ABB Emax 2 Ekip protection settings
Air circuit breaker trip unit with current, voltage, frequency and power protections in two setting sets.
The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker that protects a low voltage installation against overload, short circuit, earth fault and voltage, frequency and power faults. This Modbus RTU template reads the thresholds, trip times and enable flags of every protection in set A and set B, and lets you change them from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 519, read and write
- Brand
- ABB
- Key readings
- Overload threshold and time · Short circuit thresholds · Earth fault threshold · Voltage protection thresholds · Frequency protection thresholds · Protection enable flags
- Available commands
- Protection thresholds · Trip times · Curve types · Protection enable flags · Unit configuration
- Compatible models
- Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
- Last updated
Registers (519)
519 read, 519 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Config Time Zone settings | Read and write | 625 | FC03 / FC06 | uint16 | |
| Config Unit configuration 2 | Read and write | 626 | FC03 / FC06 | uint16 | |
| Config Unnamed 627 | Read and write | 627 | FC03 / FC06 | uint16 | |
| Config Tag name | Read and write | 628 | FC03 / FC16 | string | |
| Config User Data | Read and write | 633 | FC03 / FC16 | string | |
| Config StartUp Current Activation Threshold | Read and write | ||||
| Config Date Of CB Installation seconds low | s | Read and write | |||
| Config Date Of CB Installation seconds high | s | Read and write | |||
| Config Language | Read and write | ||||
| Config Neutral Selection | Read and write | ||||
| Config Unit configuration | Read and write | ||||
| Config External Toroid configuration | Read and write | ||||
| Config External Toroid size | Read and write | ||||
| Config Nominal voltage / TV Primary Voltage | Read and write | ||||
| Config TV Secondary Voltage | Read and write | ||||
| Config Net Frequency | Read and write | ||||
| Config Plant config | Read and write | ||||
| Config Monitor Time | Read and write | ||||
| Config CosΦ Module Threshold | Read and write | ||||
| Config Nominal voltage / TV Primary Voltage Un [V] | V | Read and write | |||
| Config TV Secondary Voltage [V] | V | Read and write | |||
| Config Open/Close CB Pulse Duration | ms | Read and write | |||
| Config MDGF In Size | A | Read and write | |||
| Config Unnamed 656 | Read and write | ||||
| Config Unnamed 657 | Read and write | ||||
| Set A L Configuration | Read and write | ||||
| Set A L Threshold l1 | Read and write | ||||
| Set A L Time t1 | s | Read and write | |||
| Set A L Curve Type | Read and write | ||||
| Set A L Threshold Iec255 | Read and write | ||||
| Set A L Time Iec255 | s | Read and write | |||
| Set A L Prealarm Threshold l1 | % | Read and write | |||
| Set A L TM Custom Time | s | Read and write | |||
| Set A S Configuration | Read and write | ||||
| Set A S Threshold I2 (I2t=k) | Read and write | ||||
| Set A S Time t2 (I2t=k) | s | Read and write | |||
| Set A S Threshold I2 (t=k) | Read and write | ||||
| Set A S Time t2 (t=k) | s | Read and write | |||
| Set A S Curve Type | Read and write | ||||
| Set A S Startup Threshold | Read and write | ||||
| Set A S Startup Time | s | Read and write | |||
| Set A S Zone Selectivity Time | s | Read and write | |||
| Set A I Configuration | Read and write | ||||
| Set A I Threshold I3 | Read and write | ||||
| Set A I Startup Threshold | Read and write | ||||
| Set A I Startup Time | s | Read and write | |||
| Set A G Configuration | Read and write | ||||
| Set A G Threshold I4 (I2t=k) | Read and write | ||||
| Set A G Time t4 (I2t=k) | s | Read and write | |||
| Set A G Threshold I4 (t=k) | Read and write | ||||
| Set A G Time t4 (t=k) | s | Read and write | |||
| Set A G Curve Type | Read and write | ||||
| Set A G Startup Threshold | Read and write | ||||
| Set A G Startup Time | s | Read and write | |||
