ABB Emax 2 Ekip external modules
Breaker trip unit modules for communication, synchrocheck, signalling and digital inputs.
The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker that takes plug-in modules for fieldbus communication, selectivity, synchrocheck and signalling. This Modbus RTU template reads the status and firmware of each module and the synchrocheck measurements, and lets you set addresses, IP settings and thresholds from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 634, read and write
- Brand
- ABB
- Key readings
- Module status · Firmware versions · Synchrocheck voltages · Synchrocheck frequencies · Phase difference · Input polarities
- Available commands
- Bus address and speed · IP settings · Input filter times · Synchrocheck thresholds · Ekip Link actors
- Compatible models
- Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
- Last updated
Registers (634)
634 read, 199 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Modbus RTU Slave Address | Read and write | 5000 | FC03 / FC06 | uint16 | |
| Modbus RTU Baud Rate | Read and write | 5001 | FC03 / FC06 | uint16 | |
| Modbus RTU Protocol Type | Read and write | 5002 | FC03 / FC06 | uint16 | |
| Modbus RTU Flags | Read and write | 5003 | FC03 / FC06 | uint16 | |
| Modbus RTU Redundant Slave Address | Read and write | 5010 | FC03 / FC06 | uint16 | |
| Modbus RTU Redundant Baud Rate | Read and write | ||||
| Modbus RTU Redundant Protocol Type | Read and write | ||||
| Modbus RTU Redundant Flags | Read and write | ||||
| Modbus TCP Static IP address | Read and write | ||||
| Modbus TCP Static IP mask | Read and write | ||||
| Modbus TCP Static IP gateway address | Read and write | ||||
| Modbus TCP Flags | Read and write | ||||
| Modbus TCP SNTP Server | Read and write | ||||
| Modbus TCP Redundant Static IP address | Read and write | ||||
| Modbus TCP Redundant Static IP mask | Read and write | ||||
| Modbus TCP Redundant Static IP gateway address | Read and write | ||||
| Modbus TCP Redundant Flags | Read and write | ||||
| Modbus TCP Redundant SNTP Server | Read and write | ||||
| Free Module Parameters Free Reg 0 | °C | Read and write | |||
| Free Module Parameters Free Reg 1 | % | Read and write | |||
| Free Module Parameters Free Reg 2 | °C | Read and write | |||
| Free Module Parameters Free Reg 3 | % | Read and write | |||
| Free Module Parameters Free Reg 4 | Read and write | ||||
| EtherNet/IP Static IP address | Read and write | ||||
| EtherNet/IP Static IP mask | Read and write | ||||
| EtherNet/IP Static IP gateway address | Read and write | ||||
| EtherNet/IP Flags | Read and write | ||||
| EtherNet/IP SNTP Server | Read and write | ||||
| Profibus Slave Address | Read and write | ||||
| Profibus Flags | Read and write | ||||
| Profibus Redundant Slave Address | Read and write | ||||
| Profibus Redundant Flags | Read and write | ||||
| EtherNet/IP Redundant Static IP address | Read and write | ||||
| EtherNet/IP Redundant Static IP mask | Read and write | ||||
| EtherNet/IP Redundant Static IP gateway address | Read and write | ||||
| EtherNet/IP Redundant Flags | Read and write | ||||
| EtherNet/IP Redundant SNTP Server | Read and write | ||||
| Link 1 Actor[1] Ip Address | Read and write | ||||
| Link 1 Actor[2] Ip Address | Read and write | ||||
| Link 1 Actor[3] Ip Address | Read and write | ||||
| Link 1 Actor[4] Ip Address | Read and write | ||||
| Link 1 Actor[5] Ip Address | Read and write | ||||
| Link 1 Actor[6] Ip Address | Read and write | ||||
| Link 1 Actor[7] Ip Address | Read and write | ||||
| Link 1 Actor[8] Ip Address | Read and write | ||||
| Link 1 Actor[9] Ip Address | Read and write | ||||
| Link 1 Actor[10] Ip Address | Read and write | ||||
| Link 1 Actor[11] Ip Address | Read and write | ||||
| Link 1 Actor[12] Ip Address | Read and write | ||||
| Link 1 Actor[13] Ip Address | Read and write | ||||
| Link 1 Actor[14] Ip Address | Read and write | ||||
| Link 1 Actor[15] Ip Address | Read and write | ||||
| Link 1 SNTP Server | Read and write | ||||
| Link 1 Static IP address | Read and write | ||||
| Link 1 Static IP mask | Read and write | ||||
| Link 1 Static IP gateway address | Read and write | ||||
| Link 1 Flags | Read and write | ||||
| Link 2 Status word selectors for Actor A and B | Read and write | ||||
| Link 2 Status word selectors for Actor C and D | Read and write | ||||
