Read
Condenser 1 Fan/Valve 3 Status (Modbus)Read
Condenser 1 Fan/Valve 4 Status (Modbus)Read
Condenser 2 Request%Read
Condenser 2 Fan/Valve 1 Status (Modbus)Read
Condenser 2 Fan/Valve 2 Status (Modbus)Read
Condenser 2 Fan/Valve 3 Status (Modbus)Read
Condenser 2 Fan/Valve 4 Status (Modbus)Read
Humidifier StatusRead
Dehumidification StatusRead
Heating Request%Read
Cooling Request (DX/CW)%Read
Humidification Request%Read
Dehumidification Request%Read
Fan Request%Read
Ultracapacitor/ATSRead
Unit StatusRead
System Fan Speed Request%Read
System FC Request%Read
System DX/CW Request%Read
System Heating Request%Read
System Humidification Request%Read
System Dehumidification Request%Read
Electrode Humidifier CurrentARead
Electrode Humidifier ConductivityRead
Electrode Humidifier Steam Productionkg/hRead
Electrode Humidifier Cylinder StateRead
Air Economizer StatusRead
Power Consumption CalculatorWRead
Frecooling Request%Read
Remote Humidity Value (Result) HumValRem_ActRead
Sel Man-AutoRead
PRE Working ModeRead
Fan Working HourshRead
CW1 Working HourshRead
CW2 Working HourshRead
Comp 1 Circ 1 Working HourshRead
Comp 2 Circ 1 Working HourshRead
Comp 1 Circ 2 Working HourshRead
Comp 2 Circ 2 Working HourshRead
EEV Circuit 1 Working HourshRead
EEV Circuit 2 Working HourshRead
FC Working HourshRead
Air Eco Working HourshRead
PRE 1 Working HourshRead
PRE 2 Working HourshRead
Condenser 1 Working HourshRead
Condenser 2 Working HourshRead
Humidification Working HourshRead
Dehumidification Working HourshRead
Heating 1 Working HourshRead
Heating 2 Working HourshRead
Hot Gas/Hot Water Working HourshRead
Pressure Prop BandPaRead
CF Differential PressurePaRead
Analog Input 1 ValueRead
Analog Input 2 ValueRead
Analog Input 3 ValueRead
Analog Input 4 ValueRead
Pump 1 Inlet PressurebarRead
Pump 2 Inlet PressurebarRead
Circuit 1 Outdoor Temperature°CRead
Circuit 2 Outdoor Temperature°CRead
EEV 1 Position%Read
EEV 2 Position%Read
Pump 1 Speed%Read
Pump 2 Speed%Read
Pump 1 Inlet Temperature°CRead
Pump 2 Inlet Temperature°CRead
Pump 1 Outlet Temperature°CRead
Pump 2 Outlet Temperature°CRead
Pump 1 StateRead
Pump 2 StateRead
Operating ModeRead
Fluid Eco StatusRead
Daily High Control Temperature°CRead
Daily Low Control Temperature°CRead
Daily High Return Humidity%Read
Daily Low Return Humidity%Read
Cooling Control Temperature°CRead
Fan Control Temperature°CRead
Supersaver Signal%Read
CW1 Opening Position%Read
Evaporator Fan 7 Status (Modbus)Read
Evaporator Fan 8 Status (Modbus)Read
Retain Memory ErrorRead
Too Much Retain WritingRead
Heater High Temperature LockoutRead
High Return TemperatureRead
High Supply TemperatureRead
High Remote TemperatureRead
Low Return TemperatureRead
Low Supply TemperatureRead
Low Remote TemperatureRead
One (or More) Evaporator Fan in AlarmRead
One (or More) Evaporator Fan OfflineRead
All Evaporator Fans OfflineRead
Loss of Air FlowRead
BMS OfflineRead
Low Pressure Circuit 1Read
Low Pressure Circuit 2Read
High Pressure Circuit 1Read
High Pressure Circuit 2Read
Soft High Pressure Circuit 1Read
Soft High Pressure Circuit 2Read
Thermal Protection Compressor 1 Circuit 1Read
Thermal Protection Compressor 2 Circuit 1Read
Thermal Protection Compressor 1 Circuit 2Read
Thermal Protection Compressor 2 Circuit 2Read
Low Suction SuperHeat Circuit 1Read
Low Suction SuperHeat Circuit 2Read
High Suction SuperHeat Circuit 1Read
High Suction SuperHeat Circuit 2Read
Return Sensor Failure (Cumulative)Read
Supply Sensor Failure (Cumulative)Read
Remote Sensor Failure (Cumulative)Read
Outdoor Sensor FailureRead
Suction Pressure Sensor Circuit 1 FailureRead
Suction Pressure Sensor Circuit 2 FailureRead
Discharge Pressure Sensor Circuit 1 FailureRead
Discharge Pressure Sensor Circuit 2 FailureRead
Suction Temperature Sensor Circuit 1 FailureRead
Suction Temperature Sensor Circuit 2 FailureRead
