ABB ABB Emax 2 Ekip external modules Modbus RTU template

ABB Emax 2 Ekip external modules

Breaker trip unit modules for communication, synchrocheck, signalling and digital inputs.

The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker that takes plug-in modules for fieldbus communication, selectivity, synchrocheck and signalling. This Modbus RTU template reads the status and firmware of each module and the synchrocheck measurements, and lets you set addresses, IP settings and thresholds from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
634, read and write
Brand
ABB
Key readings
Module status · Firmware versions · Synchrocheck voltages · Synchrocheck frequencies · Phase difference · Input polarities
Available commands
Bus address and speed · IP settings · Input filter times · Synchrocheck thresholds · Ekip Link actors
Compatible models
Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
Last updated

Registers (634)

634 read, 199 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Modbus RTU Slave AddressRead and write5000FC03 / FC06uint16
Modbus RTU Baud RateRead and write5001FC03 / FC06uint16
Modbus RTU Protocol TypeRead and write5002FC03 / FC06uint16
Modbus RTU FlagsRead and write5003FC03 / FC06uint16
Modbus RTU Redundant Slave AddressRead and write5010FC03 / FC06uint16
Modbus RTU Redundant Baud RateRead and write
Modbus RTU Redundant Protocol TypeRead and write
Modbus RTU Redundant FlagsRead and write
Modbus TCP Static IP addressRead and write
Modbus TCP Static IP maskRead and write
Modbus TCP Static IP gateway addressRead and write
Modbus TCP FlagsRead and write
Modbus TCP SNTP ServerRead and write
Modbus TCP Redundant Static IP addressRead and write
Modbus TCP Redundant Static IP maskRead and write
Modbus TCP Redundant Static IP gateway addressRead and write
Modbus TCP Redundant FlagsRead and write
Modbus TCP Redundant SNTP ServerRead and write
Free Module Parameters Free Reg 0°CRead and write
Free Module Parameters Free Reg 1%Read and write
Free Module Parameters Free Reg 2°CRead and write
Free Module Parameters Free Reg 3%Read and write
Free Module Parameters Free Reg 4Read and write
EtherNet/IP Static IP addressRead and write
EtherNet/IP Static IP maskRead and write
EtherNet/IP Static IP gateway addressRead and write
EtherNet/IP FlagsRead and write
EtherNet/IP SNTP ServerRead and write
Profibus Slave AddressRead and write
Profibus FlagsRead and write
Profibus Redundant Slave AddressRead and write
Profibus Redundant FlagsRead and write
EtherNet/IP Redundant Static IP addressRead and write
EtherNet/IP Redundant Static IP maskRead and write
EtherNet/IP Redundant Static IP gateway addressRead and write
EtherNet/IP Redundant FlagsRead and write
EtherNet/IP Redundant SNTP ServerRead and write
Link 1 Actor[1] Ip AddressRead and write
Link 1 Actor[2] Ip AddressRead and write
Link 1 Actor[3] Ip AddressRead and write
Link 1 Actor[4] Ip AddressRead and write
Link 1 Actor[5] Ip AddressRead and write
Link 1 Actor[6] Ip AddressRead and write
Link 1 Actor[7] Ip AddressRead and write
Link 1 Actor[8] Ip AddressRead and write
Link 1 Actor[9] Ip AddressRead and write
Link 1 Actor[10] Ip AddressRead and write
Link 1 Actor[11] Ip AddressRead and write
Link 1 Actor[12] Ip AddressRead and write
Link 1 Actor[13] Ip AddressRead and write
Link 1 Actor[14] Ip AddressRead and write
Link 1 Actor[15] Ip AddressRead and write
Link 1 SNTP ServerRead and write
Link 1 Static IP addressRead and write
Link 1 Static IP maskRead and write
Link 1 Static IP gateway addressRead and write
Link 1 FlagsRead and write
Link 2 Status word selectors for Actor A and BRead and write
Link 2 Status word selectors for Actor C and DRead and write
Link 2 Actor[1] S and S2 SelectivityRead and write
Link 2 Actor[1] D Backward and D Forward SelectivityRead and write
Link 2 Actor[1] G and Gext SelectivityRead and write
Link 2 Actor[2] S and S2 SelectivityRead and write
Link 2 Actor[2] D Backward and D Forward SelectivityRead and write