| Set A G Zone Selectivity Time | s | Read and write | |||
| Set A S2 Configuration | Read and write | ||||
| Set A S2 Threshold I5 (t=k) | Read and write | ||||
| Set A S2 Time t5 t=k | s | Read and write | |||
| Set A S2 Startup Threshold | Read and write | ||||
| Set A S2 Startup Time | s | Read and write | |||
| Set A S2 Zone Selectivity Time | s | Read and write | |||
| Set A Gext Configuration | Read and write | ||||
| Set A Gext Threshold I41 (I2t=k) | Read and write | ||||
| Set A Gext Time t41 (I2t=k) | s | Read and write | |||
| Set A Gext Threshold I41 (t=k) | Read and write | ||||
| Set A Gext Time t41 (t=k) | s | Read and write | |||
| Set A Gext Curve Type | Read and write | ||||
| Set A Gext Startup Threshold | Read and write | ||||
| Set A Gext Startup Time | s | Read and write | |||
| Set A Gext Zone Selectivity Time | s | Read and write | |||
| Set A D Configuration | Read and write | ||||
| Set A D Threshold I7 Forward | Read and write | ||||
| Set A D Time t7 Forward | s | Read and write | |||
| Set A D Time t7 Backward | s | Read and write | |||
| Set A D Startup Threshold Forward | Read and write | ||||
| Set A D Startup Time | s | Read and write | |||
| Set A D Zone Selectivity Time Forward | s | Read and write | |||
| Set A D Direction Minimum Angle | Read and write | ||||
| Set A IU Configuration | Read and write | ||||
| Set A IU Threshold I6 | Read and write | ||||
| Set A IU Time t6 | s | Read and write | |||
| Set A UV Configuration | Read and write | ||||
| Set A UV Threshold U8 | Read and write | ||||
| Set A UV Time t8 | s | Read and write | |||
| Set A Voltage Stability Configuration | Read and write | ||||
| Set A Voltage Stability Threshold Down | Read and write | ||||
| Set A Voltage Stability Threshold Up | Read and write | ||||
| Set A Voltage Stability Time | s | Read and write | |||
| Set A OV Configuration | Read and write | ||||
| Set A OV Threshold U9 | Read and write | ||||
| Set A OV Time t9 | s | Read and write | |||
| Set A Unnamed 795 | Read and write | ||||
| Set A Unnamed 796 | Read and write | ||||
| Set A Unnamed 797 | s | Read and write | |||
| Set A RV Configuration | Read and write | ||||
| Set A RV Threshold U22 | Read and write | ||||
| Set A RV Time t22 | s | Read and write | |||
| Set A RV Reset Time | s | Read and write | |||
| Set A RP Configuration | Read and write | ||||
| Set A RP Threshold P11 | Read and write | ||||
| Set A RP Time t11 | s | Read and write | |||
| Set A UF Configuration | Read and write | ||||
| Set A UF Threshold f12 | Read and write | ||||
| Set A UF Time t12 | s | Read and write | |||
| Set A Frequency Stability Configuration | Read and write | ||||
| Set A Frequency Stability Threshold Down | Read and write | ||||
| Set A Frequency Stability Threshold Up | Read and write | ||||
| Set A Frequency Stability Time | s | Read and write | |||
| Set A OF Configuration | Read and write | ||||
| Set A OF Threshold f13 | Read and write | ||||
| Set A OF Time t13 | s | Read and write | |||
| Set A T Configuration | Read and write | ||||
| Set A Unnamed 845 | Read and write | ||||
| Set A Unnamed 846 | Read and write | ||||
| Set A Unnamed 847 | Read and write | ||||
| Set A Rc Configuration | Read and write | ||||
| Set A Rc Idn | Read and write | ||||
| Set A Rc tdn | Read and write | ||||
| Set A LC IW Configuration | Read and write | ||||
| Set A LC IW Iw1 Threshold | Read and write | ||||
| Set A LC IW Iw2 Threshold | Read and write | ||||
| Set A LC IW LC1 Threshold | Read and write | ||||
| Set A LC IW LC2 Threshold | Read and write | ||||
| Set A MCR Configuration | Read and write | ||||
| Set A MCR I3 | Read and write | ||||
| Set A MCR Monitor Time | s | Read and write | |||
| Set A VU Configuration | Read and write | ||||
| Set A VU Threshold U14 | Read and write | ||||
| Set A VU Time t14 | s | Read and write | |||
| Set A OP Configuration | Read and write | ||||
| Set A OP Threshold P26 | Read and write | ||||