Discharge Temperature Sensor Circuit 1 FailureRead
Discharge Temperature Sensor Circuit 2 FailureRead
Configurable AlarmRead
C-Input 1Read
C-Input 2Read
C-Input 3Read
C-Input 4Read
Compressor Lockout (with PumpDown)Read
Compressor LockoutRead
Condenser 1 FailureRead
Condenser 2 FailureRead
Condensing Pump AlarmRead
Condensing Pump Alarm Al_CndPmpLCEvtRead
Condensing Pump Alarm Al_CndPmpSDEvtRead
Fire AlarmRead
Loss of FlowRead
Loss of Flow Al_FlowALLCEvtRead
Loss of Flow AL_FlowALSDEvtRead
Heater AlarmRead
High CW1 TemperatureRead
High CW2 TemperatureRead
Humidifier ProblemRead
Configurable WarningRead
Water AlarmRead
No PowerRead
Smoke AlarmRead
Clogged FilterRead
Stop Due to High TempRead
Out Of Working RangeRead
High Remote HumidityRead
Low Return HumidityRead
Low Remote HumidityRead
High Return HumidityRead
Soft Low Pressure Circuit 1 (MTM Only)Read
Force FCRead
Humidity Return Sensor Failure (MTM Only)Read
UC MissingRead
Conditioner/Fans Working Hours ExceededRead
CW1 Valve Working Hours ExceededRead
CW2 Valve Working Hours ExceededRead
Comp1 Circ1 Working Hours ExceededRead
Comp2 Circ1 Working Hours ExceededRead
Comp1 Circ2 Working Hours ExceededRead
Comp2 Circ2 Working Hours ExceededRead
FC Working Hours ExceededRead
AirEco Working Hours ExceededRead
PRE1 Working Hours ExceededRead
PRE2 Working Hours ExceededRead
El. Heater1 Working Hours ExceededRead
El. Heater2 Working Hours ExceededRead
Hot Water/Gas Working Hours ExceededRead
Condenser Fans1 Working Hours ExceededRead
Condenser Fans2 Working Hours ExceededRead
Humidifier Working Hours ExceededRead
Dehumidification Working Hours ExceededRead
VSD Circuit 1 Out of EnvelopeRead
VSD Circuit 1 Generic EventRead
VSD Circuit 1 OfflineRead
VSD Circuit 1 Generic Event Al_WarnVSD_Circ1Read
VSD Circuit 2 Out of EnvelopeRead
VSD Circuit 2 Generic EventRead
VSD Circuit 2 OfflineRead
VSD Circuit 2 Generic Event Al_WarnVSD_Circ2Read
Network FailureRead
No Connection to Unit 1Read
One (or More) Condenser C1 Fan in AlarmRead
One (or More) Condenser C1 Fan OfflineRead
All Condenser C1 Fans OfflineRead
One (or More) Condenser C2 Fan in AlarmRead
One (or More) Condenser C2 Fan OfflineRead
All Condenser C2 Fans OfflineRead
Master Unit Not AvailableRead
HCB OfflineRead
HCB Shut DownRead
Energy Meter OfflineRead
Low Operating Pressure Circuit 1Read
Low Operating Pressure Circuit 2Read
Maximum Operating Pressure Circuit 2Read
Maximum Operating Pressure Circuit 1Read
Generic EEV Circuit 1Read
Generic EEV Circuit 2Read
EEV Driver Offline Circuit 1Read
EEV Driver Offline Circuit 2Read
All Condenser C1 Fans in AlarmRead
All Condenser C2 Fans in AlarmRead
High Discharge Temperature Circuit 1Read
High Discharge Temperature Circuit 2Read
Wrong Damper PositionRead
Reduced Eco Air FlowRead
VSD Circuit 1 Startup FailureRead
VSD Circuit 2 Startup FailureRead
Loss of CW1 FlowRead
Loss of CW2 FlowRead
FC Off by DehumRead
FC Stopped for 1 Hour by HumRead
FC Stopped for 1 Hour by DehumRead
FC Stopped for 1 Hour by DT3Read
Dehum Stop by Low Limit 1Read
Dehum Stop by Low Limit 2Read
FC LockoutRead
Second Set Point ActiveRead
Heaters LockoutRead
Humidifier and Heaters LockoutRead
Humidifier LockoutRead
Standby OnRead
Cool and Fan 100%Read
Ultracap ActiveRead
Power OnRead
Power OffRead
Unit OnRead
Expansion Board 1 OfflineRead
Expansion Board 2 OfflineRead
Heater High Temperature Probe FailRead
Optional Probe 1 FailRead
Air Economizer Probe FailRead
Glycol Temperature Probe FailRead
Optional Probe 2 FailRead
Optional Probe 3 FailRead
CW1 Inlet Probe FailRead
CW1 Outlet Probe FailRead
CW2 Inlet Probe FailRead
CW2 Outlet Probe FailRead
Local Static Pressure Sensor FailRead
System Static Pressure Sensor FailRead
CW1 Water Flow Sensor FailRead
CW2 Water Flow Sensor FailRead
Return System Sensor FailureRead
Remote System Sensor FailureRead
HCB DisableRead
Mb CW Valve 1 OfflineRead