Link 2 Actor[2] G and Gext SelectivityRead and write
Link 2 Actor[3] S and S2 SelectivityRead and write
Link 2 Actor[3] D Backward and D Forward SelectivityRead and write
Link 2 Actor[3] G and Gext SelectivityRead and write
Link 2 Actor[4] S and S2 SelectivityRead and write
Link 2 Actor[4] D Backward and D Forward SelectivityRead and write
Link 2 Actor[4] G and Gext SelectivityRead and write
Link 2 Actor[5] S and S2 SelectivityRead and write
Link 2 Actor[5] D Backward and D Forward SelectivityRead and write
Link 2 Actor[5] G and Gext SelectivityRead and write
Link 2 Actor[6] S and S2 SelectivityRead and write
Link 2 Actor[6] D Backward and D Forward SelectivityRead and write
Link 2 Actor[6] G and Gext SelectivityRead and write
Link 2 Actor[7] S and S2 SelectivityRead and write
Link 2 Actor[7] D Backward and D Forward SelectivityRead and write
Link 2 Actor[7] G and Gext SelectivityRead and write
Link 2 Actor[8] S and S2 SelectivityRead and write
Link 2 Actor[8] D Backward and D Forward SelectivityRead and write
Link 2 Actor[8] G and Gext SelectivityRead and write
Link 2 Actor[9] S and S2 SelectivityRead and write
Link 2 Actor[9] D Backward and D Forward SelectivityRead and write
Link 2 Actor[9] G and Gext SelectivityRead and write
Link 2 Actor[10] S and S2 SelectivityRead and write
Link 2 Actor[10] D Backward and D Forward SelectivityRead and write
Link 2 Actor[10] G and Gext SelectivityRead and write
Link 2 Actor[11] S and S2 SelectivityRead and write
Link 2 Actor[11] D Backward and D Forward SelectivityRead and write
Link 2 Actor[11] G and Gext SelectivityRead and write
Link 2 Actor[12] S and S2 SelectivityRead and write
Link 2 Actor[12] D Backward and D Forward SelectivityRead and write
Link 2 Actor[12] G and Gext SelectivityRead and write
Link 2 Actors 1-4 functions selectionRead and write
Link 2 Actors 5-8 functions selectionRead and write
Link 2 Actors 9-12 functions selectionRead and write
Link 2 Actors 13-15 functions selectionRead and write
Link 2 Remote Programmable Status A - opcode 1Read and write
Link 2 Remote Programmable Status A - opcode 2Read and write
Link 2 Remote Programmable Status A - opcode 3Read and write
Link 2 Remote Programmable Status B - opcode 1Read and write
Link 2 Remote Programmable Status B - opcode 2Read and write
Link 2 Remote Programmable Status B - opcode 3Read and write
Link 2 Remote Programmable Status C - opcode 1Read and write
Link 2 Remote Programmable Status C - opcode 2Read and write
Link 2 Remote Programmable Status C - opcode 3Read and write
Link 2 Remote Programmable Status D - opcode 1Read and write
Link 2 Remote Programmable Status D - opcode 2Read and write
Link 2 Remote Programmable Status D - opcode 3Read and write
Link 2 Selectivity signal repeat configurationRead and write
Link 2 Remote Programmable status Actor selectionRead and write
Link 2 Selectivity HW lines diagnostic selection - 1Read and write
Link 2 Selectivity HW lines diagnostic selection - 2Read and write
Link 2 Remote Status Actors SelectorsRead and write
Ekip Synchrocheck Parameters Synchro ConfigRead and write
Ekip Synchrocheck Parameters delta V standard thRead and write
Ekip Synchrocheck Parameters V dead bar thRead and write
Ekip Synchrocheck Parameters V live threshold (standard)Read and write
Ekip Synchrocheck Parameters stability timemsRead and write
Ekip Synchrocheck Parameters delta frequency (1/10 Hz)HzRead and write
Ekip Synchrocheck Parameters delta phaseRead and write
Ekip Synchrocheck Parameters primary voltageRead and write
Ekip Synchrocheck Parameters secondary voltageRead and write
Ekip Synchrocheck Parameters match timemsRead and write
Ekip Synchrocheck Measures Concatenated Voltages x-y generatorVRead
Ekip Synchrocheck Measures Concatenated Voltages x-y net sideVRead
Ekip Synchrocheck Measures Concatenated Frequency x-y generatorHzRead
Ekip Synchrocheck Measures Concatenated Frequency x-y net sideHzRead
Ekip Synchrocheck Measures Concatenated phase difference x-yRead