| Set A OP Time t26 | s | Read and write | |||
| Set A S(V) Configuration | Read and write | ||||
| Set A S(V) Type | Read and write | ||||
| Set A S(V) Threshold I20 | Read and write | ||||
| Set A S(V) Time t20 | s | Read and write | |||
| Set A S(V) Threshold Uh (linear mode) | V | Read and write | |||
| Set A S(V) Threshold UI (linear mode) | V | Read and write | |||
| Set A S(V) Threshold UI (step mode) | V | Read and write | |||
| Set A S(V) Threshold Ks | Read and write | ||||
| Set A RQ Configuration | Read and write | ||||
| Set A RQ Threshold Kq | Read and write | ||||
| Set A RQ Threshold -Q24 | Read and write | ||||
| Set A RQ Threshold Kq2 | Read and write | ||||
| Set A RQ Threshold -Q25 | Read and write | ||||
| Set A RQ Time t24 | s | Read and write | |||
| Set A RQ Threshold V min | Read and write | ||||
| Set A ROCOF Configuration | Read and write | ||||
| Set A ROCOF Threshold f28 | Hz | Read and write | |||
| Set A ROCOF Trip Direction | Read and write | ||||
| Set A ROCOF Time t28 | s | Read and write | |||
| Set A S2(V) Configuration | Read and write | ||||
| Set A S2(V) Type | Read and write | ||||
| Set A S2(V) Threshold I21 | Read and write | ||||
| Set A S2(V) Time t21 | s | Read and write | |||
| Set A S2(V) Threshold Uh2 (linear mode) | V | Read and write | |||
| Set A S2(V) Threshold UI2 (linear mode) | V | Read and write | |||
| Set A S2(V) Threshold UI2 (step mode) | V | Read and write | |||
| Set A S2(V) Threshold Ks2 | Read and write | ||||
| Set A OQ Configuration | Read and write | ||||
| Set A OQ Threshold Q27 | Read and write | ||||
| Set A OQ Time t27 | Read and write | ||||
| Set A UP Configuration | Read and write | ||||
| Set A UP Threshold P23 | Read and write | ||||
| Set A UP Time t23 | s | Read and write | |||
| Set A UP StartUp Time | s | Read and write | |||
| Set A UV 2 Configuration | Read and write | ||||
| Set A UV 2 Threshold U15 | Read and write | ||||
| Set A UV 2 Time t15 | s | Read and write | |||
| Set A OV 2 Configuration | Read and write | ||||
| Set A OV 2 Threshold U16 | Read and write | ||||
| Set A OV 2 Time t16 | s | Read and write | |||
| Set A UF 2 Configuration | Read and write | ||||
| Set A UF 2 Threshold f17 | Read and write | ||||
| Set A UF 2 Time t17 | s | Read and write | |||
| Set A OF 2 Configuration | Read and write | ||||
| Set A OF 2 Threshold f18 | Read and write | ||||
| Set A OF 2 Time t18 | s | Read and write | |||
| Set A D Advanced Threshold Backward | Read and write | ||||
| Set A D Advanced Startup Threshold Backward | Read and write | ||||
| Set A D Advanced Zone Selectivity Time Backward | s | Read and write | |||
| Set A G Advanced Prealarm Threshold | % | Read and write | |||
| Set A G Advanced Unnamed 1011 | A | Read and write | |||
| Set A G Advanced Unnamed 1012 | A | Read and write | |||
| Set A G Advanced Unnamed 1013 | A | Read and write | |||
| Set A Gext Advanced Prealarm Threshold | % | Read and write | |||
| Set A 2I Configuration | Read and write | ||||
| Set A 2I Threshold I31 | % | Read and write | |||
| Set A Unnamed 1040 | Read and write | ||||
| Set A Unnamed 1041 | Read and write | ||||
| Set A Unnamed 1045 | Read and write | ||||
| Set A Unnamed 1046 | Read and write | ||||
| Set B L Configuration | Read and write | ||||
| Set B L Threshold l1 | Read and write | ||||
| Set B L Time t1 | s | Read and write | |||
| Set B L Curve Type | Read and write | ||||
| Set B L Threshold Iec255 | Read and write | ||||
| Set B L Time Iec255 | s | Read and write | |||
| Set B L Prealarm Threshold l1 | % | Read and write | |||
| Set B L TM Custom Time | s | Read and write | |||
| Set B S Configuration | Read and write | ||||
| Set B S Threshold I2 (I2t=k) | Read and write | ||||
| Set B S Time t2 (I2t=k) | s | Read and write | |||
| Set B S Threshold I2 (t=k) | Read and write | ||||
| Set B S Time t2 (t=k) | s | Read and write | |||
| Set B S Curve Type | Read and write | ||||
| Set B S Startup Threshold | Read and write | ||||