Mb CW Valve 2 OfflineRead
Mb CW Valve 3 OfflineRead
Mb CW Valve 4 OfflineRead
Supply Water High ConductivityRead
Air Eco Emergency OverrideRead
Remote 1 Sensor FailureRead
Remote 2 Sensor FailureRead
Remote 3 Sensor FailureRead
Remote 4 Sensor FailureRead
Remote 5 Sensor FailureRead
Remote 6 Sensor FailureRead
Remote 7 Sensor FailureRead
Remote 8 Sensor FailureRead
Remote 9 Sensor FailureRead
Remote 10 Sensor FailureRead
Condenser Refrigerant Sensor T1 FailureRead
Pump1 Outlet Temp Sensor FailureRead
Pump1 Inlet Press Sensor FailureRead
Pump1 Outlet Press Sensor FailureRead
Condenser Refrigerant Sensor T2 FailureRead
Pump2 Outlet Temp Sensor FailureRead
Pump2 Inlet Press Sensor FailureRead
Pump2 Outlet Press Sensor FailureRead
Pump1 FailureRead
Pump2 FailureRead
Condenser 1 Outdoor Temp Sensor FailureRead
Condenser 2 Outdoor Temp Sensor FailureRead
Expansion Board 3 OfflineRead
Expansion Board 4 OfflineRead
Unit Off by DisplayRead
Unit Off by Remote InputRead
Unit Off by 3 Pos SwitchRead
Unit Off by MonitoringRead
Unit Off by TimerRead
Unit Off by AlarmRead
Unit Standby ModeRead
Unit Manual ModeRead
Very Low Outdoor TemperatureRead
Very Low Outdoor Temperature Al_CndLowAmbThrs3Read
Low SuperHeat Pump 1Read
High SuperHeat Pump 1Read
Low SubCool Pump 1Read
Low Diff Press Pump 1Read
High Diff Press Pump 1Read
Low SuperHeat Pump 2Read
High SuperHeat Pump 2Read
Low SubCool Pump 2Read
Low Diff Press Pump 2Read
High Diff Press Pump 2Read
Pump 1 AlarmRead
Pump 2 AlarmRead
Startup Failure Pump 1Read
Startup Failure Pump 2Read
Startup Lock Pump 1Read
Startup Lock Pump 2Read
Low Start Pressure Circuit 1Read
Low Start Pressure Circuit 2Read
Stop On Low Pressure Circuit 1Read
Stop On Low Pressure Circuit 2Read
Freeze Protection Circuit 1Read
Freeze Protection Circuit 2Read
Low Start Pressure Circuit 1 Al_LowStartPMsgCirc1Read
Low Start Pressure Circuit 2 Al_LowStartPMsgCirc2Read
Capacity Derating Circuit 1Read
Capacity Derating Circuit 2Read
Static Pressure Out Of RangeRead
EEV Circuit 1 Working Hours ExceededRead
EEV Circuit 2 Working Hours ExceededRead
EconoPhase Prop LockoutRead
Surge Arrester FailureRead
Clogged Filter Th1Read
Clogged Filter Th2Read
Clogged Filter ErrorRead
ATS ErrorRead
Airflow Sensor FailureRead
Mb Condenser Valve 1 OfflineRead
Mb Condenser Valve 2 OfflineRead
Mb FC Valve 1 OfflineRead
Aux Sensor DisconnectedRead
Unit On/Off CommandRead and write
System On/Off CommandRead and write
Configurable Input 1Read
Configurable Input 2Read
Configurable Input 3Read
Configurable Input 4Read
Configurable Input 5Read
Configurable Input 6Read
Configurable Input 7Read
Configurable Input 8Read
Airflow StatusRead
Low Pressure Circ 1 StatusRead
High Pressure Circ 1 StatusRead
Thermal Protection Compressor 1 Circ 1Read
Thermal Protection Compressor 2 Circ 1Read
Low Pressure Circ 2 StatusRead
High Pressure Circ 2 StatusRead
Thermal Protection Compressor 1 Circ 2Read
Thermal Protection Compressor 2 Circ 2Read
Remote OffRead
3 Position SwitchRead
Clogged Filter CFRead
Heater 1Read
Heater 2Read
Low Limit 1 LowLim1_LockRead
Low Limit 2 LowLim2_LockRead
Unit On/Off Command by BMSRead and write
Alarm Reset by BMSRead and write
Generic Alarm ActiveRead
Generic Warning ActiveRead
Generic Event ActiveRead
BMS Heart BeatRead and write
ATS Power Supply Line in UseRead
ATS Power Supply 1 StatusRead
ATS Power Supply 2 StatusRead
Return Temperature Setpoint°CRead and write
Remote Temperature Setpoint°CRead and write
Supply Temperature Setpoint°CRead and write
Second Setpoint°CRead and write
Backup Setpoint (Temp)°CRead and write
Compensation ValueKRead and write
Return Proportional BandKRead and write
Remote Proportional BandKRead and write
Supply Proportional BandKRead and write
Return Temperature DeadBandKRead and write
Remote Temperature DeadBandKRead and write
Supply Temperature DeadBandKRead and write