| Link 2 Actor[1] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[1] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[1] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[2] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[2] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[2] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[3] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[3] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[3] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[4] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[4] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[4] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[5] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[5] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[5] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[6] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[6] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[6] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[7] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[7] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[7] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[8] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[8] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[8] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[9] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[9] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[9] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[10] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[10] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[10] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[11] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[11] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[11] G and Gext Selectivity | Read and write | ||||
| Link 2 Actor[12] S and S2 Selectivity | Read and write | ||||
| Link 2 Actor[12] D Backward and D Forward Selectivity | Read and write | ||||
| Link 2 Actor[12] G and Gext Selectivity | Read and write | ||||
| Link 2 Actors 1-4 functions selection | Read and write | ||||
| Link 2 Actors 5-8 functions selection | Read and write | ||||
| Link 2 Actors 9-12 functions selection | Read and write | ||||
| Link 2 Actors 13-15 functions selection | Read and write | ||||
| Link 2 Remote Programmable Status A - opcode 1 | Read and write | ||||
| Link 2 Remote Programmable Status A - opcode 2 | Read and write | ||||
| Link 2 Remote Programmable Status A - opcode 3 | Read and write | ||||
| Link 2 Remote Programmable Status B - opcode 1 | Read and write | ||||
| Link 2 Remote Programmable Status B - opcode 2 | Read and write | ||||
| Link 2 Remote Programmable Status B - opcode 3 | Read and write | ||||
| Link 2 Remote Programmable Status C - opcode 1 | Read and write | ||||
| Link 2 Remote Programmable Status C - opcode 2 | Read and write | ||||
| Link 2 Remote Programmable Status C - opcode 3 | Read and write | ||||
| Link 2 Remote Programmable Status D - opcode 1 | Read and write | ||||
| Link 2 Remote Programmable Status D - opcode 2 | Read and write | ||||
| Link 2 Remote Programmable Status D - opcode 3 | Read and write | ||||
| Link 2 Selectivity signal repeat configuration | Read and write | ||||
| Link 2 Remote Programmable status Actor selection | Read and write | ||||
| Link 2 Selectivity HW lines diagnostic selection - 1 | Read and write | ||||
| Link 2 Selectivity HW lines diagnostic selection - 2 | Read and write | ||||
| Link 2 Remote Status Actors Selectors | Read and write | ||||
| Ekip Synchrocheck Parameters Synchro Config | Read and write | ||||
| Ekip Synchrocheck Parameters delta V standard th | Read and write | ||||
| Ekip Synchrocheck Parameters V dead bar th | Read and write | ||||
| Ekip Synchrocheck Parameters V live threshold (standard) | Read and write | ||||
| Ekip Synchrocheck Parameters stability time | ms | Read and write | |||
| Ekip Synchrocheck Parameters delta frequency (1/10 Hz) | Hz | Read and write | |||
| Ekip Synchrocheck Parameters delta phase | Read and write | ||||
| Ekip Synchrocheck Parameters primary voltage | Read and write | ||||
| Ekip Synchrocheck Parameters secondary voltage | Read and write | ||||
| Ekip Synchrocheck Parameters match time | ms | Read and write | |||
| Ekip Synchrocheck Measures Concatenated Voltages x-y generator | V | Read | |||
| Ekip Synchrocheck Measures Concatenated Voltages x-y net side | V | Read | |||
| Ekip Synchrocheck Measures Concatenated Frequency x-y generator | Hz | Read | |||
| Ekip Synchrocheck Measures Concatenated Frequency x-y net side | Hz | Read | |||