| Set B S Startup Time | s | Read and write | |||
| Set B S Zone Selectivity Time | s | Read and write | |||
| Set B I Configuration | Read and write | ||||
| Set B I Threshold I3 | Read and write | ||||
| Set B I Startup Threshold | Read and write | ||||
| Set B I Startup Time | s | Read and write | |||
| Set B G Configuration | Read and write | ||||
| Set B G Threshold I4 (I2t=k) | Read and write | ||||
| Set B G Time t4 (I2t=k) | s | Read and write | |||
| Set B G Threshold I4 (t=k) | Read and write | ||||
| Set B G Time t4 (t=k) | s | Read and write | |||
| Set B G Curve Type | Read and write | ||||
| Set B G Startup Threshold | Read and write | ||||
| Set B G Startup Time | s | Read and write | |||
| Set B G Zone Selectivity Time | s | Read and write | |||
| Set B S2 Configuration | Read and write | ||||
| Set B S2 Threshold I5 (t=k) | Read and write | ||||
| Set B S2 Time t5 t=k | s | Read and write | |||
| Set B S2 Startup Threshold | Read and write | ||||
| Set B S2 Startup Time | s | Read and write | |||
| Set B S2 Zone Selectivity Time | s | Read and write | |||
| Set B Gext Configuration | Read and write | ||||
| Set B Gext Threshold I41 (I2t=k) | Read and write | ||||
| Set B Gext Time t41 (I2t=k) | s | Read and write | |||
| Set B Gext Threshold I41 (t=k) | Read and write | ||||
| Set B Gext Time t41 (t=k) | s | Read and write | |||
| Set B Gext Curve Type | Read and write | ||||
| Set B Gext Startup Threshold | Read and write | ||||
| Set B Gext Startup Time | s | Read and write | |||
| Set B Gext Zone Selectivity Time | s | Read and write | |||
| Set B D Configuration | Read and write | ||||
| Set B D Threshold I7 Forward | Read and write | ||||
| Set B D Time t7 Forward | s | Read and write | |||
| Set B D Time t7 Backward | s | Read and write | |||
| Set B D Startup Threshold Forward | Read and write | ||||
| Set B D Startup Time | s | Read and write | |||
| Set B D Zone Selectivity Time Forward | s | Read and write | |||
| Set B D Direction Minimum Angle | Read and write | ||||
| Set B IU Configuration | Read and write | ||||
| Set B IU Threshold I6 | Read and write | ||||
| Set B IU Time t6 | s | Read and write | |||
| Set B UV Configuration | Read and write | ||||
| Set B UV Threshold U8 | Read and write | ||||
| Set B UV Time t8 | s | Read and write | |||
| Set B Voltage Stability Configuration | Read and write | ||||
| Set B Voltage Stability Threshold Down | Read and write | ||||
| Set B Voltage Stability Threshold Up | Read and write | ||||
| Set B Voltage Stability Time | s | Read and write | |||
| Set B OV Configuration | Read and write | ||||
| Set B OV Threshold U9 | Read and write | ||||
| Set B OV Time t9 | s | Read and write | |||
| Set B Unnamed 1245 | Read and write | ||||
| Set B Unnamed 1246 | Read and write | ||||
| Set B Unnamed 1247 | s | Read and write | |||
| Set B RV Configuration | Read and write | ||||
| Set B RV Threshold U22 | Read and write | ||||
| Set B RV Time t22 | s | Read and write | |||
| Set B RV Reset Time | s | Read and write | |||
| Set B RP Configuration | Read and write | ||||
| Set B RP Threshold P11 | Read and write | ||||
| Set B RP Time t11 | s | Read and write | |||
| Set B UF Configuration | Read and write | ||||
| Set B UF Threshold f12 | Read and write | ||||
| Set B UF Time t12 | s | Read and write | |||
| Set B Frequency Stability Configuration | Read and write | ||||
| Set B Frequency Stability Threshold Down | Read and write | ||||
| Set B Frequency Stability Threshold Up | Read and write | ||||
| Set B Frequency Stability Time | s | Read and write | |||
| Set B OF Configuration | Read and write | ||||
| Set B OF Threshold f13 | Read and write | ||||
| Set B OF Time t13 | s | Read and write | |||
| Set B Configuration | Read and write | ||||
| Set B Unnamed 1295 | Read and write | ||||
| Set B Unnamed 1296 | Read and write | ||||
| Set B Unnamed 1297 | Read and write | ||||
| Set B Rc Configuration | Read and write | ||||
| Set B Rc Idn | Read and write | ||||