DeviceNet MAC IDRead and write
DeviceNet FlagsRead and write
Devicenet Redundant MAC IDRead and write
Devicenet Redundant FlagsRead and write
Unnamed 5240Read and write
Unnamed 5241Read and write
Unnamed 5242Read and write
Unnamed 5243Read and write
Ekip 2K and 10K Inputs Relays 2K-1 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 2K-1.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 2K-1.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relays 2K-2 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 2K-2.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 2K-2.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relays 2K-3 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 2K-3.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 2K-3.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relays 10K-1 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 10K-1.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.3 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.4 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.5 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.6 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.7 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.8 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.9 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.10 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-1.11 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relays 10K-2 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 10K-2.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.3 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.4 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.5 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.6 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.7 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.8 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.9 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.10 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-2.11 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relays 10K-3 Input PolaritiesRead and write
Ekip 2K and 10K Inputs Relay 10K-3.1 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.2 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.3 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.4 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.5 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.6 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.7 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.8 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.9 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.10 Input Filter TimeRead and write
Ekip 2K and 10K Inputs Relay 10K-3.11 Input Filter TimeRead and write
61850 Static IP addressRead and write
61850 Static IP maskRead and write
61850 Static IP gateway addressRead and write
61850 FlagsRead and write
61850 SNTP ServerRead and write
61850 Redundant Static IP addressRead and write
61850 Redundant Static IP maskRead and write
61850 Redundant Static IP gateway addressRead and write
61850 Redundant FlagsRead and write
61850 Redundant SNTP ServerRead and write
Ekip Signalling 3T 1 FlagsRead and write
Ekip Signalling 3T 2 FlagsRead and write
YO/YC Test Unit 1 Coil StatusRead
YO/YC Test Unit 1 Other InfosRead
YO/YC Test Unit 2 Coil StatusRead
YO/YC Test Unit 2 Other InfosRead
YO/YC Test Unit 3 Coil StatusRead
YO/YC Test Unit 3 Other InfosRead
YO/YC Test Unit 4 Coil StatusRead
YO/YC Test Unit 4 Other InfosRead
Hub Static IP addressRead and write
Hub Static IP maskRead and write
Hub Static IP gateway addressRead and write
Hub FlagsRead and write
Hub SNTP ServerRead and write
Unnamed 5390Read and write
Unnamed 5391Read and write
Unnamed 5392Read and write
Info DeviceNet Redundant SW VersionRead
Info DeviceNet Redundant Module serial numberRead
Info DeviceNet Redundant Boot SW VersionRead
