Ziehl Ziehl EFR4001IP Modbus TCP template

Ziehl EFR4001IP

The Ziehl EFR4001IP is a three-phase energy flow relay and grid-point meter used in PV self-consumption and zero-export installations. It connects to your network via RJ45 and exposes all measurements over Modbus TCP. This ModbusCloud template reads per-phase voltage, current, active and reactive power, grid frequency, and cumulative import and export energy counters for all three phases. That data gives installers and asset managers continuous visibility of grid exchange and energy balance at the point of common coupling, without polling the device's built-in web server.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
23, read only
Brand
Ziehl
Last updated

Registers (23)

23 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
voltage_l1VRead176FC03uint32
voltage_l2VRead178FC03uint32
voltage_l3VRead180FC03uint32
current_l1ARead182FC03uint32
current_l2ARead184FC03uint32
current_l3ARead
active_power_l1WRead
active_power_l2WRead
active_power_l3WRead
active_powerWRead
reactive_power_l1WRead
reactive_power_l2WRead
reactive_power_l3WRead
reactive_powervarRead
frequencyHzRead
active_consumption_energy_l1WhRead
active_consumption_energy_l2WhRead
active_consumption_energy_l3WhRead
active_consumption_energyWhRead
active_production_energy_l1WhRead
active_production_energy_l2WhRead
active_production_energy_l3WhRead
active_production_energyWhRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Monitor total active power import and export in real time to verify zero-export compliance at the grid connection point.
  • Track cumulative active_production_energy and active_consumption_energy to calculate daily self-consumption ratios.
  • Alert on per-phase voltage imbalance across voltage_l1, voltage_l2, and voltage_l3 to detect supply quality problems.
  • Compare per-phase active power readings to identify single-phase load asymmetry in commercial or industrial sites.
  • Report grid frequency deviations via the frequency register to support power quality audits.

Installation

  1. Enable Modbus TCP on the EFR4001IP by logging into its integrated web server, navigating to the network or Modbus section, and activating the Modbus TCP protocol.

  2. Connect the EFR4001IP to the same Ethernet LAN as the ModbusCloud Gateway using a standard RJ45 patch cable, and note the device IP address.

  3. In the ModbusCloud portal, add a new device, select the Ziehl EFR4001IP template, enter the device IP address and port 502, and assign the correct Modbus unit ID.

  4. Spot-check the connection by confirming that voltage_l1 (address 176) returns a plausible phase voltage; if it reads zero, verify the Modbus TCP setting is saved and the device is reachable from the Gateway.

Things to watch for

Modbus TCP is enabled but the gateway returns no data. Why?

Modbus TCP on the EFR4001IP must be explicitly activated through its integrated web server; it is not on by default. Log in, confirm the Modbus TCP toggle is saved, then verify the device IP is reachable from the ModbusCloud Gateway on port 502. The device supports up to three simultaneous TCP connections.

Phase voltage registers read zero even though the meter is powered.

The EFR4001IP uses external current transformers for current measurement, but voltage is measured directly. If voltage_l1 through voltage_l3 read zero, check that the measurement input terminals are correctly wired and that the supply voltage is within the device's operating range. Also confirm the unit ID in your portal matches the device configuration.

Active power values have unexpected negative signs. Is this correct?

Yes. The EFR4001IP reports active power from the grid perspective: import (consumption) is positive and export (feed-in) is negative. This is by design. Registers active_power_l1 through active_power are signed int32, so negative values indicate the site is feeding energy back into the grid at that moment.

Cumulative energy registers for individual phases have no unit. What are they?

The per-phase energy registers (active_consumption_energy_l1 through active_production_energy_l3) carry no unit in this template. The total summation registers (active_consumption_energy and active_production_energy) are in Wh. Treat the per-phase registers as relative counters in the same Wh resolution and use the totals for absolute energy reporting.