| Set B Rc tdn | Read and write | ||||
| Set B LC IW Configuration | Read and write | ||||
| Set B LC IW Iw1 Threshold | Read and write | ||||
| Set B LC IW Iw2 Threshold | Read and write | ||||
| Set B LC IW LC1 Threshold | Read and write | ||||
| Set B LC IW LC2 Threshold | Read and write | ||||
| Set B Configuration 1320 | Read and write | ||||
| Set B I3 | Read and write | ||||
| Set B Monitor Time | s | Read and write | |||
| Set B VU Configuration | Read and write | ||||
| Set B VU Threshold U14 | Read and write | ||||
| Set B VU Time t14 | s | Read and write | |||
| Set B OP Configuration | Read and write | ||||
| Set B OP Threshold P26 | Read and write | ||||
| Set B OP Time t26 | s | Read and write | |||
| Set B S(V) Configuration | Read and write | ||||
| Set B S(V) Type | Read and write | ||||
| Set B S(V) Threshold I20 | Read and write | ||||
| Set B S(V) Time t20 | s | Read and write | |||
| Set B S(V) Threshold Uh (linear mode) | V | Read and write | |||
| Set B S(V) Threshold UI (linear mode) | V | Read and write | |||
| Set B S(V) Threshold UI (step mode) | V | Read and write | |||
| Set B S(V) Threshold Ks | Read and write | ||||
| Set B RQ Configuration | Read and write | ||||
| Set B RQ Threshold Kq | Read and write | ||||
| Set B RQ Threshold -Q24 | Read and write | ||||
| Set B RQ Threshold Kq2 | Read and write | ||||
| Set B RQ Threshold -Q25 | Read and write | ||||
| Set B RQ Time t24 | s | Read and write | |||
| Set B RQ Threshold V min | Read and write | ||||
| Set B ROCOF Configuration | Read and write | ||||
| Set B ROCOF Threshold f28 | Hz | Read and write | |||
| Set B ROCOF Trip Direction | Read and write | ||||
| Set B ROCOF Time t28 | s | Read and write | |||
| Set B S2(V) Configuration | Read and write | ||||
| Set B S2(V) Type | Read and write | ||||
| Set B S2(V) Threshold I21 | Read and write | ||||
| Set B S2(V) Time t21 | s | Read and write | |||
| Set B S2(V) Threshold Uh2 (linear mode) | V | Read and write | |||
| Set B S2(V) Threshold UI2 (linear mode) | V | Read and write | |||
| Set B S2(V) Threshold UI2 (step mode) | V | Read and write | |||
| Set B S2(V) Threshold Ks2 | Read and write | ||||
| Set B OQ Configuration | Read and write | ||||
| Set B OQ Threshold Q27 | Read and write | ||||
| Set B OQ Time t27 | Read and write | ||||
| Set B UP Configuration | Read and write | ||||
| Set B UP Threshold P23 | Read and write | ||||
| Set B UP Time t23 | s | Read and write | |||
| Set B UP StartUp Time | s | Read and write | |||
| Set B UV 2 Configuration | Read and write | ||||
| Set B UV 2 Threshold U15 | Read and write | ||||
| Set B UV 2 Time t15 | s | Read and write | |||
| Set B OV 2 Configuration | Read and write | ||||
| Set B OV 2 Threshold U16 | Read and write | ||||
| Set B OV 2 Time t16 | s | Read and write | |||
| Set B UF 2 Configuration | Read and write | ||||
| Set B UF 2 Threshold f17 | Read and write | ||||
| Set B UF 2 Time t17 | s | Read and write | |||
| Set B OF 2 Configuration | Read and write | ||||
| Set B OF 2 Threshold f18 | Read and write | ||||
| Set B OF 2 Time t18 | s | Read and write | |||
| Set B D Advanced Threshold Backward | Read and write | ||||
| Set B D Advanced Startup Threshold Backward | Read and write | ||||
| Set B D Advanced Zone Selectivity Time Backward | s | Read and write | |||
| Set B G Advanced Prealarm Threshold | % | Read and write | |||
| Set B G Advanced Unnamed 1461 | A | Read and write | |||
| Set B G Advanced Unnamed 1462 | A | Read and write | |||
| Set B G Advanced Unnamed 1463 | A | Read and write | |||
| Set B Gext Advanced Prealarm Threshold | % | Read and write | |||
| Set B 2I Configuration | Read and write | ||||
| Set B 2I Threshold I31 | % | Read and write | |||
| Set B Unnamed 1490 | Read and write | ||||
| Set B Unnamed 1491 | Read and write | ||||
| Set B Unnamed 1495 | Read and write | ||||
| Set B Unnamed 1496 | Read and write | ||||
| Set A Unnamed 8630 | Read and write | ||||
| Set A Unnamed 8631 | Read and write | ||||