| Ekip Synchrocheck Measures Concatenated phase difference x-y | Read | ||||
| DeviceNet MAC ID | Read and write | ||||
| DeviceNet Flags | Read and write | ||||
| Devicenet Redundant MAC ID | Read and write | ||||
| Devicenet Redundant Flags | Read and write | ||||
| Unnamed 5240 | Read and write | ||||
| Unnamed 5241 | Read and write | ||||
| Unnamed 5242 | Read and write | ||||
| Unnamed 5243 | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 2K-1 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-1.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-1.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 2K-2 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-2.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-2.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 2K-3 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-3.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 2K-3.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 10K-1 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.3 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.4 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.5 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.6 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.7 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.8 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.9 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.10 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-1.11 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 10K-2 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.3 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.4 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.5 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.6 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.7 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.8 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.9 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.10 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-2.11 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relays 10K-3 Input Polarities | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.1 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.2 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.3 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.4 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.5 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.6 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.7 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.8 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.9 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.10 Input Filter Time | Read and write | ||||
| Ekip 2K and 10K Inputs Relay 10K-3.11 Input Filter Time | Read and write | ||||
| 61850 Static IP address | Read and write | ||||
| 61850 Static IP mask | Read and write | ||||
| 61850 Static IP gateway address | Read and write | ||||
| 61850 Flags | Read and write | ||||
| 61850 SNTP Server | Read and write | ||||
| 61850 Redundant Static IP address | Read and write | ||||
| 61850 Redundant Static IP mask | Read and write | ||||
| 61850 Redundant Static IP gateway address | Read and write | ||||
| 61850 Redundant Flags | Read and write | ||||
| 61850 Redundant SNTP Server | Read and write | ||||
| Ekip Signalling 3T 1 Flags | Read and write | ||||
| Ekip Signalling 3T 2 Flags | Read and write | ||||
| YO/YC Test Unit 1 Coil Status | Read | ||||
| YO/YC Test Unit 1 Other Infos | Read | ||||
| YO/YC Test Unit 2 Coil Status | Read | ||||
| YO/YC Test Unit 2 Other Infos | Read | ||||
| YO/YC Test Unit 3 Coil Status | Read | ||||
| YO/YC Test Unit 3 Other Infos | Read | ||||
| YO/YC Test Unit 4 Coil Status | Read | ||||
| YO/YC Test Unit 4 Other Infos | Read | ||||
| Hub Static IP address | Read and write | ||||
| Hub Static IP mask | Read and write | ||||
| Hub Static IP gateway address | Read and write | ||||
| Hub Flags | Read and write | ||||
| Hub SNTP Server | Read and write | ||||
| Unnamed 5390 | Read and write | ||||
| Unnamed 5391 | Read and write | ||||
| Unnamed 5392 | Read and write | ||||
| Info DeviceNet Redundant SW Version | Read | ||||
| Info DeviceNet Redundant Module serial number | Read | ||||
| Info DeviceNet Redundant Boot SW Version | Read | ||||
| Info DeviceNet Redundant HW Version | Read | ||||
| Info DeviceNet Redundant Status | Read | ||||
| Info EtherNet/IP 32bit Module IP address | Read | ||||
| Info EtherNet/IP 32bit Module Network mask | Read | ||||