Info DeviceNet Redundant HW VersionRead
Info DeviceNet Redundant StatusRead
Info EtherNet/IP 32bit Module IP addressRead
Info EtherNet/IP 32bit Module Network maskRead
Info EtherNet/IP 32bit Module gateway addressRead
Info EtherNet/IP 32bit IEEE1588 Grand Master Clock IP addressRead
Info Profinet Redundant SW VersionRead
Info Profinet Redundant Module serial numberRead
Info Profinet Redundant MAC Address Word 1Read
Info Profinet Redundant MAC Address Word 2Read
Info Profinet Redundant MAC Address Word 3Read
Info Profinet Redundant Boot SW VersionRead
Info Profinet Redundant HW VersionRead
Info Profinet Redundant Module StatusRead
Info Modbus RTU Redundant SW VersionRead
Info Modbus RTU Redundant Module serial numberRead
Info Modbus RTU Redundant Boot SW VersionRead
Info Modbus RTU Redundant HW VersionRead
Info Modbus RTU Redundant Module StatusRead
Info EtherNet/IP Redundant 32bit Module IP addressRead
Info EtherNet/IP Redundant 32bit Module Network maskRead
Info EtherNet/IP Redundant 32bit Module gateway addressRead
Info EtherNet/IP Redundant 32bit IEEE1588 Grand Master Clock IPRead
Info Modbus TCP Redundant SW VersionRead
Info Modbus TCP Redundant Module serial numberRead
Info Modbus TCP Redundant MAC Address Word 1Read
Info Modbus TCP Redundant MAC Address Word 2Read
Info Modbus TCP Redundant MAC Address Word 3Read
Info Modbus TCP Redundant Boot SW VersionRead
Info Modbus TCP Redundant HW VersionRead
Info Modbus TCP Redundant Module StatusRead
Info Modbus TCP Redundant 32bit Module IP addressRead
Info Modbus TCP Redundant 32bit Module Network maskRead
Info Modbus TCP Redundant 32bit Module gateway addressRead
Info Modbus TCP Redundant 32bit Modbus TCP Client n.1Read
Info Modbus TCP Redundant 32bit Modbus TCP Client n.2Read
Info Modbus TCP Redundant 32bit Modbus TCP Client n.3Read
Info Modbus TCP Redundant 32bit IEEE1588 Grand Master Clock IPRead
Info Profibus Redundant SW VersionRead
Info Profibus Redundant Module serial numberRead
Info Profibus Redundant Boot SW VersionRead
Info Profibus Redundant HW VersionRead
Info Profibus Redundant Module StatusRead
Info Ekip Link SW VersionRead
Info Ekip Link Module serial numberRead
Info Ekip Link MAC Address Word 1Read
Info Ekip Link MAC Address Word 2Read
Info Ekip Link MAC Address Word 3Read
Info Ekip Link Boot SW VersionRead
Info Ekip Link HW VersionRead
Info Ekip Link Module StatusRead
Info Ekip Link 32bit Modbus TCP Client n.1Read
Info Ekip Link 32bit Modbus TCP Client n.2Read
Info Ekip Link 32bit Modbus TCP Client n.3Read
Info Ekip Link 32bit Module IP addressRead
Info Ekip Link 32bit Module Network maskRead
Info Ekip Link 32bit Module Gateway addressRead
Info Ekip Link 32bit IEEE1588 Grand Master Clock IP addressRead
Info Ekip Link Selectivity Test Report Selectivity Actors SRead
Info Ekip Link Selectivity Test Report Selectivity Actors GRead
Info Ekip Link Selectivity Test Report Selectivity Actors S/GRead
Info Modbus RTU SW VersionRead
Info Modbus RTU Module serial numberRead
Info Modbus RTU Boot SW VersionRead
Info Modbus RTU HW VersionRead
Info Modbus RTU Module StatusRead
Info Modbus TCP SW VersionRead
Info Modbus TCP Module serial numberRead
Info Modbus TCP MAC Address Word 1Read
Info Modbus TCP MAC Address Word 2Read
Info Modbus TCP MAC Address Word 3Read
Info Modbus TCP Boot SW VersionRead
Info Modbus TCP HW VersionRead
Info Modbus TCP Module StatusRead
Info Modbus TCP 32bit Module IP addressRead
Info Modbus TCP 32bit Module Network maskRead
Info Modbus TCP 32bit Module gateway addressRead
Info Modbus TCP 32bit Modbus TCP Client n.1Read
Info Modbus TCP 32bit Modbus TCP Client n.2Read
Info Modbus TCP 32bit Modbus TCP Client n.3Read
Info Modbus TCP 32bit IEEE1588 Grand Master Clock IP addressRead
Info Profibus SW VersionRead
Info Profibus Module serial numberRead
Info Profibus Boot SW VersionRead
Info Profibus HW VersionRead
Info Profibus Module StatusRead
Info 61850 32bit Module IP addressRead
Info 61850 32bit Module Network maskRead
