ABB ABB Emax 2 Ekip protection settings Modbus RTU template

ABB Emax 2 Ekip protection settings

Air circuit breaker trip unit with current, voltage, frequency and power protections in two setting sets.

The ABB Emax 2 with an Ekip Touch trip unit is an air circuit breaker that protects a low voltage installation against overload, short circuit, earth fault and voltage, frequency and power faults. This Modbus RTU template reads the thresholds, trip times and enable flags of every protection in set A and set B, and lets you change them from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
519, read and write
Brand
ABB
Key readings
Overload threshold and time · Short circuit thresholds · Earth fault threshold · Voltage protection thresholds · Frequency protection thresholds · Protection enable flags
Available commands
Protection thresholds · Trip times · Curve types · Protection enable flags · Unit configuration
Compatible models
Ekip Touch · Ekip Hi-Touch · Ekip G Touch · ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 with Ekip Com Modbus RTU, trip unit firmware 3.xx
Last updated

Registers (519)

519 read, 519 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Config Time Zone settingsRead and write625FC03 / FC06uint16
Config Unit configuration 2Read and write626FC03 / FC06uint16
Config Unnamed 627Read and write627FC03 / FC06uint16
Config Tag nameRead and write628FC03 / FC16string
Config User DataRead and write633FC03 / FC16string
Config StartUp Current Activation ThresholdRead and write
Config Date Of CB Installation seconds lowsRead and write
Config Date Of CB Installation seconds highsRead and write
Config LanguageRead and write
Config Neutral SelectionRead and write
Config Unit configurationRead and write
Config External Toroid configurationRead and write
Config External Toroid sizeRead and write
Config Nominal voltage / TV Primary VoltageRead and write
Config TV Secondary VoltageRead and write
Config Net FrequencyRead and write
Config Plant configRead and write
Config Monitor TimeRead and write
Config CosΦ Module ThresholdRead and write
Config Nominal voltage / TV Primary Voltage Un [V]VRead and write
Config TV Secondary Voltage [V]VRead and write
Config Open/Close CB Pulse DurationmsRead and write
Config MDGF In SizeARead and write
Config Unnamed 656Read and write
Config Unnamed 657Read and write
Set A L ConfigurationRead and write
Set A L Threshold l1Read and write
Set A L Time t1sRead and write
Set A L Curve TypeRead and write
Set A L Threshold Iec255Read and write
Set A L Time Iec255sRead and write
Set A L Prealarm Threshold l1%Read and write
Set A L TM Custom TimesRead and write
Set A S ConfigurationRead and write
Set A S Threshold I2 (I2t=k)Read and write
Set A S Time t2 (I2t=k)sRead and write
Set A S Threshold I2 (t=k)Read and write
Set A S Time t2 (t=k)sRead and write
Set A S Curve TypeRead and write
Set A S Startup ThresholdRead and write
Set A S Startup TimesRead and write
Set A S Zone Selectivity TimesRead and write
Set A I ConfigurationRead and write
Set A I Threshold I3Read and write
Set A I Startup ThresholdRead and write
Set A I Startup TimesRead and write
Set A G ConfigurationRead and write
Set A G Threshold I4 (I2t=k)Read and write
Set A G Time t4 (I2t=k)sRead and write
Set A G Threshold I4 (t=k)Read and write
Set A G Time t4 (t=k)sRead and write
Set A G Curve TypeRead and write
Set A G Startup ThresholdRead and write
Set A G Startup TimesRead and write
Set A G Zone Selectivity TimesRead and write
Set A S2 ConfigurationRead and write
Set A S2 Threshold I5 (t=k)Read and write
Set A S2 Time t5 t=ksRead and write
Set A S2 Startup ThresholdRead and write
Set A S2 Startup TimesRead and write
Set A S2 Zone Selectivity TimesRead and write
Set A Gext ConfigurationRead and write
Set A Gext Threshold I41 (I2t=k)Read and write
Set A Gext Time t41 (I2t=k)sRead and write
Set A Gext Threshold I41 (t=k)Read and write
Set A Gext Time t41 (t=k)sRead and write
Set A Gext Curve TypeRead and write
Set A Gext Startup ThresholdRead and write
Set A Gext Startup TimesRead and write
Set A Gext Zone Selectivity TimesRead and write
Set A D ConfigurationRead and write
Set A D Threshold I7 ForwardRead and write
Set A D Time t7 ForwardsRead and write
Set A D Time t7 BackwardsRead and write
Set A D Startup Threshold ForwardRead and write
Set A D Startup TimesRead and write
Set A D Zone Selectivity Time ForwardsRead and write
Set A D Direction Minimum AngleRead and write
Set A IU ConfigurationRead and write
