Ziehl-Abegg Ziehl-Abegg ECblue Modbus RTU template

Ziehl-Abegg ECblue

EC fan motor: speed, current, power, temperatures and faults, with speed control over RS485.

The Ziehl-Abegg ECblue is an EC external rotor motor that drives fans in air handling units, cooling and ventilation systems. This Modbus RTU template reads speed, current, power, temperatures and fault status, and lets you set the speed, control mode and speed limits from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
77, read and write
Key readings
Speed · Motor current · Motor input power · Modulation · DC link and line voltage · IGBT and inside temperature · Error status
Available commands
Enable and reverse · Speed setpoint · Control mode · Minimum and maximum speed · Internal speed setpoints · Communication watchdog
Compatible models
ECblue MODBUS · ECblue Basic · ECblue lite · Icontrol Basic with AM-MODBUS · Fcontrol Basic with AM-MODBUS
Last updated

Registers (77)

77 read, 29 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
SpeedrpmRead
Motor CurrentARead
Motor Input PowerWRead
Modulation%Read
DC Link VoltageVRead
Line VoltageVRead
IGBT Temperature°CRead
Inside Temperature°CRead
MCU Temperature°CRead
E1 InputRead
Operation Condition 1Read
Operation Condition 2Read
Error StatusRead
Error Status 2Read
EventRead
Event NumberRead
PIN Protection LevelRead
ControlRead and write
Speed ControlRead and write
PIN InputRead and write
COM ParameterRead and write
Control ModeRead and write
Set Intern1rpmRead and write
Set Intern2rpmRead and write
Min. SpeedrpmRead and write
Max. SpeedrpmRead and write
Set Intern3rpmRead and write
InvertingRead and write
E1 Min%Read and write
E1 Max%Read and write
E1 FunctionRead and write
D1 FunctionRead and write
K1 FunctionRead and write
Controller Setup FlagsRead and write
Communication WatchdogRead and write
Limit%Read and write
Radio Network CodeRead and write
Ramp TimingRead and write
Speed SuppressionRead and write
Range 1 MinrpmRead and write
Range 1 MaxrpmRead and write
Range 2 MinrpmRead and write
Range 2 MaxrpmRead and write
Range 3 MinrpmRead and write
Range 3 MaxrpmRead and write
Fan BadRead and write
Factory Setting h20Read
Factory Setting h21Read
Factory Setting h22Read
Factory Setting h23Read
Factory Setting h24Read
Factory Setting h26Read
Factory Setting h27Read
Factory Setting h28Read
Factory Setting h29Read
Factory Setting h38Read
Factory Setting h39Read
Factory Setting h40Read
Factory Setting h41Read
Factory Setting h42Read
Factory Setting h43Read
Factory Setting h44Read
Factory Setting h45Read
Factory Setting h46Read
Factory Setting h47Read
Factory Setting h48Read
Factory Setting h49Read
Firmware VersionRead
Product CodeRead
Parameter Set IDRead
Unique Device Signature 0Read
Unique Device Signature 1Read
Unique Device Signature 2Read
Unique Device Signature 3Read
Unique Device Signature 4Read
Unique Device Signature 5Read
Parameter Set IndexRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show speed, current and input power of every fan in an air handling unit on one ModbusCloud dashboard.
  • Send an email alert when the error status of a fan is no longer 0.
  • Track the IGBT and inside temperature over the summer to find fans that run hot.
  • Lower the speed setpoint of a fan remotely during the night or at low load.
  • Compare input power and speed in the history to spot a clogged filter or a worn bearing.

Installation

  1. Connect RS485 A and B of the ECblue to the RS485 port of the ModbusCloud Gateway and terminate the bus at both ends.

  2. Give every fan its own Modbus address in COM Parameter or with the Ziehl-Abegg setup tool; the factory address is 247.

  3. In ModbusCloud, add a Modbus RTU device with the fan address, 19200 baud, 8 data bits, even parity and 1 stop bit, and import this template.

  4. Check that Speed and Line Voltage show plausible values. Set Control Mode to bus control before you write a speed setpoint.

Things to watch for

The fan does not answer on the bus. What should I check?

Check the settings: 19200 baud, 8E1 and address 247 from the factory. Swap A and B if nothing answers, and terminate the bus at both ends. Several new fans all have address 247, so give each one its own address before you connect them together.

My write to a setting is ignored. Why?

Most settings need a PIN protection level. Write 1234 (level 1) or 0010 (level 2) to PIN Input first, then write the setting within about 15 minutes. Read the register before and after the write so you see whether the value was taken.

The fan ignores my speed setpoint.

Speed Control only works when Control Mode is set to bus control (mode 1, 2 or 3) and the fan is enabled, through D1 or through Control bit 0 with bus enable switched on in Control Mode. Also check Min. Speed and Max. Speed.

The fan runs at a fixed speed after a bus failure.

That is the communication watchdog. When it is on, the fan switches to a fault or a fixed speed after the set time without messages. Make sure the master writes often enough, or change the watchdog mode and time.

How do I read the temperatures correctly?

IGBT, inside and chip temperature are signed values in 0.1 °C steps, so 200 means 20.0 °C. The template applies this scale, so the values in ModbusCloud are already in °C.