Info 61850 32bit Module gateway addressRead
Info 61850 32bit IEEE1588 Grand Master Clock IP addressRead
Info 61850 Redundant 32bit Module IP addressRead
Info 61850 Redundant 32bit Module Network maskRead
Info 61850 Redundant 32bit Module gateway addressRead
Info 61850 Redundant 32bit IEEE1588 Grand Master Clock IPRead
Info Ekip 2K-1 SW VersionRead
Info Ekip 2K-1 Module serial numberRead
Info Ekip 2K-1 Boot SW VersionRead
Info Ekip 2K-1 HW VersionRead
Info Ekip 2K-1 Module StatusRead
Info Ekip 2K-2 SW VersionRead
Info Ekip 2K-2 Module serial numberRead
Info Ekip 2K-2 Boot SW VersionRead
Info Ekip 2K-2 HW VersionRead
Info Ekip 2K-2 Module StatusRead
Info Ekip 2K-3 SW VersionRead
Info Ekip 2K-3 Module serial numberRead
Info Ekip 2K-3 Boot SW VersionRead
Info Ekip 2K-3 HW VersionRead
Info Ekip 2K-3 Module StatusRead
Info Ekip Synchro SW VersionRead
Info Ekip Synchro Module serial numberRead
Info Ekip Synchro Boot SW VersionRead
Info Ekip Synchro HW VersionRead
Info Ekip Synchro Module StatusRead
Info Unnamed 5788Read
Info Unnamed 5789 Word 1Read
Info Unnamed 5789 Word 2Read
Info Unnamed 5789 Word 3Read
Info Unnamed 5789 Word 4Read
Info Unnamed 5789 Word 5Read
Info Unnamed 5789 Word 6Read
Info Unnamed 5789 Word 7Read
Info Unnamed 5789 Word 8Read
Info Unnamed 5797Read
Info Unnamed 5798Read
Info Unnamed 5799Read
Info Unnamed 5800Read
Info Unnamed 5802Read
Info Unnamed 5804Read
Info Unnamed 5806Read
Info Unnamed 5808Read
Info Unnamed 5810Read
Info Unnamed 5812Read
Info Unnamed 5814Read
Info Unnamed 5816Read
Info EtherNet/IP SW VersionRead
Info EtherNet/IP Module serial numberRead
Info EtherNet/IP MAC Address Word 1Read
Info EtherNet/IP MAC Address Word 2Read
Info EtherNet/IP MAC Address Word 3Read
Info EtherNet/IP Boot SW VersionRead
Info EtherNet/IP HW VersionRead
Info EtherNet/IP Module StatusRead
Info EtherNet/IP Redundant SW VersionRead
Info EtherNet/IP Redundant Module serial numberRead
Info EtherNet/IP Redundant MAC Address Word 1Read
Info EtherNet/IP Redundant MAC Address Word 2Read
Info EtherNet/IP Redundant MAC Address Word 3Read
Info EtherNet/IP Redundant Boot SW VersionRead
Info EtherNet/IP Redundant HW VersionRead
Info EtherNet/IP Redundant Module StatusRead
Info DeviceNet SW VersionRead
Info DeviceNet Module serial numberRead
Info DeviceNet Boot SW VersionRead
Info DeviceNet HW VersionRead
Info DeviceNet StatusRead
Info Profinet SW VersionRead
Info Profinet Module serial numberRead
Info Profinet MAC Address Word 1Read
Info Profinet MAC Address Word 2Read
Info Profinet MAC Address Word 3Read
Info Profinet Boot SW VersionRead
Info Profinet HW VersionRead
Info Profinet Module StatusRead
Info Ekip 10K-1 SW VersionRead
Info Ekip 10K-1 Module serial numberRead
Info Ekip 10K-1 Boot SW VersionRead
Info Ekip 10K-1 HW VersionRead
Info Ekip 10K-1 Module StatusRead
Info Ekip 10K-2 SW VersionRead
Info Ekip 10K-2 Module serial numberRead
Info Ekip 10K-2 Boot SW VersionRead
Info Ekip 10K-2 HW VersionRead
Info Ekip 10K-2 Module StatusRead
Info Ekip 10K-3 SW VersionRead
Info Ekip 10K-3 Module serial numberRead
Info Ekip 10K-3 Boot SW VersionRead
Info Ekip 10K-3 HW VersionRead
Info Ekip 10K-3 Module StatusRead
Info 61850 SW VersionRead
Info 61850 Module serial numberRead
Info 61850 MAC Address Word 1Read
Info 61850 MAC Address Word 2Read
Info 61850 MAC Address Word 3Read
Info 61850 Boot SW VersionRead
Info 61850 HW VersionRead
Info 61850 Configuration FileRead
Info 61850 Configuration File Error CodeRead
Info 61850 Module StatusRead
Info YO/YC Test Unit 1 SW VersionRead
Info YO/YC Test Unit 1 Module serial numberRead
Info YO/YC Test Unit 1 Boot SW VersionRead
Info YO/YC Test Unit 1 HW VersionRead
Info YO/YC Test Unit 1 Module StatusRead
Info YO/YC Test Unit 2 SW VersionRead
Info YO/YC Test Unit 2 Module serial numberRead
Info YO/YC Test Unit 2 Boot SW VersionRead
Info YO/YC Test Unit 2 HW VersionRead
Info YO/YC Test Unit 2 Module StatusRead
Info YO/YC Test Unit 3 SW VersionRead
Info YO/YC Test Unit 3 Module serial numberRead