| Info EtherNet/IP 32bit Module gateway address | Read | ||||
| Info EtherNet/IP 32bit IEEE1588 Grand Master Clock IP address | Read | ||||
| Info Profinet Redundant SW Version | Read | ||||
| Info Profinet Redundant Module serial number | Read | ||||
| Info Profinet Redundant MAC Address Word 1 | Read | ||||
| Info Profinet Redundant MAC Address Word 2 | Read | ||||
| Info Profinet Redundant MAC Address Word 3 | Read | ||||
| Info Profinet Redundant Boot SW Version | Read | ||||
| Info Profinet Redundant HW Version | Read | ||||
| Info Profinet Redundant Module Status | Read | ||||
| Info Modbus RTU Redundant SW Version | Read | ||||
| Info Modbus RTU Redundant Module serial number | Read | ||||
| Info Modbus RTU Redundant Boot SW Version | Read | ||||
| Info Modbus RTU Redundant HW Version | Read | ||||
| Info Modbus RTU Redundant Module Status | Read | ||||
| Info EtherNet/IP Redundant 32bit Module IP address | Read | ||||
| Info EtherNet/IP Redundant 32bit Module Network mask | Read | ||||
| Info EtherNet/IP Redundant 32bit Module gateway address | Read | ||||
| Info EtherNet/IP Redundant 32bit IEEE1588 Grand Master Clock IP | Read | ||||
| Info Modbus TCP Redundant SW Version | Read | ||||
| Info Modbus TCP Redundant Module serial number | Read | ||||
| Info Modbus TCP Redundant MAC Address Word 1 | Read | ||||
| Info Modbus TCP Redundant MAC Address Word 2 | Read | ||||
| Info Modbus TCP Redundant MAC Address Word 3 | Read | ||||
| Info Modbus TCP Redundant Boot SW Version | Read | ||||
| Info Modbus TCP Redundant HW Version | Read | ||||
| Info Modbus TCP Redundant Module Status | Read | ||||
| Info Modbus TCP Redundant 32bit Module IP address | Read | ||||
| Info Modbus TCP Redundant 32bit Module Network mask | Read | ||||
| Info Modbus TCP Redundant 32bit Module gateway address | Read | ||||
| Info Modbus TCP Redundant 32bit Modbus TCP Client n.1 | Read | ||||
| Info Modbus TCP Redundant 32bit Modbus TCP Client n.2 | Read | ||||
| Info Modbus TCP Redundant 32bit Modbus TCP Client n.3 | Read | ||||
| Info Modbus TCP Redundant 32bit IEEE1588 Grand Master Clock IP | Read | ||||
| Info Profibus Redundant SW Version | Read | ||||
| Info Profibus Redundant Module serial number | Read | ||||
| Info Profibus Redundant Boot SW Version | Read | ||||
| Info Profibus Redundant HW Version | Read | ||||
| Info Profibus Redundant Module Status | Read | ||||
| Info Ekip Link SW Version | Read | ||||
| Info Ekip Link Module serial number | Read | ||||
| Info Ekip Link MAC Address Word 1 | Read | ||||
| Info Ekip Link MAC Address Word 2 | Read | ||||
| Info Ekip Link MAC Address Word 3 | Read | ||||
| Info Ekip Link Boot SW Version | Read | ||||
| Info Ekip Link HW Version | Read | ||||
| Info Ekip Link Module Status | Read | ||||
| Info Ekip Link 32bit Modbus TCP Client n.1 | Read | ||||
| Info Ekip Link 32bit Modbus TCP Client n.2 | Read | ||||
| Info Ekip Link 32bit Modbus TCP Client n.3 | Read | ||||
| Info Ekip Link 32bit Module IP address | Read | ||||
| Info Ekip Link 32bit Module Network mask | Read | ||||
| Info Ekip Link 32bit Module Gateway address | Read | ||||
| Info Ekip Link 32bit IEEE1588 Grand Master Clock IP address | Read | ||||
| Info Ekip Link Selectivity Test Report Selectivity Actors S | Read | ||||
| Info Ekip Link Selectivity Test Report Selectivity Actors G | Read | ||||
| Info Ekip Link Selectivity Test Report Selectivity Actors S/G | Read | ||||
| Info Modbus RTU SW Version | Read | ||||
| Info Modbus RTU Module serial number | Read | ||||
| Info Modbus RTU Boot SW Version | Read | ||||
| Info Modbus RTU HW Version | Read | ||||
| Info Modbus RTU Module Status | Read | ||||
| Info Modbus TCP SW Version | Read | ||||
| Info Modbus TCP Module serial number | Read | ||||
| Info Modbus TCP MAC Address Word 1 | Read | ||||
| Info Modbus TCP MAC Address Word 2 | Read | ||||
| Info Modbus TCP MAC Address Word 3 | Read | ||||
| Info Modbus TCP Boot SW Version | Read | ||||
| Info Modbus TCP HW Version | Read | ||||
| Info Modbus TCP Module Status | Read | ||||
| Info Modbus TCP 32bit Module IP address | Read | ||||
| Info Modbus TCP 32bit Module Network mask | Read | ||||
| Info Modbus TCP 32bit Module gateway address | Read | ||||
| Info Modbus TCP 32bit Modbus TCP Client n.1 | Read | ||||
| Info Modbus TCP 32bit Modbus TCP Client n.2 | Read | ||||
| Info Modbus TCP 32bit Modbus TCP Client n.3 | Read | ||||
| Info Modbus TCP 32bit IEEE1588 Grand Master Clock IP address | Read | ||||
| Info Profibus SW Version | Read | ||||
| Info Profibus Module serial number | Read | ||||