Set A IU Threshold I6Read and write
Set A IU Time t6sRead and write
Set A UV ConfigurationRead and write
Set A UV Threshold U8Read and write
Set A UV Time t8sRead and write
Set A Voltage Stability ConfigurationRead and write
Set A Voltage Stability Threshold DownRead and write
Set A Voltage Stability Threshold UpRead and write
Set A Voltage Stability TimesRead and write
Set A OV ConfigurationRead and write
Set A OV Threshold U9Read and write
Set A OV Time t9sRead and write
Set A Unnamed 795Read and write
Set A Unnamed 796Read and write
Set A Unnamed 797sRead and write
Set A RV ConfigurationRead and write
Set A RV Threshold U22Read and write
Set A RV Time t22sRead and write
Set A RV Reset TimesRead and write
Set A RP ConfigurationRead and write
Set A RP Threshold P11Read and write
Set A RP Time t11sRead and write
Set A UF ConfigurationRead and write
Set A UF Threshold f12Read and write
Set A UF Time t12sRead and write
Set A Frequency Stability ConfigurationRead and write
Set A Frequency Stability Threshold DownRead and write
Set A Frequency Stability Threshold UpRead and write
Set A Frequency Stability TimesRead and write
Set A OF ConfigurationRead and write
Set A OF Threshold f13Read and write
Set A OF Time t13sRead and write
Set A T ConfigurationRead and write
Set A Unnamed 845Read and write
Set A Unnamed 846Read and write
Set A Unnamed 847Read and write
Set A Rc ConfigurationRead and write
Set A Rc IdnRead and write
Set A Rc tdnRead and write
Set A LC IW ConfigurationRead and write
Set A LC IW Iw1 ThresholdRead and write
Set A LC IW Iw2 ThresholdRead and write
Set A LC IW LC1 ThresholdRead and write
Set A LC IW LC2 ThresholdRead and write
Set A MCR ConfigurationRead and write
Set A MCR I3Read and write
Set A MCR Monitor TimesRead and write
Set A VU ConfigurationRead and write
Set A VU Threshold U14Read and write
Set A VU Time t14sRead and write
Set A OP ConfigurationRead and write
Set A OP Threshold P26Read and write
Set A OP Time t26sRead and write
Set A S(V) ConfigurationRead and write
Set A S(V) TypeRead and write
Set A S(V) Threshold I20Read and write
Set A S(V) Time t20sRead and write
Set A S(V) Threshold Uh (linear mode)VRead and write
Set A S(V) Threshold UI (linear mode)VRead and write
Set A S(V) Threshold UI (step mode)VRead and write
Set A S(V) Threshold KsRead and write
Set A RQ ConfigurationRead and write
Set A RQ Threshold KqRead and write
Set A RQ Threshold -Q24Read and write
Set A RQ Threshold Kq2Read and write
Set A RQ Threshold -Q25Read and write
Set A RQ Time t24sRead and write
Set A RQ Threshold V minRead and write
Set A ROCOF ConfigurationRead and write
Set A ROCOF Threshold f28HzRead and write
Set A ROCOF Trip DirectionRead and write
Set A ROCOF Time t28sRead and write
Set A S2(V) ConfigurationRead and write
Set A S2(V) TypeRead and write
Set A S2(V) Threshold I21Read and write
Set A S2(V) Time t21sRead and write
Set A S2(V) Threshold Uh2 (linear mode)VRead and write
Set A S2(V) Threshold UI2 (linear mode)VRead and write
Set A S2(V) Threshold UI2 (step mode)VRead and write
Set A S2(V) Threshold Ks2Read and write
Set A OQ ConfigurationRead and write
Set A OQ Threshold Q27Read and write
Set A OQ Time t27Read and write
Set A UP ConfigurationRead and write
Set A UP Threshold P23Read and write
Set A UP Time t23sRead and write
Set A UP StartUp TimesRead and write
Set A UV 2 ConfigurationRead and write
Set A UV 2 Threshold U15Read and write
Set A UV 2 Time t15sRead and write
Set A OV 2 ConfigurationRead and write
Set A OV 2 Threshold U16Read and write
Set A OV 2 Time t16sRead and write
Set A UF 2 ConfigurationRead and write
Set A UF 2 Threshold f17Read and write
Set A UF 2 Time t17sRead and write
Set A OF 2 ConfigurationRead and write
Set A OF 2 Threshold f18Read and write
Set A OF 2 Time t18sRead and write
Set A D Advanced Threshold BackwardRead and write
Set A D Advanced Startup Threshold BackwardRead and write
Set A D Advanced Zone Selectivity Time BackwardsRead and write
Set A G Advanced Prealarm Threshold%Read and write
Set A G Advanced Unnamed 1011ARead and write
Set A G Advanced Unnamed 1012ARead and write
Set A G Advanced Unnamed 1013ARead and write
Set A Gext Advanced Prealarm Threshold%Read and write
Set A 2I ConfigurationRead and write
Set A 2I Threshold I31%Read and write
Set A Unnamed 1040Read and write
Set A Unnamed 1041Read and write
Set A Unnamed 1045Read and write
Set A Unnamed 1046Read and write
Set B L ConfigurationRead and write
Set B L Threshold l1Read and write