Info YO/YC Test Unit 3 Boot SW VersionRead
Info YO/YC Test Unit 3 HW VersionRead
Info YO/YC Test Unit 3 Module StatusRead
Info YO/YC Test Unit 4 SW VersionRead
Info YO/YC Test Unit 4 Module serial numberRead
Info YO/YC Test Unit 4 Boot SW VersionRead
Info YO/YC Test Unit 4 HW VersionRead
Info YO/YC Test Unit 4 Module StatusRead
Info Ekip Multimeter 1 SW VersionRead
Info Ekip Multimeter 1 Module serial numberRead
Info Ekip Multimeter 1 Boot SW VersionRead
Info Ekip Multimeter 1 HW VersionRead
Info Ekip Multimeter 2 SW VersionRead
Info Ekip Multimeter 2 Module serial numberRead
Info Ekip Multimeter 2 Boot SW VersionRead
Info Ekip Multimeter 2 HW VersionRead
Info Ekip Multimeter 3 SW VersionRead
Info Ekip Multimeter 3 Module serial numberRead
Info Ekip Multimeter 3 Boot SW VersionRead
Info Ekip Multimeter 3 HW VersionRead
Info Ekip Multimeter 4 SW VersionRead
Info Ekip Multimeter 4 Module serial numberRead
Info Ekip Multimeter 4 Boot SW VersionRead
Info Ekip Multimeter 4 HW VersionRead
Info 61850 Redundant SW VersionRead
Info 61850 Redundant Module serial numberRead
Info 61850 Redundant MAC Address Word 1Read
Info 61850 Redundant MAC Address Word 2Read
Info 61850 Redundant MAC Address Word 3Read
Info 61850 Redundant Boot SW VersionRead
Info 61850 Redundant HW VersionRead
Info 61850 Redundant Configuration FileRead
Info 61850 Redundant Configuration File Error CodeRead
Info 61850 Redundant Module StatusRead
Info Hub 32bit Module IP addressRead
Info Hub 32bit Module Network maskRead
Info Hub 32bit Module gateway addressRead
Info Hub 32bit Modbus TCP Client n.1Read
Info Hub 32bit Modbus TCP Client n.2Read
Info Hub 32bit Modbus TCP Client n.3Read
Info Hub SW VersionRead
Info Hub Module serial numberRead
Info Hub MAC Address Word 1Read
Info Hub MAC Address Word 2Read
Info Hub MAC Address Word 3Read
Info Hub Boot SW VersionRead
Info Hub HW VersionRead
Info Hub Module StatusRead
Info Hub Timestamp of Last Log - Seconds (Low)Read
Info Hub Timestamp of Last Log - Seconds (High)Read
Info Hub Timestamp of Last Upload - Seconds (Low)Read
Info Hub Timestamp of Last Upload - Seconds (High)Read
Info Hub Parser Error CodeRead
Info Hub ConfiguredDevicesRead
Info Hub Configured Sample PeriodRead
Info Hub Configured Log PeriodRead
Info Hub Configured Upload PeriodRead
Info Hub Measured Sample TimeRead
Info Hub Max WD call rateRead
Info Hub Misconnected deviceRead
Info Hub Misconnection counterRead
Info Hub Configuration FileRead
Info Hub Security FileRead
Info Hub Resource occupationRead
Info Hub API events (Low)Read
Info Hub API events (High)Read
Info Hub Module Status 2Read
Info Hub API UTC (Low)Read
Info Hub API UTC (High)Read
Info Hub Delta UTC (Low)Read
Info Hub Delta UTC (High)Read
Info Hub Post test data operation stateRead
Info Hub Post data operation stateRead
Info Hub Get renew operation stateRead
Info Hub Get events operation stateRead
Info Hub Get CRL operation stateRead
Info Hub Certificate Revocation List fileRead
Info Hub Get events test operation stateRead
Info Hub Get FW operation stateRead
Info Hub Executable fileRead
Info Hub Retry DiagnosticsRead
Info Hub API Device communication error detailRead
Info Hub Event Hub communication error detailRead
Info Hub Polling period API EventsRead
Info Hub Client certificate fileRead
Info Hub Client private key fileRead
Info Hub Build versionRead
Info Hub Module Status 3Read
Info Hub Get gathering operation stateRead
Info Ekip Signalling 3T 1 SW VersionRead
Info Ekip Signalling 3T 1 Module serial numberRead
Info Ekip Signalling 3T 1 Boot SW VersionRead
Info Ekip Signalling 3T 1 HW VersionRead
Info Ekip Signalling 3T 1 Temperature Sensor 1 Measure°CRead
Info Ekip Signalling 3T 1 Temperature Sensor 2 Measure°CRead
Info Ekip Signalling 3T 1 Temperature Sensor 3 Measure°CRead
Info Ekip Signalling 3T 1 Sensor 4-20mA%Read
Info Ekip Signalling 3T 1 Module StatusRead
Info Ekip Signalling 3T 1 Accelerometer Axe X MeasureRead
Info Ekip Signalling 3T 1 Accelerometer Axe Y MeasureRead