| Info Profibus Boot SW Version | Read | ||||
| Info Profibus HW Version | Read | ||||
| Info Profibus Module Status | Read | ||||
| Info 61850 32bit Module IP address | Read | ||||
| Info 61850 32bit Module Network mask | Read | ||||
| Info 61850 32bit Module gateway address | Read | ||||
| Info 61850 32bit IEEE1588 Grand Master Clock IP address | Read | ||||
| Info 61850 Redundant 32bit Module IP address | Read | ||||
| Info 61850 Redundant 32bit Module Network mask | Read | ||||
| Info 61850 Redundant 32bit Module gateway address | Read | ||||
| Info 61850 Redundant 32bit IEEE1588 Grand Master Clock IP | Read | ||||
| Info Ekip 2K-1 SW Version | Read | ||||
| Info Ekip 2K-1 Module serial number | Read | ||||
| Info Ekip 2K-1 Boot SW Version | Read | ||||
| Info Ekip 2K-1 HW Version | Read | ||||
| Info Ekip 2K-1 Module Status | Read | ||||
| Info Ekip 2K-2 SW Version | Read | ||||
| Info Ekip 2K-2 Module serial number | Read | ||||
| Info Ekip 2K-2 Boot SW Version | Read | ||||
| Info Ekip 2K-2 HW Version | Read | ||||
| Info Ekip 2K-2 Module Status | Read | ||||
| Info Ekip 2K-3 SW Version | Read | ||||
| Info Ekip 2K-3 Module serial number | Read | ||||
| Info Ekip 2K-3 Boot SW Version | Read | ||||
| Info Ekip 2K-3 HW Version | Read | ||||
| Info Ekip 2K-3 Module Status | Read | ||||
| Info Ekip Synchro SW Version | Read | ||||
| Info Ekip Synchro Module serial number | Read | ||||
| Info Ekip Synchro Boot SW Version | Read | ||||
| Info Ekip Synchro HW Version | Read | ||||
| Info Ekip Synchro Module Status | Read | ||||
| Info Unnamed 5788 | Read | ||||
| Info Unnamed 5789 Word 1 | Read | ||||
| Info Unnamed 5789 Word 2 | Read | ||||
| Info Unnamed 5789 Word 3 | Read | ||||
| Info Unnamed 5789 Word 4 | Read | ||||
| Info Unnamed 5789 Word 5 | Read | ||||
| Info Unnamed 5789 Word 6 | Read | ||||
| Info Unnamed 5789 Word 7 | Read | ||||
| Info Unnamed 5789 Word 8 | Read | ||||
| Info Unnamed 5797 | Read | ||||
| Info Unnamed 5798 | Read | ||||
| Info Unnamed 5799 | Read | ||||
| Info Unnamed 5800 | Read | ||||
| Info Unnamed 5802 | Read | ||||
| Info Unnamed 5804 | Read | ||||
| Info Unnamed 5806 | Read | ||||
| Info Unnamed 5808 | Read | ||||
| Info Unnamed 5810 | Read | ||||
| Info Unnamed 5812 | Read | ||||
| Info Unnamed 5814 | Read | ||||
| Info Unnamed 5816 | Read | ||||
| Info EtherNet/IP SW Version | Read | ||||
| Info EtherNet/IP Module serial number | Read | ||||
| Info EtherNet/IP MAC Address Word 1 | Read | ||||
| Info EtherNet/IP MAC Address Word 2 | Read | ||||
| Info EtherNet/IP MAC Address Word 3 | Read | ||||
| Info EtherNet/IP Boot SW Version | Read | ||||
| Info EtherNet/IP HW Version | Read | ||||
| Info EtherNet/IP Module Status | Read | ||||
| Info EtherNet/IP Redundant SW Version | Read | ||||
| Info EtherNet/IP Redundant Module serial number | Read | ||||
| Info EtherNet/IP Redundant MAC Address Word 1 | Read | ||||
| Info EtherNet/IP Redundant MAC Address Word 2 | Read | ||||
| Info EtherNet/IP Redundant MAC Address Word 3 | Read | ||||
| Info EtherNet/IP Redundant Boot SW Version | Read | ||||
| Info EtherNet/IP Redundant HW Version | Read | ||||
| Info EtherNet/IP Redundant Module Status | Read | ||||
| Info DeviceNet SW Version | Read | ||||
| Info DeviceNet Module serial number | Read | ||||
| Info DeviceNet Boot SW Version | Read | ||||
| Info DeviceNet HW Version | Read | ||||
| Info DeviceNet Status | Read | ||||
| Info Profinet SW Version | Read | ||||
| Info Profinet Module serial number | Read | ||||
| Info Profinet MAC Address Word 1 | Read | ||||
| Info Profinet MAC Address Word 2 | Read | ||||
| Info Profinet MAC Address Word 3 | Read | ||||
| Info Profinet Boot SW Version | Read | ||||
| Info Profinet HW Version | Read | ||||
| Info Profinet Module Status | Read | ||||
| Info Ekip 10K-1 SW Version | Read | ||||
| Info Ekip 10K-1 Module serial number | Read | ||||
| Info Ekip 10K-1 Boot SW Version | Read | ||||
| Info Ekip 10K-1 HW Version | Read | ||||
| Info Ekip 10K-1 Module Status | Read | ||||
| Info Ekip 10K-2 SW Version | Read | ||||
| Info Ekip 10K-2 Module serial number | Read | ||||
| Info Ekip 10K-2 Boot SW Version | Read | ||||
| Info Ekip 10K-2 HW Version | Read | ||||
| Info Ekip 10K-2 Module Status | Read | ||||
| Info Ekip 10K-3 SW Version | Read | ||||
| Info Ekip 10K-3 Module serial number | Read | ||||
| Info Ekip 10K-3 Boot SW Version | Read | ||||
| Info Ekip 10K-3 HW Version | Read | ||||
| Info Ekip 10K-3 Module Status | Read | ||||
| Info 61850 SW Version | Read | ||||