Set B L Time t1sRead and write
Set B L Curve TypeRead and write
Set B L Threshold Iec255Read and write
Set B L Time Iec255sRead and write
Set B L Prealarm Threshold l1%Read and write
Set B L TM Custom TimesRead and write
Set B S ConfigurationRead and write
Set B S Threshold I2 (I2t=k)Read and write
Set B S Time t2 (I2t=k)sRead and write
Set B S Threshold I2 (t=k)Read and write
Set B S Time t2 (t=k)sRead and write
Set B S Curve TypeRead and write
Set B S Startup ThresholdRead and write
Set B S Startup TimesRead and write
Set B S Zone Selectivity TimesRead and write
Set B I ConfigurationRead and write
Set B I Threshold I3Read and write
Set B I Startup ThresholdRead and write
Set B I Startup TimesRead and write
Set B G ConfigurationRead and write
Set B G Threshold I4 (I2t=k)Read and write
Set B G Time t4 (I2t=k)sRead and write
Set B G Threshold I4 (t=k)Read and write
Set B G Time t4 (t=k)sRead and write
Set B G Curve TypeRead and write
Set B G Startup ThresholdRead and write
Set B G Startup TimesRead and write
Set B G Zone Selectivity TimesRead and write
Set B S2 ConfigurationRead and write
Set B S2 Threshold I5 (t=k)Read and write
Set B S2 Time t5 t=ksRead and write
Set B S2 Startup ThresholdRead and write
Set B S2 Startup TimesRead and write
Set B S2 Zone Selectivity TimesRead and write
Set B Gext ConfigurationRead and write
Set B Gext Threshold I41 (I2t=k)Read and write
Set B Gext Time t41 (I2t=k)sRead and write
Set B Gext Threshold I41 (t=k)Read and write
Set B Gext Time t41 (t=k)sRead and write
Set B Gext Curve TypeRead and write
Set B Gext Startup ThresholdRead and write
Set B Gext Startup TimesRead and write
Set B Gext Zone Selectivity TimesRead and write
Set B D ConfigurationRead and write
Set B D Threshold I7 ForwardRead and write
Set B D Time t7 ForwardsRead and write
Set B D Time t7 BackwardsRead and write
Set B D Startup Threshold ForwardRead and write
Set B D Startup TimesRead and write
Set B D Zone Selectivity Time ForwardsRead and write
Set B D Direction Minimum AngleRead and write
Set B IU ConfigurationRead and write
Set B IU Threshold I6Read and write
Set B IU Time t6sRead and write
Set B UV ConfigurationRead and write
Set B UV Threshold U8Read and write
Set B UV Time t8sRead and write
Set B Voltage Stability ConfigurationRead and write
Set B Voltage Stability Threshold DownRead and write
Set B Voltage Stability Threshold UpRead and write
Set B Voltage Stability TimesRead and write
Set B OV ConfigurationRead and write
Set B OV Threshold U9Read and write
Set B OV Time t9sRead and write
Set B Unnamed 1245Read and write
Set B Unnamed 1246Read and write
Set B Unnamed 1247sRead and write
Set B RV ConfigurationRead and write
Set B RV Threshold U22Read and write
Set B RV Time t22sRead and write
Set B RV Reset TimesRead and write
Set B RP ConfigurationRead and write
Set B RP Threshold P11Read and write
Set B RP Time t11sRead and write
Set B UF ConfigurationRead and write
Set B UF Threshold f12Read and write
Set B UF Time t12sRead and write
Set B Frequency Stability ConfigurationRead and write
Set B Frequency Stability Threshold DownRead and write
Set B Frequency Stability Threshold UpRead and write
Set B Frequency Stability TimesRead and write
Set B OF ConfigurationRead and write
Set B OF Threshold f13Read and write
Set B OF Time t13sRead and write
Set B ConfigurationRead and write
Set B Unnamed 1295Read and write
Set B Unnamed 1296Read and write
Set B Unnamed 1297Read and write
Set B Rc ConfigurationRead and write
Set B Rc IdnRead and write
Set B Rc tdnRead and write
Set B LC IW ConfigurationRead and write
Set B LC IW Iw1 ThresholdRead and write
Set B LC IW Iw2 ThresholdRead and write
Set B LC IW LC1 ThresholdRead and write
Set B LC IW LC2 ThresholdRead and write
Set B Configuration 1320Read and write
Set B I3Read and write
Set B Monitor TimesRead and write
Set B VU ConfigurationRead and write
Set B VU Threshold U14Read and write
Set B VU Time t14sRead and write
Set B OP ConfigurationRead and write
Set B OP Threshold P26Read and write
Set B OP Time t26sRead and write
Set B S(V) ConfigurationRead and write
Set B S(V) TypeRead and write
Set B S(V) Threshold I20Read and write
Set B S(V) Time t20sRead and write
Set B S(V) Threshold Uh (linear mode)VRead and write
Set B S(V) Threshold UI (linear mode)VRead and write
Set B S(V) Threshold UI (step mode)VRead and write
Set B S(V) Threshold KsRead and write
Set B RQ ConfigurationRead and write
Set B RQ Threshold KqRead and write