Info Ekip Signalling 3T 1 Accelerometer Axe Z MeasureRead
Info Ekip Signalling 3T 1 Humidity Sensor MeasureRead
Info Ekip Signalling 3T 1 Internal Temperature Sensor MeasureRead
Info Ekip Signalling 3T 1 Temperature Sensor 1 Measure °FRead
Info Ekip Signalling 3T 1 Temperature Sensor 2 Measure °FRead
Info Ekip Signalling 3T 1 Temperature Sensor 3 Measure °FRead
Info Ekip Signalling 3T 1 SW SubversionRead
Info Ekip Signalling 3T 1 Unnamed 7200Read
Info Ekip Signalling 3T 2 SW VersionRead
Info Ekip Signalling 3T 2 Module serial numberRead
Info Ekip Signalling 3T 2 Boot SW VersionRead
Info Ekip Signalling 3T 2 HW VersionRead
Info Ekip Signalling 3T 2 Temperature Sensor 1 Measure°CRead
Info Ekip Signalling 3T 2 Temperature Sensor 2 Measure°CRead
Info Ekip Signalling 3T 2 Temperature Sensor 3 Measure°CRead
Info Ekip Signalling 3T 2 Sensor 4-20mA%Read
Info Ekip Signalling 3T 2 Module StatusRead
Info Ekip Signalling 3T 2 Accelerometer Axe X MeasureRead
Info Ekip Signalling 3T 2 Accelerometer Axe Y MeasureRead
Info Ekip Signalling 3T 2 Accelerometer Axe Z MeasureRead
Info Ekip Signalling 3T 2 Humidity Sensor MeasureRead
Info Ekip Signalling 3T 2 Internal Temperature Sensor MeasureRead
Info Ekip Signalling 3T 2 Temperature Sensor 1 Measure °FRead
Info Ekip Signalling 3T 2 Temperature Sensor 2 Measure °FRead
Info Ekip Signalling 3T 2 Temperature Sensor 3 Measure °FRead
Info Ekip Signalling 3T 2 SW SubversionRead
Info Ekip Signalling 3T 2 Unnamed 7235Read
Info Unnamed 7250Read
Info Unnamed 7251 Word 1Read
Info Unnamed 7251 Word 2Read
Info Unnamed 7251 Word 3Read
Info Unnamed 7251 Word 4Read
Info Unnamed 7251 Word 5Read
Info Unnamed 7251 Word 6Read
Info Unnamed 7251 Word 7Read
Info Unnamed 7251 Word 8Read
Info Unnamed 7259Read
Info Unnamed 7260Read
Info Unnamed 7261Read
Info Unnamed 7262Read
Info Unnamed 7263Read
Info Unnamed 7264Read
Info Profinet 32bit Module IP addressRead
Info Profinet 32bit Module Network maskRead
Info Profinet 32bit Module Gateway addressRead
Info Profinet 32bit Redundant Module IP addressRead
Info Profinet 32bit Redundant Module Network maskRead
Info Profinet 32bit Redundant Module gateway addressRead
Info Profinet DCP names 32bit DCP nameRead
Info Profinet DCP names 32bit DCP name (Redundant module)Read
Info Unnamed 7400Read
Info Unnamed 7401 Word 1Read
Info Unnamed 7401 Word 2Read
Info Unnamed 7401 Word 3Read
Info Unnamed 7401 Word 4Read
Info Unnamed 7401 Word 5Read
Info Unnamed 7401 Word 6Read
Info Unnamed 7401 Word 7Read
Info Unnamed 7401 Word 8Read
Info Unnamed 7409Read
Info Unnamed 7410Read
Info Unnamed 7411Read
Info Unnamed 7412Read
Info Unnamed 7413Read
Info Unnamed 7414Read
Info Unnamed 7415Read
Info Unnamed 7416Read
Info Unnamed 7417Read
Info Unnamed 7418Read
Info Unnamed 7419Read
Info Unnamed 7420Read
Info Unnamed 7421Read
Info Unnamed 7422Read
Info Unnamed 7423Read
Info Unnamed 7424Read
Info Unnamed 7425Read
Info Unnamed 7450Read
Info Unnamed 7451 Word 1Read
Info Unnamed 7451 Word 2Read
Info Unnamed 7451 Word 3Read
Info Unnamed 7451 Word 4Read
Info Unnamed 7451 Word 5Read
Info Unnamed 7451 Word 6Read
Info Unnamed 7451 Word 7Read
Info Unnamed 7451 Word 8Read
Info Unnamed 7459Read
Info Unnamed 7460Read
Info Unnamed 7461Read
Info Unnamed 7462Read
Info Unnamed 7463Read
Info Unnamed 7464Read
Info Unnamed 7465Read
Info Unnamed 7466Read
Info Unnamed 7467Read
Info Unnamed 7468Read
Info Unnamed 7469Read
Info Unnamed 7470Read
Info Unnamed 7471Read
Info Unnamed 7472Read
Info Unnamed 7473Read
Info Unnamed 7474Read
Info Unnamed 7475Read
Info Unnamed 7480Read
Info Unnamed 7481 Word 1Read
Info Unnamed 7481 Word 2Read
Info Unnamed 7481 Word 3Read
Info Unnamed 7481 Word 4Read
Info Unnamed 7481 Word 5Read
Info Unnamed 7481 Word 6Read
Info Unnamed 7481 Word 7Read
Info Unnamed 7481 Word 8Read
Info Unnamed 7489 Word 1Read
Info Unnamed 7489 Word 2Read
Info Unnamed 7489 Word 3Read
Info Unnamed 7492Read
Info Unnamed 7493Read
Info Unnamed 7494Read
Info Unnamed 7520Read