| Info 61850 Module serial number | Read | ||||
| Info 61850 MAC Address Word 1 | Read | ||||
| Info 61850 MAC Address Word 2 | Read | ||||
| Info 61850 MAC Address Word 3 | Read | ||||
| Info 61850 Boot SW Version | Read | ||||
| Info 61850 HW Version | Read | ||||
| Info 61850 Configuration File | Read | ||||
| Info 61850 Configuration File Error Code | Read | ||||
| Info 61850 Module Status | Read | ||||
| Info YO/YC Test Unit 1 SW Version | Read | ||||
| Info YO/YC Test Unit 1 Module serial number | Read | ||||
| Info YO/YC Test Unit 1 Boot SW Version | Read | ||||
| Info YO/YC Test Unit 1 HW Version | Read | ||||
| Info YO/YC Test Unit 1 Module Status | Read | ||||
| Info YO/YC Test Unit 2 SW Version | Read | ||||
| Info YO/YC Test Unit 2 Module serial number | Read | ||||
| Info YO/YC Test Unit 2 Boot SW Version | Read | ||||
| Info YO/YC Test Unit 2 HW Version | Read | ||||
| Info YO/YC Test Unit 2 Module Status | Read | ||||
| Info YO/YC Test Unit 3 SW Version | Read | ||||
| Info YO/YC Test Unit 3 Module serial number | Read | ||||
| Info YO/YC Test Unit 3 Boot SW Version | Read | ||||
| Info YO/YC Test Unit 3 HW Version | Read | ||||
| Info YO/YC Test Unit 3 Module Status | Read | ||||
| Info YO/YC Test Unit 4 SW Version | Read | ||||
| Info YO/YC Test Unit 4 Module serial number | Read | ||||
| Info YO/YC Test Unit 4 Boot SW Version | Read | ||||
| Info YO/YC Test Unit 4 HW Version | Read | ||||
| Info YO/YC Test Unit 4 Module Status | Read | ||||
| Info Ekip Multimeter 1 SW Version | Read | ||||
| Info Ekip Multimeter 1 Module serial number | Read | ||||
| Info Ekip Multimeter 1 Boot SW Version | Read | ||||
| Info Ekip Multimeter 1 HW Version | Read | ||||
| Info Ekip Multimeter 2 SW Version | Read | ||||
| Info Ekip Multimeter 2 Module serial number | Read | ||||
| Info Ekip Multimeter 2 Boot SW Version | Read | ||||
| Info Ekip Multimeter 2 HW Version | Read | ||||
| Info Ekip Multimeter 3 SW Version | Read | ||||
| Info Ekip Multimeter 3 Module serial number | Read | ||||
| Info Ekip Multimeter 3 Boot SW Version | Read | ||||
| Info Ekip Multimeter 3 HW Version | Read | ||||
| Info Ekip Multimeter 4 SW Version | Read | ||||
| Info Ekip Multimeter 4 Module serial number | Read | ||||
| Info Ekip Multimeter 4 Boot SW Version | Read | ||||
| Info Ekip Multimeter 4 HW Version | Read | ||||
| Info 61850 Redundant SW Version | Read | ||||
| Info 61850 Redundant Module serial number | Read | ||||
| Info 61850 Redundant MAC Address Word 1 | Read | ||||
| Info 61850 Redundant MAC Address Word 2 | Read | ||||
| Info 61850 Redundant MAC Address Word 3 | Read | ||||
| Info 61850 Redundant Boot SW Version | Read | ||||
| Info 61850 Redundant HW Version | Read | ||||
| Info 61850 Redundant Configuration File | Read | ||||
| Info 61850 Redundant Configuration File Error Code | Read | ||||
| Info 61850 Redundant Module Status | Read | ||||
| Info Hub 32bit Module IP address | Read | ||||
| Info Hub 32bit Module Network mask | Read | ||||
| Info Hub 32bit Module gateway address | Read | ||||
| Info Hub 32bit Modbus TCP Client n.1 | Read | ||||
| Info Hub 32bit Modbus TCP Client n.2 | Read | ||||
| Info Hub 32bit Modbus TCP Client n.3 | Read | ||||
| Info Hub SW Version | Read | ||||
| Info Hub Module serial number | Read | ||||
| Info Hub MAC Address Word 1 | Read | ||||
| Info Hub MAC Address Word 2 | Read | ||||
| Info Hub MAC Address Word 3 | Read | ||||
| Info Hub Boot SW Version | Read | ||||
| Info Hub HW Version | Read | ||||
| Info Hub Module Status | Read | ||||
| Info Hub Timestamp of Last Log - Seconds (Low) | Read | ||||
| Info Hub Timestamp of Last Log - Seconds (High) | Read | ||||
| Info Hub Timestamp of Last Upload - Seconds (Low) | Read | ||||
| Info Hub Timestamp of Last Upload - Seconds (High) | Read | ||||
| Info Hub Parser Error Code | Read | ||||
| Info Hub ConfiguredDevices | Read | ||||
| Info Hub Configured Sample Period | Read | ||||
| Info Hub Configured Log Period | Read | ||||
| Info Hub Configured Upload Period | Read | ||||
| Info Hub Measured Sample Time | Read | ||||
| Info Hub Max WD call rate | Read | ||||
| Info Hub Misconnected device | Read | ||||
| Info Hub Misconnection counter | Read | ||||
| Info Hub Configuration File | Read | ||||
| Info Hub Security File | Read | ||||
| Info Hub Resource occupation | Read | ||||
| Info Hub API events (Low) | Read | ||||
| Info Hub API events (High) | Read | ||||
| Info Hub Module Status 2 | Read | ||||
| Info Hub API UTC (Low) | Read | ||||
| Info Hub API UTC (High) | Read | ||||