| Set A Unnamed 8632 | Read and write | ||||
| Set A Unnamed 8640 | Read and write | ||||
| Set A Unnamed 8641 | Read and write | ||||
| Set A Unnamed 8650 | Read and write | ||||
| Set A Unnamed 8651 | Read and write | ||||
| Set A Unnamed 8652 | Read and write | ||||
| Set A Unnamed 8653 | Read and write | ||||
| Set A Unnamed 8660 | Read and write | ||||
| Set A Unnamed 8661 | Read and write | ||||
| Set A Unnamed 8662 | Read and write | ||||
| Set A Unnamed 8670 | Read and write | ||||
| Set A Ekip Signalling 3T 1 - Parameters Protection Enable | Read and write | ||||
| Set A Ekip Signalling 3T 1 - Parameters Protection Configuration | Read and write | ||||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 | % | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 | % | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 | % | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 hyst | % | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 hyst | % | Read and write | |||
| Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 hyst | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters Protection Enable | Read and write | ||||
| Set A Ekip Signalling 3T 2 - Parameters Protection Configuration | Read and write | ||||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 1 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 2 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 3 | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 1 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 2 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 3 hys | °C | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 1 | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 2 | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 3 | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 1 hyst | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 2 hyst | % | Read and write | |||
| Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 3 hyst | % | Read and write | |||
| Set A Voltage Stability 2 Configuration | Read and write | ||||
| Set A Voltage Stability 2 Threshold Down | Read and write | ||||
| Set A Voltage Stability 2 Threshold Up | Read and write | ||||
| Set A Voltage Stability 2 Time | s | Read and write | |||
| Set A Frequency Stability 2 Configuration | Read and write | ||||
| Set A Frequency Stability 2 Threshold Down | Read and write | ||||
| Set A Frequency Stability 2 Threshold Up | Read and write | ||||
| Set A Frequency Stability 2 Time | s | Read and write | |||
| Set A Unnamed 8750 | Read and write | ||||
| Set A Unnamed 8751 | Read and write | ||||
| Set A Unnamed 8752 | Read and write | ||||
| Set A Unnamed 8753 | Read and write | ||||
| Set A Unnamed 8754 | Read and write | ||||
| Set B Unnamed 9080 | Read and write | ||||
| Set B Unnamed 9081 | Read and write | ||||
| Set B Unnamed 9082 | Read and write | ||||
| Set B Unnamed 9090 | Read and write | ||||
| Set B Unnamed 9091 | Read and write | ||||
| Set B Unnamed 9100 | Read and write | ||||
| Set B Unnamed 9101 | Read and write | ||||
| Set B Unnamed 9102 | Read and write | ||||
| Set B Unnamed 9103 | Read and write | ||||
| Set B Unnamed 9110 | Read and write | ||||
| Set B Unnamed 9111 | Read and write | ||||
| Set B Unnamed 9112 | Read and write | ||||
| Set B Unnamed 9120 | Read and write | ||||
| Set B Ekip Signalling 3T 1 - Parameters Protection Enable | Read and write | ||||
| Set B Ekip Signalling 3T 1 - Parameters Protection Configuration | Read and write | ||||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 | % | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 | % | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 | % | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 hyst | % | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 hyst | % | Read and write | |||
| Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 hyst | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters Protection Enable | Read and write | ||||