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Check the firmware and status of every module in the terminal box from one dashboard before a site visit.
  • Get an alarm when the status of a communication or Link module changes, so you know a module dropped out.
  • Watch generator and net side voltage, frequency and phase difference while a synchrocheck closes two sources.
  • Keep a year of module status history to find when a fieldbus module started reporting errors.
  • Correct an IP address or input filter time from ModbusCloud after a change in the switchboard network.

Installation

  1. Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and modules auxiliary supply.

  2. Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.

  3. Note address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).

  4. In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.

  5. Check that the status and firmware version of the installed modules come in.

Things to watch for

Why do the values of some modules always read zero?

Only installed modules return data. A module that is not in the terminal box, or not recognised by the trip unit, reads zero. Check the module list on the Ekip Touch display.

The module does not answer at all. What should I check?

Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even parity). Swap A and B if needed and terminate the bus at both ends.

How do I read an IP address from these registers?

IP addresses are one 32-bit value with the low word at the lower address. Each byte of the value is one part of the address. Check one known address, such as the static IP of the Modbus TCP module, against the display.

Can I change module settings from ModbusCloud?

Addresses, IP settings, filter times and thresholds are writable, but the trip unit only accepts them inside a programming session, opened and closed with commands in the core Emax 2 template. Changing the address or speed of the module you talk through cuts your own connection, so change those on site.

Want to see how it works?