Relative Humidity Setpoint%Read and write
Absolute Humidity Setpointg/kgRead and write
Dew Point Humidity Setpoint°CRead and write
Relative Humidity Proportional Band%Read and write
Absolute Humidity Proportional Bandg/kgRead and write
Dew Point Humidity Proportional BandKRead and write
Relative Humidity DeadBand%Read and write
Absolute Humidity DeadBandg/kgRead and write
Dew Point Humidity DeadBandKRead and write
Return Fan Speed Setpoint°CRead and write
Remote Fan Speed Setpoint°CRead and write
Supply Fan Speed Setpoint°CRead and write
Delta Fan Speed SetpointKRead and write
Static Pressure SetpointPaRead and write
Static Pressure DeadBandPaRead and write
Low Limit 1KRead and write
Low Limit 2KRead and write
Condenser Cut-OffbarRead and write
Condenser 1 SetpointbarRead and write
Condenser 1 Proportional BandbarRead and write
Condenser 2 SetpointbarRead and write
Condenser 2 Proportional BandbarRead and write
System Temperature Setpoint°CRead and write
System Humidity SetpointRead and write
Temperature ControlRead and write
Compensation TypeRead and write
Return Integration TimesRead and write
Remote Integration TimesRead and write
Supply Integration TimesRead and write
Humidity ControlRead and write
Humidity Control MethodRead and write
Fan Speed ControlRead and write
Auto ModeRead and write
Fixed Fan Speed%Read and write
Fan Startup Speed%Read and write
Fan Startup TimesRead and write
Fan Shutdown Speed%Read and write
Fan Shutdown TimesRead and write
Minimum Speed%Read and write
Maximum Speed%Read and write
Minimum DX Speed%Read and write
Dehumidification Speed%Read and write
Humidification Speed%Read and write
Heating Speed%Read and write
No Power Speed%Read and write
Control Sensor Failure Speed%Read and write
Fan Back Draft ControlRead and write
Fan Back Draft Control Speed%Read and write
High Return Temperature Event EnableRead and write
High Ret Temp Speed%Read and write
Modbus High Speed OperationRead and write
CW Valve Operating ModeRead and write
CW Main ValveRead and write
Daily Valve RotationRead and write
Rotation HourRead and write
Loss of Flow at%Read and write
CW Start Position%Read and write
CW Start TimesRead and write
Configurable Input 1 SettingRead and write
Configurable Input 2 SettingRead and write
Configurable Input 3 SettingRead and write
Configurable Input 4 SettingRead and write
Configurable Input 5 SettingRead and write
Configurable Input 6 SettingRead and write
Configurable Input 7 SettingRead and write
Configurable Input 8 SettingRead and write
Auto Restart EnableRead and write
Auto Restart TimesRead and write
Dehumidification EnableRead and write
Low Limit ProbeRead and write
Alarm OFF by LWDRead and write
Alarm OFF by Loss of AirflowRead and write
Alarm OFF by High Supply Temp.Read and write
Humidifier Steam Rate%Read and write
Return Damper EnableRead and write
Return Damper Opening TimesRead and write
Condenser Control TypeRead and write
Condenser Min Speed/Opening%Read and write
Condenser Max Speed/Opening%Read and write
Condenser 1 Integration TimesRead and write
Condenser 1 Setpoint TypeRead and write
Condenser 2 Integration TimesRead and write
Condenser 2 Setpoint TypeRead and write
High Return Temperature Event Limit°CRead and write
Low Return Temperature Event EnableRead and write
Low Return Temperature Event Limit°CRead and write
High Remote Temperature Event EnableRead and write
High Remote Temperature Event Limit°CRead and write
Low Remote Temperature Event EnableRead and write
Low Remote Temperature Event Limit°CRead and write
High Supply Temperature Event EnableRead and write
High Supply Temperature Event Limit°CRead and write
Low Supply Temperature Event EnableRead and write
Low Supply Temperature Event Limit°CRead and write
High Return Humidity Event Enable (Relative)Read and write
High Return Humidity Event Limit (Relative)%Read and write