| Info Hub Delta UTC (Low) | Read | ||||
| Info Hub Delta UTC (High) | Read | ||||
| Info Hub Post test data operation state | Read | ||||
| Info Hub Post data operation state | Read | ||||
| Info Hub Get renew operation state | Read | ||||
| Info Hub Get events operation state | Read | ||||
| Info Hub Get CRL operation state | Read | ||||
| Info Hub Certificate Revocation List file | Read | ||||
| Info Hub Get events test operation state | Read | ||||
| Info Hub Get FW operation state | Read | ||||
| Info Hub Executable file | Read | ||||
| Info Hub Retry Diagnostics | Read | ||||
| Info Hub API Device communication error detail | Read | ||||
| Info Hub Event Hub communication error detail | Read | ||||
| Info Hub Polling period API Events | Read | ||||
| Info Hub Client certificate file | Read | ||||
| Info Hub Client private key file | Read | ||||
| Info Hub Build version | Read | ||||
| Info Hub Module Status 3 | Read | ||||
| Info Hub Get gathering operation state | Read | ||||
| Info Ekip Signalling 3T 1 SW Version | Read | ||||
| Info Ekip Signalling 3T 1 Module serial number | Read | ||||
| Info Ekip Signalling 3T 1 Boot SW Version | Read | ||||
| Info Ekip Signalling 3T 1 HW Version | Read | ||||
| Info Ekip Signalling 3T 1 Temperature Sensor 1 Measure | °C | Read | |||
| Info Ekip Signalling 3T 1 Temperature Sensor 2 Measure | °C | Read | |||
| Info Ekip Signalling 3T 1 Temperature Sensor 3 Measure | °C | Read | |||
| Info Ekip Signalling 3T 1 Sensor 4-20mA | % | Read | |||
| Info Ekip Signalling 3T 1 Module Status | Read | ||||
| Info Ekip Signalling 3T 1 Accelerometer Axe X Measure | Read | ||||
| Info Ekip Signalling 3T 1 Accelerometer Axe Y Measure | Read | ||||
| Info Ekip Signalling 3T 1 Accelerometer Axe Z Measure | Read | ||||
| Info Ekip Signalling 3T 1 Humidity Sensor Measure | Read | ||||
| Info Ekip Signalling 3T 1 Internal Temperature Sensor Measure | Read | ||||
| Info Ekip Signalling 3T 1 Temperature Sensor 1 Measure °F | Read | ||||
| Info Ekip Signalling 3T 1 Temperature Sensor 2 Measure °F | Read | ||||
| Info Ekip Signalling 3T 1 Temperature Sensor 3 Measure °F | Read | ||||
| Info Ekip Signalling 3T 1 SW Subversion | Read | ||||
| Info Ekip Signalling 3T 1 Unnamed 7200 | Read | ||||
| Info Ekip Signalling 3T 2 SW Version | Read | ||||
| Info Ekip Signalling 3T 2 Module serial number | Read | ||||
| Info Ekip Signalling 3T 2 Boot SW Version | Read | ||||
| Info Ekip Signalling 3T 2 HW Version | Read | ||||
| Info Ekip Signalling 3T 2 Temperature Sensor 1 Measure | °C | Read | |||
| Info Ekip Signalling 3T 2 Temperature Sensor 2 Measure | °C | Read | |||
| Info Ekip Signalling 3T 2 Temperature Sensor 3 Measure | °C | Read | |||
| Info Ekip Signalling 3T 2 Sensor 4-20mA | % | Read | |||
| Info Ekip Signalling 3T 2 Module Status | Read | ||||
| Info Ekip Signalling 3T 2 Accelerometer Axe X Measure | Read | ||||
| Info Ekip Signalling 3T 2 Accelerometer Axe Y Measure | Read | ||||
| Info Ekip Signalling 3T 2 Accelerometer Axe Z Measure | Read | ||||
| Info Ekip Signalling 3T 2 Humidity Sensor Measure | Read | ||||
| Info Ekip Signalling 3T 2 Internal Temperature Sensor Measure | Read | ||||
| Info Ekip Signalling 3T 2 Temperature Sensor 1 Measure °F | Read | ||||
| Info Ekip Signalling 3T 2 Temperature Sensor 2 Measure °F | Read | ||||
| Info Ekip Signalling 3T 2 Temperature Sensor 3 Measure °F | Read | ||||
| Info Ekip Signalling 3T 2 SW Subversion | Read | ||||
| Info Ekip Signalling 3T 2 Unnamed 7235 | Read | ||||
| Info Unnamed 7250 | Read | ||||
| Info Unnamed 7251 Word 1 | Read | ||||
| Info Unnamed 7251 Word 2 | Read | ||||
| Info Unnamed 7251 Word 3 | Read | ||||
| Info Unnamed 7251 Word 4 | Read | ||||
| Info Unnamed 7251 Word 5 | Read | ||||
| Info Unnamed 7251 Word 6 | Read | ||||
| Info Unnamed 7251 Word 7 | Read | ||||
| Info Unnamed 7251 Word 8 | Read | ||||
| Info Unnamed 7259 | Read | ||||
| Info Unnamed 7260 | Read | ||||
| Info Unnamed 7261 | Read | ||||
| Info Unnamed 7262 | Read | ||||
| Info Unnamed 7263 | Read | ||||
| Info Unnamed 7264 | Read | ||||
| Info Profinet 32bit Module IP address | Read | ||||
| Info Profinet 32bit Module Network mask | Read | ||||
| Info Profinet 32bit Module Gateway address | Read | ||||
| Info Profinet 32bit Redundant Module IP address | Read | ||||
| Info Profinet 32bit Redundant Module Network mask | Read | ||||
| Info Profinet 32bit Redundant Module gateway address | Read | ||||
| Info Profinet DCP names 32bit DCP name | Read | ||||