Set B RQ Threshold -Q24Read and write
Set B RQ Threshold Kq2Read and write
Set B RQ Threshold -Q25Read and write
Set B RQ Time t24sRead and write
Set B RQ Threshold V minRead and write
Set B ROCOF ConfigurationRead and write
Set B ROCOF Threshold f28HzRead and write
Set B ROCOF Trip DirectionRead and write
Set B ROCOF Time t28sRead and write
Set B S2(V) ConfigurationRead and write
Set B S2(V) TypeRead and write
Set B S2(V) Threshold I21Read and write
Set B S2(V) Time t21sRead and write
Set B S2(V) Threshold Uh2 (linear mode)VRead and write
Set B S2(V) Threshold UI2 (linear mode)VRead and write
Set B S2(V) Threshold UI2 (step mode)VRead and write
Set B S2(V) Threshold Ks2Read and write
Set B OQ ConfigurationRead and write
Set B OQ Threshold Q27Read and write
Set B OQ Time t27Read and write
Set B UP ConfigurationRead and write
Set B UP Threshold P23Read and write
Set B UP Time t23sRead and write
Set B UP StartUp TimesRead and write
Set B UV 2 ConfigurationRead and write
Set B UV 2 Threshold U15Read and write
Set B UV 2 Time t15sRead and write
Set B OV 2 ConfigurationRead and write
Set B OV 2 Threshold U16Read and write
Set B OV 2 Time t16sRead and write
Set B UF 2 ConfigurationRead and write
Set B UF 2 Threshold f17Read and write
Set B UF 2 Time t17sRead and write
Set B OF 2 ConfigurationRead and write
Set B OF 2 Threshold f18Read and write
Set B OF 2 Time t18sRead and write
Set B D Advanced Threshold BackwardRead and write
Set B D Advanced Startup Threshold BackwardRead and write
Set B D Advanced Zone Selectivity Time BackwardsRead and write
Set B G Advanced Prealarm Threshold%Read and write
Set B G Advanced Unnamed 1461ARead and write
Set B G Advanced Unnamed 1462ARead and write
Set B G Advanced Unnamed 1463ARead and write
Set B Gext Advanced Prealarm Threshold%Read and write
Set B 2I ConfigurationRead and write
Set B 2I Threshold I31%Read and write
Set B Unnamed 1490Read and write
Set B Unnamed 1491Read and write
Set B Unnamed 1495Read and write
Set B Unnamed 1496Read and write
Set A Unnamed 8630Read and write
Set A Unnamed 8631Read and write
Set A Unnamed 8632Read and write
Set A Unnamed 8640Read and write
Set A Unnamed 8641Read and write
Set A Unnamed 8650Read and write
Set A Unnamed 8651Read and write
Set A Unnamed 8652Read and write
Set A Unnamed 8653Read and write
Set A Unnamed 8660Read and write
Set A Unnamed 8661Read and write
Set A Unnamed 8662Read and write
Set A Unnamed 8670Read and write
Set A Ekip Signalling 3T 1 - Parameters Protection EnableRead and write
Set A Ekip Signalling 3T 1 - Parameters Protection ConfigurationRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1%Read and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2%Read and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3%Read and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 hyst%Read and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 hyst%Read and write
Set A Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 hyst%Read and write
Set A Ekip Signalling 3T 2 - Parameters Protection EnableRead and write
Set A Ekip Signalling 3T 2 - Parameters Protection ConfigurationRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 1°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 2°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 3°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 1 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 1°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 2°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 3°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 2 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 1°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 2°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 3°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 1 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 2 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters PT1000 3 threshold 3 hys°CRead and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 1%Read and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 2%Read and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 3%Read and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 1 hyst%Read and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 2 hyst%Read and write
Set A Ekip Signalling 3T 2 - Parameters 4-20 mA threshold 3 hyst%Read and write
Set A Voltage Stability 2 ConfigurationRead and write
Set A Voltage Stability 2 Threshold DownRead and write
Set A Voltage Stability 2 Threshold UpRead and write