Low Return Humidity Event Enable (Relative)Read and write
Low Return Humidity Event Limit (Relative)%Read and write
High Remote Humidity Event Enable (Relative)Read and write
High Remote Humidity Event Limit (Relative)%Read and write
Low Remote Humidity Event Enable (Relative)Read and write
Low Remote Humidity Event Limit (Relative)%Read and write
High Return Humidity Event Limit (Absolute)g/kgRead and write
Low Return Humidity Event Limit (Absolute)g/kgRead and write
High Remote Humidity Event Limit (Absolute)g/kgRead and write
Low Remote Humidity Event Limit (Absolute)g/kgRead and write
High Return Dew Point Event Limit°CRead and write
Low Return Dew Point Event Limit°CRead and write
High Remote Dew Point Event Limit°CRead and write
Low Remote Dew Point Event Limit°CRead and write
Analog Output 1 SettingRead and write
Analog Output 2 SettingRead and write
Analog Output 3 SettingRead and write
Analog Output 4 SettingRead and write
Analog Output 5 SettingRead and write
Number of Return ProbesRead and write
Return Probes Control ModeRead and write
Number of Supply ProbesRead and write
Return Control ModeRead and write
Number of Remote ProbesRead and write
Remote Probes Control ModeRead and write
Number of Optional ProbesRead and write
Date DayRead and write
Date MonthRead and write
Date YearRead and write
Time HourRead and write
Time MinuteRead and write
Time SecondRead and write
Teamwork Total UnitsRead and write
Teamwork Standby UnitsRead and write
Teamwork ModeRead and write
CascadeRead and write
El Heater High Supply Temp Counter ResetRead and write
Condenser Emergency Mode DelaysRead and write
Condenser Emergency Mode Speed/Opening%Read and write
Condenser Emergency Mode EnableRead and write
Evaporating Fans Emergency Mode DelaysRead and write
Evaporating Fans Emergency Mode Speed%Read and write
Evaporating Fans Emergency Mode EnableRead and write
Air Economizer TypeRead and write
Stop Air Economizer on Clogged FilterRead and write
Air Economizer DT1 TypeRead and write
Air Economizer DT1 Room Ambient Temperature DifferenceKRead and write
Air Economizer DT3 Temperature EnableRead and write
Air Economizer DT3 Room Temperature/Setpoint DifferenceKRead and write
Air Economizer Reduced Economizer Airflow EnableRead and write
Air Economizer Emergency Override EnableRead and write
BMS Time-Out EnableRead and write
BMS TimeoutsRead and write
Static Pressure Events EnableRead and write
Low Static Pressure Event LimitPaRead and write
High Static Pressure Event LimitPaRead and write
Nominal Vol. Flow Rate (CW)l/sRead and write
BMS Temp. ControlRead and write
BMS Fan ControlRead and write
Backup Speed%Read and write
Backup Setpoint (Fan)°CRead and write
P-Band Switchback Thrs%Read and write
Fluid Eco DX+FCRead and write
Fluid Eco Lockout FC at°CRead and write
Fluid Eco Minimum Glycol EnableRead and write
Fluid Eco Minimum Glycol Temperature°CRead and write
Fluid Eco DT1 TypeRead and write
Fluid Eco DT1 ValueKRead and write
Fluid Eco DT2 TypeRead and write
Fluid Eco DT2 ValueKRead and write
Fluid Eco DT3 EnableRead and write
Fluid Eco DT3 ValueKRead and write
Nominal Vol. Flow Rate (Fluid Economizer)l/sRead and write
Nominal Vol. Flow Rate (Water Condenser)l/sRead and write
IR Flush Rate%Read and write
Monitoring System of MeasurementRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show return and supply temperature and humidity of every cooling unit in a server room on one ModbusCloud dashboard.
  • Send an email or webhook alert as soon as the generic alarm or a high temperature warning becomes active.
  • Keep 365 days of history of temperatures, fan speed and compressor requests to see how the cooling load develops.
  • Compare working hours of fans and compressors across units to plan maintenance.
  • Get a no data alert when the monitoring port of a unit stops answering.