| Info Profinet DCP names 32bit DCP name (Redundant module) | Read | ||||
| Info Unnamed 7400 | Read | ||||
| Info Unnamed 7401 Word 1 | Read | ||||
| Info Unnamed 7401 Word 2 | Read | ||||
| Info Unnamed 7401 Word 3 | Read | ||||
| Info Unnamed 7401 Word 4 | Read | ||||
| Info Unnamed 7401 Word 5 | Read | ||||
| Info Unnamed 7401 Word 6 | Read | ||||
| Info Unnamed 7401 Word 7 | Read | ||||
| Info Unnamed 7401 Word 8 | Read | ||||
| Info Unnamed 7409 | Read | ||||
| Info Unnamed 7410 | Read | ||||
| Info Unnamed 7411 | Read | ||||
| Info Unnamed 7412 | Read | ||||
| Info Unnamed 7413 | Read | ||||
| Info Unnamed 7414 | Read | ||||
| Info Unnamed 7415 | Read | ||||
| Info Unnamed 7416 | Read | ||||
| Info Unnamed 7417 | Read | ||||
| Info Unnamed 7418 | Read | ||||
| Info Unnamed 7419 | Read | ||||
| Info Unnamed 7420 | Read | ||||
| Info Unnamed 7421 | Read | ||||
| Info Unnamed 7422 | Read | ||||
| Info Unnamed 7423 | Read | ||||
| Info Unnamed 7424 | Read | ||||
| Info Unnamed 7425 | Read | ||||
| Info Unnamed 7450 | Read | ||||
| Info Unnamed 7451 Word 1 | Read | ||||
| Info Unnamed 7451 Word 2 | Read | ||||
| Info Unnamed 7451 Word 3 | Read | ||||
| Info Unnamed 7451 Word 4 | Read | ||||
| Info Unnamed 7451 Word 5 | Read | ||||
| Info Unnamed 7451 Word 6 | Read | ||||
| Info Unnamed 7451 Word 7 | Read | ||||
| Info Unnamed 7451 Word 8 | Read | ||||
| Info Unnamed 7459 | Read | ||||
| Info Unnamed 7460 | Read | ||||
| Info Unnamed 7461 | Read | ||||
| Info Unnamed 7462 | Read | ||||
| Info Unnamed 7463 | Read | ||||
| Info Unnamed 7464 | Read | ||||
| Info Unnamed 7465 | Read | ||||
| Info Unnamed 7466 | Read | ||||
| Info Unnamed 7467 | Read | ||||
| Info Unnamed 7468 | Read | ||||
| Info Unnamed 7469 | Read | ||||
| Info Unnamed 7470 | Read | ||||
| Info Unnamed 7471 | Read | ||||
| Info Unnamed 7472 | Read | ||||
| Info Unnamed 7473 | Read | ||||
| Info Unnamed 7474 | Read | ||||
| Info Unnamed 7475 | Read | ||||
| Info Unnamed 7480 | Read | ||||
| Info Unnamed 7481 Word 1 | Read | ||||
| Info Unnamed 7481 Word 2 | Read | ||||
| Info Unnamed 7481 Word 3 | Read | ||||
| Info Unnamed 7481 Word 4 | Read | ||||
| Info Unnamed 7481 Word 5 | Read | ||||
| Info Unnamed 7481 Word 6 | Read | ||||
| Info Unnamed 7481 Word 7 | Read | ||||
| Info Unnamed 7481 Word 8 | Read | ||||
| Info Unnamed 7489 Word 1 | Read | ||||
| Info Unnamed 7489 Word 2 | Read | ||||
| Info Unnamed 7489 Word 3 | Read | ||||
| Info Unnamed 7492 | Read | ||||
| Info Unnamed 7493 | Read | ||||
| Info Unnamed 7494 | Read | ||||
| Info Unnamed 7520 | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Check the firmware and status of every module in the terminal box from one dashboard before a site visit.
- Get an alarm when the status of a communication or Link module changes, so you know a module dropped out.
- Watch generator and net side voltage, frequency and phase difference while a synchrocheck closes two sources.
- Keep a year of module status history to find when a fieldbus module started reporting errors.
- Correct an IP address or input filter time from ModbusCloud after a change in the switchboard network.
Installation
Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and modules auxiliary supply.
Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.
Note address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).
In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.
Check that the status and firmware version of the installed modules come in.
Things to watch for
Why do the values of some modules always read zero?
Only installed modules return data. A module that is not in the terminal box, or not recognised by the trip unit, reads zero. Check the module list on the Ekip Touch display.
The module does not answer at all. What should I check?
Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even parity). Swap A and B if needed and terminate the bus at both ends.
How do I read an IP address from these registers?
IP addresses are one 32-bit value with the low word at the lower address. Each byte of the value is one part of the address. Check one known address, such as the static IP of the Modbus TCP module, against the display.
Can I change module settings from ModbusCloud?
Addresses, IP settings, filter times and thresholds are writable, but the trip unit only accepts them inside a programming session, opened and closed with commands in the core Emax 2 template. Changing the address or speed of the module you talk through cuts your own connection, so change those on site.
Want to see how it works?