Set A Voltage Stability 2 TimesRead and write
Set A Frequency Stability 2 ConfigurationRead and write
Set A Frequency Stability 2 Threshold DownRead and write
Set A Frequency Stability 2 Threshold UpRead and write
Set A Frequency Stability 2 TimesRead and write
Set A Unnamed 8750Read and write
Set A Unnamed 8751Read and write
Set A Unnamed 8752Read and write
Set A Unnamed 8753Read and write
Set A Unnamed 8754Read and write
Set B Unnamed 9080Read and write
Set B Unnamed 9081Read and write
Set B Unnamed 9082Read and write
Set B Unnamed 9090Read and write
Set B Unnamed 9091Read and write
Set B Unnamed 9100Read and write
Set B Unnamed 9101Read and write
Set B Unnamed 9102Read and write
Set B Unnamed 9103Read and write
Set B Unnamed 9110Read and write
Set B Unnamed 9111Read and write
Set B Unnamed 9112Read and write
Set B Unnamed 9120Read and write
Set B Ekip Signalling 3T 1 - Parameters Protection EnableRead and write
Set B Ekip Signalling 3T 1 - Parameters Protection ConfigurationRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 1 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 2 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 1 threshold 3 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 1 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 2 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 2 threshold 3 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 1 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 2 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters PT1000 3 threshold 3 hys°CRead and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1%Read and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2%Read and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3%Read and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 1 hyst%Read and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 2 hyst%Read and write
Set B Ekip Signalling 3T 1 - Parameters 4-20 mA threshold 3 hyst%Read and write
Set B Ekip Signalling 4T 2 - Parameters Protection EnableRead and write
Set B Ekip Signalling 4T 2 - Parameters Protection ConfigurationRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 1°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 2°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 3°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 1 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 2 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 1 threshold 3 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 1°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 2°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 3°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 1 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 2 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 2 threshold 3 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 1°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 2°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 3°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 1 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 2 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters PT1000 3 threshold 3 hys°CRead and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 1%Read and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 2%Read and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 3%Read and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 1 hyst%Read and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 2 hyst%Read and write
Set B Ekip Signalling 4T 2 - Parameters 4-20 mA threshold 3 hyst%Read and write
Set B Voltage Stability 2 ConfigurationRead and write
Set B Voltage Stability 2 Threshold DownRead and write
Set B Voltage Stability 2 Threshold UpRead and write
Set B Frequency Stability 2 ConfigurationRead and write
Set B Frequency Stability 2 Threshold DownRead and write
Set B Frequency Stability 2 Threshold UpRead and write
Set B Frequency Stability 2 TimesRead and write
Set B Voltage Presence ConfigurationRead and write
Set B Voltage Presence Threshold DownRead and write
Set B Voltage Presence Threshold UpRead and write
Set B Voltage Presence TimeOffsRead and write
Set B Voltage Presence TimeOnsRead and write
Load Shedding DropOut voltageRead and write
Load Shedding Minimum Power LoadRead and write
Load Shedding Global disable maskRead and write
Load Shedding Reconnection disable maskRead and write
Load Shedding User activation triggerRead and write