| Set B Ekip Signalling 4T 2 - Parameters Protection Configuration | Read and write | ||||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 1 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 2 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 3 | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 1 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 2 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 3 hys | °C | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 1 | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 2 | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 3 | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 1 hyst | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 2 hyst | % | Read and write | |||
| Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 3 hyst | % | Read and write | |||
| Set B Voltage Stability 2 Configuration | Read and write | ||||
| Set B Voltage Stability 2 Threshold Down | Read and write | ||||
| Set B Voltage Stability 2 Threshold Up | Read and write | ||||
| Set B Frequency Stability 2 Configuration | Read and write | ||||
| Set B Frequency Stability 2 Threshold Down | Read and write | ||||
| Set B Frequency Stability 2 Threshold Up | Read and write | ||||
| Set B Frequency Stability 2 Time | s | Read and write | |||
| Set B Voltage Presence Configuration | Read and write | ||||
| Set B Voltage Presence Threshold Down | Read and write | ||||
| Set B Voltage Presence Threshold Up | Read and write | ||||
| Set B Voltage Presence TimeOff | s | Read and write | |||
| Set B Voltage Presence TimeOn | s | Read and write | |||
| Load Shedding DropOut voltage | Read and write | ||||
| Load Shedding Minimum Power Load | Read and write | ||||
| Load Shedding Global disable mask | Read and write | ||||
| Load Shedding Reconnection disable mask | Read and write | ||||
| Load Shedding User activation trigger | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Keep the active overload and short circuit settings of each breaker in view, so you can compare them with the selectivity study.
- Get an alarm when a protection enable flag changes, for example when earth fault protection is switched off.
- Compare set A and set B side by side before switching sets for maintenance or generator operation.
- Keep a year of setting history to show which thresholds were in force on a given day.
- Adjust an undervoltage or frequency threshold from ModbusCloud after the grid operator asks for new values.
Installation
Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and module auxiliary supply.
Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.
Note address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).
In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.
Check that the overload threshold and time match the values on the trip unit display.
Things to watch for
Why does writing a threshold return an error?
The trip unit only accepts new settings inside a programming session. Open the session with the command in the core Emax 2 template, write the values, then close it so the unit checks and stores them. Write one value at a time, check it on the display, and agree changes with whoever is responsible for the switchboard and the selectivity study.
The module does not answer at all. What should I check?
Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even parity). Swap A and B if needed and terminate the bus at both ends.
Why do thresholds show values like 0.950 instead of amps or volts?
The trip unit stores most thresholds relative to the rated current In, voltage Un, frequency Fn or power Pn. Multiply by the rated value of the breaker or installation to get amps, volts or hertz.
Some protections always read zero. Is that a fault?
Not every trip unit has every protection. Voltage, frequency, power and the second protection set depend on the trip unit version and installed functions. A protection that is not present reads zero.
Want to see how it works?