Installation

  1. Connect the monitoring Ethernet port of the iCOM 3 to the network of the ModbusCloud Gateway, separate from the Teamwork network of the units.

  2. Give the monitoring port an address in that network through its web page; the default is 192.168.254.200.

  3. Check in the monitoring port that the V1A monitoring model is active and that Modbus TCP is on port 502.

  4. In ModbusCloud, add a Modbus TCP device with that IP address, port 502 and unit ID 1, and import this template.

  5. Check that return temperature and the generic alarm come in with sensible values.

Things to watch for

The unit does not answer on Modbus TCP. What should I check?

Make sure you use the monitoring Ethernet port and not the Teamwork port, that the IP address is in the same network as the gateway, and that a monitoring model is active in the monitoring port. Modbus TCP listens on port 502 with unit ID 1.

Why do temperatures look too high or wrong?

Values follow the unit system in the Monitoring System of Measurement register (address 417). With 1 (imperial) temperatures are in °F and pressures in psi. Set it to 0 for metric, which matches the units in this template.

Why are all registers one address off?

The Vertiv tables count from 1. This template uses the address in the Modbus message, which is the table number minus 1. If your other software shows 40001 for the first register, that is the same register.

Can I switch the unit on and off from ModbusCloud?

Yes, through the Unit On/Off command coil or the BMS on/off coil, once writing is enabled for your gateway. ModbusCloud turns writing on per gateway on request; by default the template only reads.

Want to see how it works?

Electrician working in an open distribution board