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Keep the active overload and short circuit settings of each breaker in view, so you can compare them with the selectivity study.
  • Get an alarm when a protection enable flag changes, for example when earth fault protection is switched off.
  • Compare set A and set B side by side before switching sets for maintenance or generator operation.
  • Keep a year of setting history to show which thresholds were in force on a given day.
  • Adjust an undervoltage or frequency threshold from ModbusCloud after the grid operator asks for new values.

Installation

  1. Fit the Ekip Com Modbus RTU module in the Emax 2 terminal box and give the trip unit and module auxiliary supply.

  2. Wire the RS485 pair of the module to RS485 A and B of the ModbusCloud Gateway and terminate the bus with 120 ohm at both ends.

  3. Note address, baud rate and parity on the Ekip Touch display (default 247, 19200, even parity).

  4. In ModbusCloud, add a Modbus device with the same settings, or use the device of the core Emax 2 template, and import this template.

  5. Check that the overload threshold and time match the values on the trip unit display.

Things to watch for

Why does writing a threshold return an error?

The trip unit only accepts new settings inside a programming session. Open the session with the command in the core Emax 2 template, write the values, then close it so the unit checks and stores them. Write one value at a time, check it on the display, and agree changes with whoever is responsible for the switchboard and the selectivity study.

The module does not answer at all. What should I check?

Check the auxiliary supply of the Ekip Com module and that address, baud rate and parity match the Gateway (default 247, 19200, even parity). Swap A and B if needed and terminate the bus at both ends.

Why do thresholds show values like 0.950 instead of amps or volts?

The trip unit stores most thresholds relative to the rated current In, voltage Un, frequency Fn or power Pn. Multiply by the rated value of the breaker or installation to get amps, volts or hertz.

Some protections always read zero. Is that a fault?

Not every trip unit has every protection. Voltage, frequency, power and the second protection set depend on the trip unit version and installed functions. A protection that is not present reads zero.

Want to see how it works?